TOSNIC-U350 Large-Capacity Modular Type UPS for Large-Scale Data Centers

Toshiba · Katsuya Mineno, Akira Miyamoto

A Toshiba Review article of July 2022: 350 kVA modules give a 1050-1750 kVA single UPS, 97.2% peak efficiency, 99% in bypass eco mode and support for transformerless three-phase four-wire 400 V distribution; at 1000 kVA the footprint falls 20%.

On this page

Overview

The article (Japanese text with an English abstract) presents the TOSNIC-U350 modular UPS developed by Toshiba Infrastructure Systems for large data centres. The rationale is to raise capacity per UPS as data-centre power consumption grows: as the UPS count rises, so do parallel, distribution and transfer panels, with more space and operating complexity. The answer is to reach the required system capacity with fewer UPS.

The system comprises UPS modules and one bypass module. A UPS module contains the inverter, converter and main control board; the bypass module holds the thyristor module and peripheral circuits. Against the earlier TOSNIC-U300, module rating rises from 300 kVA to 350 kVA and connectable modules from 3 to 5, giving 1050-1750 kVA per UPS (power factor 1.0). In the 1000 kVA example the footprint is 20% smaller than a conventional 2 x 500 kVA parallel system.

Three features are highlighted. Reliability: on a module fault only the faulty module is disconnected, and remaining modules supply without interruption if the load fraction allows; module redundancy (+1) increases continuity; batteries can be connected as one group or per module. Efficiency: peak efficiency is 97.2% and the eco drive, which adjusts the number of modules to the load, gains about 3% in the stated condition; bypass eco mode confirmed 99% peak efficiency. Distribution: three-phase four-wire 400 V is supported without a PDU transformer.

This is a manufacturer journal article describing Toshiba's own product and contains no independent test data. It is written in a Japanese market context and states 50 and 60 Hz and 400, 415 and 420 V options.

Key points

  1. UPS module 350 kVA (previously 300 kVA); connectable modules 3-5 (previously 1-3); rated output per UPS 1050, 1400 and 1750 kVA.
  2. Output power factor 1.0 (previously 0.9); voltage accuracy +/-1% (0-100% load), frequency accuracy 0.01%; overload 10 minutes at 125% and 1 minute at 150%.
  3. Maximum conversion efficiency 97.2% (previously 97.0%).
  4. Input three-phase three-wire 400, 415 or 420 V, 50 or 60 Hz; output three-phase three-wire or three-phase four-wire.
  5. A 1000 kVA system occupies 20% less floor area than a conventional system (UPS and peripheral panels included).
  6. On a module fault only the faulty module is disconnected; continuity holds if the remaining modules can carry the load; +1 module redundancy can be chosen.
  7. Eco drive adjusts the number of running modules to the load fraction and in the stated example raises efficiency by about 3% (for example at 17% load fraction efficiency is about 93% before).
  8. In bypass eco mode peak efficiency is 99%; the load is fed continuously through the thyristor bypass with the inverter on standby.
  9. Three-phase four-wire 400 V distribution allows feeding 230 V single-phase loads without a PDU transformer and has lower loss than conventional three-phase three-wire.

Using it in design

  • In large halls consider reducing the number of UPS to cut the count of parallel, distribution and transfer panels and floor area; in the 1000 kVA example area falls 20%.
  • Choose module redundancy (N+1) and the battery connection style (common or per module) together, on fault-domain and battery room area grounds.
  • For part-load operation, compute the efficiency gain of an eco-drive-type feature that adjusts module count to load (about 3% in the example) with your data-centre load profile.
  • If bypass eco mode is to be used, weigh the 99% efficiency against the protection limits of feeding the load through the bypass line.
  • Compare three-phase four-wire 400 V distribution on the single-line diagram for whether removing the PDU transformer saves loss and space.

Who should read it

Electrical designers and investment decision makers selecting UPS topology of 1 MVA and above in large-scale data centres.

Document contents

  1. Introduction
  2. Product overview and unit ratings
  3. Features: high reliability, high-efficiency operation, support for three-phase four-wire 400 V distribution
  4. Conclusion

Publication details

Authors
Katsuya Mineno; Akira Miyamoto
Publisher
Toshiba
Year
2022
Document number
Toshiba Review Vol. 77 No. 4, pp. 40–43
Document language
Japanese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.

Citation

Katsuya Mineno; Akira Miyamoto (2022). TOSNIC-U350 Large-Capacity Modular Type UPS for Large-Scale Data Centers. Toshiba. Toshiba Review Vol. 77 No. 4, pp. 40–43. https://www.global.toshiba/content/dam/toshiba/jp/technology/corporate/review/2022/04/f01.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.