Design and Implementation of a 700 VA Uninterruptible Power Supply Circuit
Original title 700 VA Kesintisiz Güç Kaynağı Devresinin Tasarımı ve Gerçekleştirilmesi
Gazi Üniversitesi Mühendislik Mimarlık Fakültesi Dergisi · Müzeyyen Sarıtaş, M. Timur Aydemir et al.
A 2002 paper from Gazi University describing a 700 VA, PWM-controlled on-line UPS with 2x12 V dry batteries that supplies full load for 15 to 30 minutes after mains loss.
On this page
Overview
The paper describes the design and build of a 700 VA on-line UPS that continuously charges 24 V DC dry batteries from 220 V AC mains and regenerates 220 V / 50 Hz from them. The system has an input power stage, battery charger, driver, inverter, sampling, control and output stages.
The theory section summarises three UPS types (stand-by, on-line, line-interactive) and battery practice. Lead-acid batteries are charged by constant voltage and constant current; they should never be left uncharged nor drawn on while discharged. As an example, a 60 Ah, 12 V battery is best charged at 5-6 A over 10-12 hours for life.
In the implementation the charger holds the 24 V battery at 27.2 V DC. The inverter is a parallel type with a centre-tapped transformer and MOSFET switches; sampling from the output adjusts the pulse width to hold voltage constant. The control stage also handles overcurrent and low battery: output is inhibited below 20 V and a buzzer sounds between 20 V and 25 V.
Reported performance: voltage change under 1% for load changes from 1% to 100%, output change under 10% for sudden load changes and interruptions, output frequency 49.5-50.5 Hz when mains frequency deviates. The three-state output is close to a square wave and can be made sinusoidal with an LC filter. It is a small prototype and does not transfer directly to data-centre-class equipment.
Key points
- The system is a 700 VA on-line design producing 220 V AC / 50 Hz from a 24 V DC (2x12 V dry cell) source.
- It supplies full load for 15 to 30 minutes after mains loss; two 12 V, 18 Ah batteries can deliver 18 A for one hour.
- Battery charge voltage is 27.2 V DC for the 24 V block.
- Low-battery warning: buzzer every 3 seconds between 20 V and 25 V; no output below 20 V.
- Voltage change stays under 1% for load changes of 1% to 100%; the acceptable band is stated as 2%.
- Output change under 10% for sudden load changes and interruptions; frequency held at 49.5-50.5 Hz.
- Mains voltage is stated to deviate between -20% and +15%; the UPS reduces the variation to under 1%.
- The inverter is a parallel centre-tapped type; the three-state output can be brought close to a sine wave with an LC filter.
- An RS232 link to a computer is possible; toroidal transformers and more batteries are suggested for more power.
Using it in design
- When calculating battery autonomy, define charge voltage, discharge cut-off and warning threshold as separate parameters; the paper gives 20 V and 20-25 V as an example.
- Include the rules of never leaving batteries uncharged and not drawing current from discharged batteries in the operating procedure.
- Compare UPS output-quality criteria (load regulation 1%, sudden load 10%, frequency 49.5-50.5 Hz) with the dynamic-performance lines of the specification.
- Verify separately the suitability of small UPSs with near-square-wave output for loads that need a sine wave.
Who should read it
Students and electronics designers studying small UPS design, battery charge logic and PWM inverter control.
Document contents
- Introduction
- Theoretical background
- The implemented UPS circuit and its operation
- Conclusions and discussion
Publication details
- Authors
- Müzeyyen Sarıtaş; M. Timur Aydemir; Ayhan Dalbaz
- Publisher
- Gazi Üniversitesi Mühendislik Mimarlık Fakültesi Dergisi
- Year
- 2002
- Document number
- 17(1), 33–42
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. 2002 yılı PDF cilt/sayı künyesidir; arama motorundaki 2013 tarihi yayın yılı yerine kullanılmadı.
Citation
Müzeyyen Sarıtaş; M. Timur Aydemir; Ayhan Dalbaz (2002). 700 VA Kesintisiz Güç Kaynağı Devresinin Tasarımı ve Gerçekleştirilmesi. Gazi Üniversitesi Mühendislik Mimarlık Fakültesi Dergisi. 17(1), 33–42. https://dergipark.org.tr/tr/download/article-file/76416
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.