Energy Management in Air-Conditioning Systems (8th National HVAC Engineering Congress, 2007)

Original title İklimlendirme Sistemlerinde Enerji Yönetimi

TMMOB Makina Mühendisleri Odası · Ali Güngör, Senem Güngör

A 2007 congress paper by Ali and Senem Güngör on energy audit types, chiller replacement and control, and economiser cycles; scroll chillers exceed COP 3.2 and a 20% fan speed cut saves about 50% energy.

On this page

Overview

The paper is a seminar text prepared for the 8th National HVAC Engineering Congress of the Chamber of Mechanical Engineers (2007, paper 2007-55). Its aim is to give the principles of making air-conditioning systems energy efficient through controls, equipment, building and system features, and of monitoring and auditing energy use in existing installations.

The text defines four audit types: on-site walk-through, system equipment cost analysis, standard energy audit and comprehensive audit. In the standard audit, simple models such as the degree-day method and linear regression are combined with simple payback and life-cycle cost analysis. Energy-saving areas such as comfort, air quality, maintenance, scheduled operation, night setback and overheating/overcooling follow.

On the cooling side, multi-compressor chillers (100-7000 kW) can save up to 25% against single-compressor units and variable-speed centrifugal chillers (500-2500 kW) can cut cooling energy by about 50%; scroll compressors can exceed COP 3.2. In one example, raising chilled-water leaving temperature from 4.5 °C to 7.0 °C raises COP by 8%. In a water-side economiser, cooling-tower water is used directly or through a heat exchanger.

The document concerns general air-conditioning energy management and dates from 2007; it is not specific to data centres. Its equations and examples are in a comfort and industrial context, but its methods (control, economisers, fan speed) transfer directly to cooling systems.

Key points

  1. Four audit types: on-site walk-through, system equipment cost analysis, standard energy audit and comprehensive audit.
  2. The standard audit uses degree-day and linear regression models, simple payback and life-cycle cost analysis.
  3. Multi-compressor chillers cover 100-7000 kW and can save up to 25% against single-compressor units.
  4. Variable-speed centrifugal chillers cover 500-2500 kW and can cut cooling energy by about 50%.
  5. Scroll-compressor chillers can exceed COP 3.2.
  6. In the worked example, raising chilled-water leaving temperature on a centrifugal chiller from 4.5 °C to 7.0 °C raises COP by 8% (seasonal COP 4.0, 1500 h/year).
  7. Cutting airflow by 50% cuts fan energy by 87.5%; a 20% fan speed reduction lowers energy demand by about 50%.
  8. In a water-side economiser, tower-water contamination calls for water conditioning or a heat exchanger.

Using it in design

  • Add metering and logging infrastructure (part load, leaving water temperature, compressor and fan power) to the cooling plant from the start; measured data is the first step of any audit.
  • For plants running at part load, compare multi-compressor or variable-speed chillers with single-compressor options in the annual energy calculation.
  • Move the chilled-water leaving temperature setpoint as high as possible; a rise of about 2.5 °C shows an 8% COP gain.
  • When designing a water-side economiser, separate tower water from the chilled-water loop with a heat exchanger and plan water conditioning.
  • Vary fan and pump flow with speed; because of the cube law, a speed reduction gives large power savings.

Who should read it

Mechanical engineers doing HVAC and cooling energy audits, energy managers and students.

Document contents

  1. Introduction
  2. Energy Audit Types (on-site, system cost analysis, standard audit)
  3. Energy Management Opportunities: Comfort, Air Quality, Airflow, Maintenance, Demand Management
  4. Chiller Replacement and Chiller Control Improvements
  5. Water-side Economisers, Evaporative Cooling, Desiccant Cooling
  6. Ventilation and Air-side Economiser Cycles
  7. Indoor Temperature Control and Fan Size Corrections

Publication details

Authors
Ali Güngör; Senem Güngör
Publisher
TMMOB Makina Mühendisleri Odası
Year
2007
Document number
VIII. Ulusal Tesisat Mühendisliği Kongresi, bildiri 2007-55
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi.

Citation

Ali Güngör; Senem Güngör (2007). İklimlendirme Sistemlerinde Enerji Yönetimi. TMMOB Makina Mühendisleri Odası. VIII. Ulusal Tesisat Mühendisliği Kongresi, bildiri 2007-55. https://mmoteskon.org/images/2025/01/2007-55.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.