Tesar Cast Resin Transformers: Ecodesign Technical Catalogue

Tesar / R&S Group · Tesar

The Tesar catalogue gives losses, efficiency and dimensions for 100-3150 kVA EU 548/2014 Ecodesign phase 2 cast resin transformers; at 1000 kVA / 12 kV no-load loss is 1395 W and load loss 9000 W.

On this page

Overview

Tesar is an Italian cast resin (dry-type) transformer manufacturer founded in 1979. The catalogue presents its range, from standard distribution transformers up to power transformers of 20 MVA / 52 kV, plus rectifier, traction and multi-winding renewable-energy units. The focus is transformers compliant with the EU Ecodesign regulation 548/2014; lower-loss design is argued on the grounds that operating cost outweighs purchase price over the product life.

For the economics the catalogue states that more than 80% of a transformer's total cost is operating cost, mostly losses, that average life is 30 years and that transformers are energised 24 hours a day, 365 days a year. The legislation section covers IEC 60076-11:2018, EN 50588-1 (2015) and 548/2014: the regulation sets maximum no-load and load losses up to 3150 kVA and a Peak Efficiency Index (PEI) for larger ratings, applied in two phases from 1 July 2015 and 1 July 2021.

The technical tables are separate for 12, 17.5 and 24 kV primary classes. Common data: 400 V secondary, 50 Hz, Dyn11 or Dyn5, AL/AL windings, AN cooling, F/F insulation class, 100/100 K temperature rise, 40 °C ambient, altitude below 1000 m, IP00 and ±2x2.5% taps. For each rating the Extra-EU design and the Ecodesign phase 2 model are listed side by side, so differences in loss, efficiency, sound and weight read directly.

A sample comparison at 12 kV, 1000 kVA: the Extra-EU design has 2400 W no-load loss, 10800 W load loss and 2100 kg; Ecodesign phase 2 has 1395 W, 9000 W and 3050 kg. Efficiency is 98.97% (full load, cos φ 1) and 99.15% (75% load). The Ecodesign model is more efficient and quieter (51 dB LpA against 60 dB) but heavier and larger. The catalogue also lists E2-C2-F1 and E4-C3-F1 class certificates, IP31/IP23 metal enclosures and accessories.

Key points

  1. Ratings 100 to 3150 kVA; separate tables for 12, 17.5 and 24 kV primary; secondary 400 V, Dyn11-Dyn5.
  2. EU 548/2014 Ecodesign: maximum loss limits up to 3150 kVA, PEI above; phases July 2015 and July 2021.
  3. 12 kV, 1000 kVA Ecodesign phase 2: Po 1395 W, Pk 9000 W (120 °C), Uk 6%, Io 1.0%, efficiency 98.97% / 99.15%, 51 dB LpA, 3050 kg.
  4. Same rating, Extra-EU design: Po 2400 W, Pk 10800 W, 60 dB LpA, 2100 kg.
  5. 12 kV, 3150 kVA Ecodesign phase 2: Po 3420 W, Pk 22000 W, Uk 8%, efficiency 99.20% / 99.34%.
  6. For phase 2 units with dual primary voltage, no-load loss rises 15% and load loss 10%; rated power refers to the lower voltage.
  7. Common data: AN cooling, class F insulation, 100 K rise, 40 °C, IP00, altitude below 1000 m.
  8. The catalogue holds operating cost at over 80% of total cost and life at 30 years.

Using it in design

  • When choosing a transformer, take no-load and load losses (Po, Pk) from the table, not only the rating, and compute annual loss energy from the loading profile; continuous 24/365 operation in a data centre raises the weight of Po.
  • Feed the weight and size penalty of the Ecodesign model (for example 3050 kg against 2100 kg at 1000 kVA) into electrical-room floor loading and layout.
  • Note the sound level (LpA 51 dB at 1000 kVA) and that IP00 means open windings; ask for an IP31 or IP23 enclosure where needed and for derating above 40 °C ambient.
  • Use the Uk value (for example 6%) as an input to short-circuit current and selectivity calculations.
  • If dual primary voltage is required, add the 15% and 10% increases in Po and Pk to the loss budget.

Who should read it

Data-centre and building electrical designers, engineers writing transformer specifications and energy-efficiency consultants.

Document contents

  1. Our Brand Story
  2. Energy
  3. Reference Legislation, Norms and Standards
  4. Our Proposal
  5. Technical Details (12, 17.5, 24 kV)
  6. A World of Reliability
  7. Special Applications
  8. Metal Enclosures
  9. Our Accessories
  10. Description and Features
  11. Certified Quality
  12. Environmental, Climate and Fire-resistance Classes
  13. Customer-care and After-sales Service
  14. Sustainability
  15. Test Room

Publication details

Authors
Tesar
Publisher
Tesar / R&S Group
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Tesar Tesar Cast Resin Transformers: Ecodesign Technical Catalogue. Tesar / R&S Group. https://the-rsgroup.com/wp-content/uploads/2020/01/TESAR-catalogue-Cast_Resin-Ecodesign-ENG-web.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.