Design of a Single Phase Power Factor Corrected Uninterruptible Power Supply
Original title Bir Fazlı Güç Faktörü Düzeltmeli Kesintisiz Güç Kaynağı Tasarımı
Politeknik Dergisi · Ömer Faruk Bay, İsmail Atacak
A 2003 paper from Gazi University that compares control techniques for the PFC, battery converter and inverter stages of a single-phase 220 V / 50 Hz on-line UPS, using simulation.
On this page
Overview
The paper starts from the point that European and international norms limiting input-current harmonics require a power factor correction (PFC) stage, and it designs a single-phase double-conversion (on-line) UPS accordingly. The design has three stages: a half-bridge boost-type AC/DC PFC stage, a battery buck/boost converter stage and the output inverter.
Its distinctive contribution is the comparison of control techniques. In the PFC stage it examines average-current, hysteresis and peak-current control; in the battery-charge, battery-boost and inverter stages it builds current-mode and voltage-mode controllers with PI coefficients. Advantages and drawbacks of each are shown through simulated waveforms.
Simulation parameters are tabulated: 220 V / 50 Hz input, 50 V battery, 400 V DC bus, 220 V / 50 Hz output, 500 uH input inductance, 1750 uF bus capacitors and 1 mH output inductance. In load-step tests the current-mode boost converter settles at 400 V in about 1.2 ms; when the load drops from 30 ohm to 15 ohm the voltage falls to 350 V and returns to 400 V within 0.5 ms.
Results rest on simulation only, with no hardware measurements or efficiency figures. For a data-centre designer the value is conceptual: why an active PFC front end is needed in a UPS, and how fast the internal control loops of a double-conversion unit react.
Key points
- The UPS is single-phase on-line with three stages: PFC stage, battery buck/boost converter and output inverter.
- The PFC stage is a half-bridge boost AC/DC converter; average-current, hysteresis and peak-current control are compared.
- Simulation values: input 220 V / 50 Hz, DC bus 400 V, battery 50 V, output 220 V / 50 Hz.
- The current-mode boost converter settles its output at 400 V in about 1.2 ms with a 30 ohm load.
- When load drops from 30 ohm to 15 ohm, bus voltage falls to 350 V and recovers to 400 V in about 0.5 ms.
- In the current-mode controller the current loop switches at 20 kHz and the voltage loop at 10 kHz.
- Desired properties for critical loads are regulation, voltage stability, load regulation and frequency stability, which the control methods determine.
- The results come from simulation; no hardware tests are included.
Using it in design
- Ask for UPS input power factor and input-current harmonic distortion (THDi) as separate selection criteria; the paper shows a PFC stage is needed to meet such limits.
- For generator-backed systems, include in the compatibility check how the UPS active PFC stage shapes the input current waveform.
- Request recovery times after a load step (millisecond range) from the manufacturer as dynamic output performance and map them to the IEC 62040-3 class.
- The work covers a small single-phase model; do not reuse its parameters for three-phase data-centre UPSs, use only the stage structure as a reference.
Who should read it
Electrical and electronics engineers and students who want to understand UPS internals, power factor correction and control techniques.
Document contents
- Introduction
- Control techniques used in UPSs
- Deriving the UPS model equations
- Building the control stage
- Simulation studies
- Conclusion
Publication details
- Authors
- Ömer Faruk Bay; İsmail Atacak
- Publisher
- Politeknik Dergisi
- Year
- 2003
- Document number
- 6(2), 433–443; PDF ilk sayfa üstbilgisi 433–444
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. DergiPark sayfa aralığı ve indirilen PDF son sayfası 443; PDF ilk sayfa üstbilgisi 444 gösterir. Fark korunmuştur.
Citation
Ömer Faruk Bay; İsmail Atacak (2003). Bir Fazlı Güç Faktörü Düzeltmeli Kesintisiz Güç Kaynağı Tasarımı. Politeknik Dergisi. 6(2), 433–443; PDF ilk sayfa üstbilgisi 433–444. https://dergipark.org.tr/tr/download/article-file/384344
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.