White paperFree to read2023

A Quantitative Comparison of UPS Monitoring and Servicing Approaches Across Edge Environments

Schneider Electric · Wendy Torell

Schneider Electric WP 283 (2023) compares monitoring and servicing of single-phase UPS fleets spread over many unstaffed edge sites, in four options depending on whether the owner or a third party does each, using a cost model.

On this page

Overview

The monitoring spectrum runs from none through physical inspection to basic and advanced remote monitoring, and the servicing spectrum from run-to-fail through calendar-based to condition-based maintenance. The authors recommend advanced monitoring and condition-based service: once a battery fails its self-test there are weeks to months left to replace it proactively. Model assumptions are VRLA batteries with 3-5 year life (Li-ion typically 10-12 years), a 3-year factory warranty, and parts cost for out-of-warranty repairs taken as a replacement battery.

Default annual share of UPSs with failure events by age: 0-1 yr 2%, 1-2 yr 1%, 2-3 yr 2%, 3-4 yr 10%, 4-5 yr 30%, over 5 yr 35%. Scenario inputs: 100 sites, 1000 VA UPSs, $100k per person staff cost, $1000 technician and travel per failure, 50% of failures cause downtime, 60 minutes per event, 80% of downtime avoided with a third party, and $30 per minute downtime.

Annual cost, self-managed versus third party: 0-4 yr fleet $28.1k vs $28.3k (under 1% premium); 2-6 yr fleet $61.2k vs $51.3k (16% saving); staff time at 20% $81.2k vs $51.3k (37% saving); with no downtime cost $63.2k vs $47.7k (25% saving). So outsourcing is roughly break-even for a young fleet and saves 16-37% for older ones. A typical truck-roll dispatch is cited at $1000.

Key points

  1. Assumptions: VRLA 3-5 years, Li-ion 10-12 years, 3-year warranty.
  2. Annual failure share: 0-1 yr 2%, 1-2 yr 1%, 2-3 yr 2%, 3-4 yr 10%, 4-5 yr 30%, over 5 yr 35%.
  3. Scenario: 100 sites, 1000 VA UPSs, $100k per person, $1000 per failure, $30/min downtime, 80% of downtime avoided.
  4. 0-4 yr fleet: $28.1k self-managed vs $28.3k third party, under 1% difference.
  5. 2-6 yr fleet: $61.2k vs $51.3k, 16% saving.
  6. Staff time 20%: $81.2k vs $51.3k, 37% saving; no downtime cost: 25% saving.
  7. In condition-based service, weeks to months remain to replace a battery after a failed self-test.
  8. Typical truck-roll cost is $1000.

Using it in design

  • Calculate UPS fleet lifecycle and operating costs from site count, UPS VA, battery chemistry, installation-year distribution, warranty, service travel, staffing and downtime cost per minute.
  • Use the Table 3 age-failure curve as the default editable profile.
  • Record battery chemistry, design life, warranty duration and whether a network card is included.
  • Warn when an edge UPS has no network management card or when planned battery replacement intervals exceed the chemistry's expected life, and generate a battery-replacement schedule in the maintenance export.

Who should read it

Owners deciding whether to run single-phase UPS fleets across many remote sites in-house or through a provider.

Publication details

Authors
Wendy Torell
Publisher
Schneider Electric
Year
2023
Document number
WP 283
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Wendy Torell (2023). A Quantitative Comparison of UPS Monitoring and Servicing Approaches Across Edge Environments. Schneider Electric. WP 283. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP283_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.