AC vs. DC Power Distribution for Data Centers
Schneider Electric · Neil Rasmussen
Neil Rasmussen's paper models end-to-end electrical efficiency at 50% load for five distribution options and recommends 400/230 V AC with high-efficiency UPS and power supplies for new builds.
On this page
Overview
The options compared are North American 480/208 V AC with PDU transformers, 400/230 V AC, 48 V DC, 380 V DC and a hybrid 575 V DC system. At 50% load the product of UPS, distribution and IT power-supply efficiency comes out at 83.56% for 480 to 208 V AC, 86.39% for 400/230 V AC, 80.74% for 48 V DC, 87.64% for 380 V DC and 80.74% for hybrid 575 V DC. The paper attributes many published DC advantages to outdated AC efficiency assumptions.
It grants that 380 V DC may offer about a 1% efficiency edge over the best AC system at full load, about 1.5% less rack heat and about 10% copper saving (9.5 kW per wire against 8.625 kW for 400/230 V AC with 50 A wiring). Wiring conduction losses are insignificant in real data centres because load diversity keeps circuits well below rating. DC UPS cost is typically 10% to 20% lower than AC UPS, but 48 V DC distribution needs 10X or more copper weight and cost and is impractical above 20 kW per cabinet.
Safety and compliance are weighed too: 380 V DC would not be legal in Japan, where the regulatory limit is 300 V, and North America has no arc-flash regulations for commercial DC. In hosting sites with much telecom equipment, the 48 V DC requirement may reach 10% of the AC requirement, and point-of-use battery-less rack rectifiers are recommended. The conclusion is that the North American 480 V AC system with PDU transformers should be viewed as inefficient and obsolete for new designs.
Key points
- Overall efficiency at 50% load (UPS x distribution x IT PSU): 480 to 208 V AC 83.56%; 400/230 V AC 86.39%; 48 V DC 80.74%; 380 V DC 87.64%; hybrid 575 V DC 80.74%.
- Wiring conduction losses are insignificant in real data centres because load diversity keeps circuits well below rating, though wire sizing must still meet the worst case.
- 380 V DC may offer about 1% efficiency over the best AC system at full load, about 1.5% less rack heat and about 10% copper saving (9.5 kW per wire vs 8.625 kW).
- DC UPS cost is typically 10-20% below AC UPS, but 48 V DC distribution needs 10X or more copper weight and cost and is impractical above 20 kW per cabinet.
- 380 V DC would be illegal in Japan, where the limit is 300 V; North America has no arc-flash regulation for commercial DC.
- In hosting sites with much telecom equipment the 48 V DC need may reach 10% of the AC need; point-of-use battery-less rack rectifiers are recommended.
- The paper calls the North American 480 V AC system with PDU transformers inefficient and obsolete for new designs.
Using it in design
- Multiply UPS, transformer/PDU, distribution and PSU efficiencies at operating load. State the assumptions when comparing the five architectures with Table 1 values.
- In North American projects, suggest 415/240 V distribution to eliminate PDU transformers.
- Warn when 48 V DC busway is proposed above 20 kW per cabinet, or when DC distribution exceeds a local regulatory voltage limit (for example 300 V in Japan).
- For PDU selection, record hasTransformer flag and a part-load efficiency curve.
Who should read it
Electrical designers choosing the distribution voltage and UPS architecture of a new facility.
Related standards
- IEC 60364
- NFPA 70
Publication details
- Authors
- Neil Rasmussen
- Publisher
- Schneider Electric
- Year
- 2011
- Document number
- WP 63
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Neil Rasmussen (2011). AC vs. DC Power Distribution for Data Centers. Schneider Electric. WP 63. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_SADE-5TNRLG_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.