Considerations for Selecting a Lithium-ion Battery System for UPSs and Energy Storage Systems
Schneider Electric · Scott Daniels
This paper explains the variables that drive lithium-ion battery decisions for UPS and storage: chemistry, C-rate, depth of discharge, cycle and calendar life, round-trip efficiency and temperature. It prepares buyers for vendor trade-offs rather than giving a design procedure.
On this page
Overview
The paper explains the variables that drive lithium-ion battery system decisions: cathode chemistry (NMC, LFP, NCA, LTO), C-rate, depth of discharge, cycle life, calendar life, round-trip efficiency and temperature. The common cathode chemistries for UPS and energy storage systems are named as NMC, LFP and NCA. The text aims to prepare buyers for vendor trade-offs rather than to give a design procedure.
An important section shows that short-runtime UPS discharges extract only a fraction of a lead-acid battery's nominal energy. Lead-acid energy extraction is about 100% at the 20-hour rate but about 33% at the 5-minute rate. A lead-acid battery priced at $100/kWh with 33% extraction is therefore effectively about $300/kWh, which changes simple cost comparisons. Comparisons across chemistries and vendors therefore need to use the same assumptions throughout, or they can mislead.
The end-of-life definition also affects comparison: typically 80% of initial capacity is used in automotive applications and 70% in stationary ones. A UPS loaded at 50% gets more than double its full-load runtime (for example more than 20 minutes). A limit is that the paper gives no numerical design method for a specific product or system, so results must be checked against chemistry and manufacturer data.
Key points
- End of life: typically 80% of initial capacity (automotive) and 70% (stationary).
- Lead-acid energy extraction is about 100% at the 20-hour rate but about 33% at the 5-minute rate.
- Example: $100/kWh lead-acid at 33% extraction is effectively about $300/kWh.
- A UPS loaded at 50% gets more than double the full-load runtime (for example more than 20 minutes).
- Common cathode chemistries for UPS and ESS: NMC, LFP, NCA.
Using it in design
- Use C-rate-dependent usable energy (Peukert-like) in the battery runtime calculation rather than nameplate kWh.
- Record the following selection criteria: chemistry, maximum C-rate, cycle life, calendar life, round-trip efficiency, end-of-life percentage.
- For dual-use UPS/BESS, make cycle life a required input.
Who should read it
Buyers and designers selecting a lithium-ion battery system for UPS and energy storage.
Related standards
- IEC 62619
- IEC 62040-1
- UL 1973
- UL 9540A
Publication details
- Authors
- Scott Daniels
- Publisher
- Schneider Electric
- Year
- 2020
- Document number
- WP 284
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Scott Daniels (2020). Considerations for Selecting a Lithium-ion Battery System for UPSs and Energy Storage Systems. Schneider Electric. WP 284. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP284_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.