Energy Management in Air-Conditioning Systems (8th National HVAC Engineering Congress, 2007)
Original title İklimlendirme Sistemlerinde Enerji Yönetimi
TMMOB Makina Mühendisleri Odası · Ali Güngör, Senem Güngör
A 2007 congress paper by Ali and Senem Güngör on energy audit types, chiller replacement and control, and economiser cycles; scroll chillers exceed COP 3.2 and a 20% fan speed cut saves about 50% energy.
On this page
Overview
The paper is a seminar text prepared for the 8th National HVAC Engineering Congress of the Chamber of Mechanical Engineers (2007, paper 2007-55). Its aim is to give the principles of making air-conditioning systems energy efficient through controls, equipment, building and system features, and of monitoring and auditing energy use in existing installations.
The text defines four audit types: on-site walk-through, system equipment cost analysis, standard energy audit and comprehensive audit. In the standard audit, simple models such as the degree-day method and linear regression are combined with simple payback and life-cycle cost analysis. Energy-saving areas such as comfort, air quality, maintenance, scheduled operation, night setback and overheating/overcooling follow.
On the cooling side, multi-compressor chillers (100-7000 kW) can save up to 25% against single-compressor units and variable-speed centrifugal chillers (500-2500 kW) can cut cooling energy by about 50%; scroll compressors can exceed COP 3.2. In one example, raising chilled-water leaving temperature from 4.5 °C to 7.0 °C raises COP by 8%. In a water-side economiser, cooling-tower water is used directly or through a heat exchanger.
The document concerns general air-conditioning energy management and dates from 2007; it is not specific to data centres. Its equations and examples are in a comfort and industrial context, but its methods (control, economisers, fan speed) transfer directly to cooling systems.
Key points
- Four audit types: on-site walk-through, system equipment cost analysis, standard energy audit and comprehensive audit.
- The standard audit uses degree-day and linear regression models, simple payback and life-cycle cost analysis.
- Multi-compressor chillers cover 100-7000 kW and can save up to 25% against single-compressor units.
- Variable-speed centrifugal chillers cover 500-2500 kW and can cut cooling energy by about 50%.
- Scroll-compressor chillers can exceed COP 3.2.
- In the worked example, raising chilled-water leaving temperature on a centrifugal chiller from 4.5 °C to 7.0 °C raises COP by 8% (seasonal COP 4.0, 1500 h/year).
- Cutting airflow by 50% cuts fan energy by 87.5%; a 20% fan speed reduction lowers energy demand by about 50%.
- In a water-side economiser, tower-water contamination calls for water conditioning or a heat exchanger.
Using it in design
- Add metering and logging infrastructure (part load, leaving water temperature, compressor and fan power) to the cooling plant from the start; measured data is the first step of any audit.
- For plants running at part load, compare multi-compressor or variable-speed chillers with single-compressor options in the annual energy calculation.
- Move the chilled-water leaving temperature setpoint as high as possible; a rise of about 2.5 °C shows an 8% COP gain.
- When designing a water-side economiser, separate tower water from the chilled-water loop with a heat exchanger and plan water conditioning.
- Vary fan and pump flow with speed; because of the cube law, a speed reduction gives large power savings.
Who should read it
Mechanical engineers doing HVAC and cooling energy audits, energy managers and students.
Document contents
- Introduction
- Energy Audit Types (on-site, system cost analysis, standard audit)
- Energy Management Opportunities: Comfort, Air Quality, Airflow, Maintenance, Demand Management
- Chiller Replacement and Chiller Control Improvements
- Water-side Economisers, Evaporative Cooling, Desiccant Cooling
- Ventilation and Air-side Economiser Cycles
- Indoor Temperature Control and Fan Size Corrections
Publication details
- Authors
- Ali Güngör; Senem Güngör
- Publisher
- TMMOB Makina Mühendisleri Odası
- Year
- 2007
- Document number
- VIII. Ulusal Tesisat Mühendisliği Kongresi, bildiri 2007-55
- Document language
- Turkish
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi.
Citation
Ali Güngör; Senem Güngör (2007). İklimlendirme Sistemlerinde Enerji Yönetimi. TMMOB Makina Mühendisleri Odası. VIII. Ulusal Tesisat Mühendisliği Kongresi, bildiri 2007-55. https://mmoteskon.org/images/2025/01/2007-55.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.