Real-Time Thermal Symmetry Control of Data Centers Based on Distributed Optical Fiber Sensing and Model Predictive Control

Symmetry / MDPI · Lin-Xiang Tang, Mu-Jiang-Shan Wang

A 2026 Symmetry paper using distributed fibre temperature sensing and MPC in a production data centre cuts daily cooling energy by 14.4%, lowers PUE from 1.58 to 1.47 and reduces the Thermal Symmetry Index from 0.060 to 0.035.

On this page

Overview

Tang and Wang treat the high energy use and spatiotemporal thermal asymmetry of data centre cooling as a bottleneck for sustainable development. Point-type temperature sensors lack spatial coverage and conventional feedback control responds late and adapts poorly under dynamic workloads. The proposed framework combines Brillouin scattering-based distributed sensing, collecting dense temperature measurements from thousands of points along a single optical fibre, with model predictive control (MPC).

A hybrid prediction model integrating thermodynamic equations with a TCN-BiGRU deep neural network is developed, and a symmetry-aware MPC controller is designed to minimise cooling energy while suppressing thermal field deviation. Experimental validation in a production data centre ran July to September 2024 in East China; raw data are withheld because of partner agreements and site security. The Thermal Symmetry Index (TSI) is the ratio of spatial temperature standard deviation to mean temperature.

Key points

  1. The distributed sensing system achieves a measurement deviation of 0.12 degrees C.
  2. The hybrid prediction model gives an RMSE of 0.41 degrees C, a 26.8% improvement over baseline methods.
  3. The MPC strategy reduces daily cooling energy consumption by 14.4%.
  4. PUE falls from 1.58 to 1.47.
  5. The Thermal Symmetry Index falls from 0.060 to 0.035, a 41.7% improvement in spatial temperature uniformity.
  6. TSI < 0.03 is read as excellent, 0.03-0.05 as good and > 0.08 as significant asymmetry needing intervention.
  7. The experimental campaign ran July to September 2024 in a production data centre in East China.

Using it in design

  • Consider distributed fibre sensing instead of or alongside point sensors for fine-grained thermal field visibility.
  • Add thermal symmetry (such as TSI) to the objective function of cooling control together with the energy target.
  • Evaluate model predictive control as an alternative to feedback control under dynamic workloads.
  • Use the TSI thresholds (0.03 and 0.05) as a reference for operating alarm levels.

Who should read it

Engineers and researchers designing data centre temperature monitoring and cooling control.

Publication details

Authors
Lin-Xiang Tang; Mu-Jiang-Shan Wang
Publisher
Symmetry / MDPI
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Article-specific CC BY 4.0 notice verified on the publisher page. Retain attribution, license link and change notices; third-party exceptions require separate review. Generic MDPI dc.rights metadata may say BY 3.0; the article-specific notice takes precedence. Round 5/6 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Lin-Xiang Tang; Mu-Jiang-Shan Wang (2026). Real-Time Thermal Symmetry Control of Data Centers Based on Distributed Optical Fiber Sensing and Model Predictive Control. Symmetry / MDPI. https://doi.org/10.3390/sym18030398

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.