Performance Comparison of Fuzzy Logic and Gain Scheduling Adaptive Based PI Controllers for Uninterruptible Power Supply Output Power Regulation
Original title Kesintisiz Güç Kaynağı Çıkış Gücü Düzenlemesi için Bulanık Mantık ve Kazanç Çizelgesi Uyarlanır Tabanlı PI Kontrolörlerin Performans Karşılaştırılması
Avrupa Bilim ve Teknoloji Dergisi · Vedat Gül, Savaş Şahin
A 2021 paper by authors from Tescom and Izmir Katip Celebi University: on a 5 kW UPS inverter the gain scheduling adaptive PI controller cuts output voltage THD from 1.7% for conventional PI to 0.9% in the experiment.
On this page
Overview
The study compares the conventional fixed-gain PI controller with fuzzy logic (FL) based and gain scheduling adaptive (GSA) based PI controllers for UPS inverter output voltage regulation. The rationale is that controllers which update their coefficients to the operating condition may perform better than the fixed-gain PI common in inverters. Output voltage quality is measured by total harmonic distortion (THD) and mean absolute error (MAE).
The method first simulates a 5 kW UPS system in Simulink, then tests the same controllers on an experimental rig built with a dsPIC33EP512GM710 processor board, an intelligent power module and a driver board. The FL controller takes the error between inverter output voltage and reference, and its rate of change, to produce Kp and Ki. The GSA controller selects Kp and Ki from a coefficient table determined from THD measurements at different load values. In the rig the reference is 220 V rms sine, sampling frequency 12868 Hz and bus voltage 360 VAC, with Kp=50 and Ki=30 for conventional PI.
Results are for resistive full load (100%). In simulation THD is 1.05% for conventional PI, 0.75% for FL and 0.60% for GSA, with MAE of 1.7121, 1.6805 and 1.6698. In the experiment THD is 1.7%, 1.2% and 0.9% and MAE 3.0719, 2.7888 and 2.7047. GSA-based PI gives the best result in both. The study covers only resistive full load and one 5 kW design; non-linear load and other power levels are not examined.
Key points
- Three controllers are compared: conventional PI, fuzzy logic based PI and gain scheduling adaptive (GSA) based PI.
- The system is a 5 kW UPS inverter; in the experiment a dsPIC33EP512GM710 processor, 220 V rms reference, 12868 Hz sampling and 360 VAC bus.
- Simulation (resistive 100% load): THD conventional PI 1.05%, FL 0.75%, GSA 0.60%; MAE 1.7121, 1.6805, 1.6698.
- Experiment (resistive 100% load): THD conventional PI 1.7%, FL 1.2%, GSA 0.9%; MAE 3.0719, 2.7888, 2.7047.
- GSA-based PI gives the lowest THD and MAE in both simulation and experiment; in the experiment THD falls by about 47% against conventional PI.
- Conventional PI parameters are Kp=50 and Ki=30; the GSA coefficient table was derived from THD measurements against load values.
- THD and MAE are computed from the output voltage waveform.
Using it in design
- In UPS product specifications ask for output voltage THD at different load levels and on non-linear load, not only linear load; the controller type affects these values.
- When comparing products, assess control method (fixed-gain PI, adaptive or fuzzy) together with harmonic quality and dynamic response.
- For sensitive loads ask the manufacturer for the curve of output THD against load fraction.
- In UPS acceptance testing, measure output voltage THD and voltage regulation across several load steps.
Who should read it
Power-electronics engineers designing UPS inverters and controllers, and system designers assessing output voltage quality.
Document contents
- Introduction
- Material and method (UPS system, conventional PI, fuzzy logic and gain scheduling adaptive design)
- Simulation and experimental studies
- Conclusion
Publication details
- Authors
- Vedat Gül; Savaş Şahin
- Publisher
- Avrupa Bilim ve Teknoloji Dergisi
- Year
- 2021
- Document number
- Özel Sayı 24, 416–420
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. PDF telif hakkının EJOSAT’a ait olduğunu belirtir. Çalışmada TESCOM laboratuvar ve deney düzeneği desteği açıklanmıştır.
Citation
Vedat Gül; Savaş Şahin (2021). Kesintisiz Güç Kaynağı Çıkış Gücü Düzenlemesi için Bulanık Mantık ve Kazanç Çizelgesi Uyarlanır Tabanlı PI Kontrolörlerin Performans Karşılaştırılması. Avrupa Bilim ve Teknoloji Dergisi. Özel Sayı 24, 416–420. https://doi.org/10.31590/ejosat.903268
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.