Research paperFree to read2003

Design of a Single Phase Power Factor Corrected Uninterruptible Power Supply

Original title Bir Fazlı Güç Faktörü Düzeltmeli Kesintisiz Güç Kaynağı Tasarımı

Politeknik Dergisi · Ömer Faruk Bay, İsmail Atacak

A 2003 paper from Gazi University that compares control techniques for the PFC, battery converter and inverter stages of a single-phase 220 V / 50 Hz on-line UPS, using simulation.

On this page

Overview

The paper starts from the point that European and international norms limiting input-current harmonics require a power factor correction (PFC) stage, and it designs a single-phase double-conversion (on-line) UPS accordingly. The design has three stages: a half-bridge boost-type AC/DC PFC stage, a battery buck/boost converter stage and the output inverter.

Its distinctive contribution is the comparison of control techniques. In the PFC stage it examines average-current, hysteresis and peak-current control; in the battery-charge, battery-boost and inverter stages it builds current-mode and voltage-mode controllers with PI coefficients. Advantages and drawbacks of each are shown through simulated waveforms.

Simulation parameters are tabulated: 220 V / 50 Hz input, 50 V battery, 400 V DC bus, 220 V / 50 Hz output, 500 uH input inductance, 1750 uF bus capacitors and 1 mH output inductance. In load-step tests the current-mode boost converter settles at 400 V in about 1.2 ms; when the load drops from 30 ohm to 15 ohm the voltage falls to 350 V and returns to 400 V within 0.5 ms.

Results rest on simulation only, with no hardware measurements or efficiency figures. For a data-centre designer the value is conceptual: why an active PFC front end is needed in a UPS, and how fast the internal control loops of a double-conversion unit react.

Key points

  1. The UPS is single-phase on-line with three stages: PFC stage, battery buck/boost converter and output inverter.
  2. The PFC stage is a half-bridge boost AC/DC converter; average-current, hysteresis and peak-current control are compared.
  3. Simulation values: input 220 V / 50 Hz, DC bus 400 V, battery 50 V, output 220 V / 50 Hz.
  4. The current-mode boost converter settles its output at 400 V in about 1.2 ms with a 30 ohm load.
  5. When load drops from 30 ohm to 15 ohm, bus voltage falls to 350 V and recovers to 400 V in about 0.5 ms.
  6. In the current-mode controller the current loop switches at 20 kHz and the voltage loop at 10 kHz.
  7. Desired properties for critical loads are regulation, voltage stability, load regulation and frequency stability, which the control methods determine.
  8. The results come from simulation; no hardware tests are included.

Using it in design

  • Ask for UPS input power factor and input-current harmonic distortion (THDi) as separate selection criteria; the paper shows a PFC stage is needed to meet such limits.
  • For generator-backed systems, include in the compatibility check how the UPS active PFC stage shapes the input current waveform.
  • Request recovery times after a load step (millisecond range) from the manufacturer as dynamic output performance and map them to the IEC 62040-3 class.
  • The work covers a small single-phase model; do not reuse its parameters for three-phase data-centre UPSs, use only the stage structure as a reference.

Who should read it

Electrical and electronics engineers and students who want to understand UPS internals, power factor correction and control techniques.

Document contents

  1. Introduction
  2. Control techniques used in UPSs
  3. Deriving the UPS model equations
  4. Building the control stage
  5. Simulation studies
  6. Conclusion

Publication details

Authors
Ömer Faruk Bay; İsmail Atacak
Publisher
Politeknik Dergisi
Year
2003
Document number
6(2), 433–443; PDF ilk sayfa üstbilgisi 433–444
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. DergiPark sayfa aralığı ve indirilen PDF son sayfası 443; PDF ilk sayfa üstbilgisi 444 gösterir. Fark korunmuştur.

Citation

Ömer Faruk Bay; İsmail Atacak (2003). Bir Fazlı Güç Faktörü Düzeltmeli Kesintisiz Güç Kaynağı Tasarımı. Politeknik Dergisi. 6(2), 433–443; PDF ilk sayfa üstbilgisi 433–444. https://dergipark.org.tr/tr/download/article-file/384344

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.