A 2002 paper from Gazi University describing a 700 VA, PWM-controlled on-line UPS with 2x12 V dry batteries that supplies full load for 15 to 30 minutes after mains loss.

On this page

Overview

The paper describes the design and build of a 700 VA on-line UPS that continuously charges 24 V DC dry batteries from 220 V AC mains and regenerates 220 V / 50 Hz from them. The system has an input power stage, battery charger, driver, inverter, sampling, control and output stages.

The theory section summarises three UPS types (stand-by, on-line, line-interactive) and battery practice. Lead-acid batteries are charged by constant voltage and constant current; they should never be left uncharged nor drawn on while discharged. As an example, a 60 Ah, 12 V battery is best charged at 5-6 A over 10-12 hours for life.

In the implementation the charger holds the 24 V battery at 27.2 V DC. The inverter is a parallel type with a centre-tapped transformer and MOSFET switches; sampling from the output adjusts the pulse width to hold voltage constant. The control stage also handles overcurrent and low battery: output is inhibited below 20 V and a buzzer sounds between 20 V and 25 V.

Reported performance: voltage change under 1% for load changes from 1% to 100%, output change under 10% for sudden load changes and interruptions, output frequency 49.5-50.5 Hz when mains frequency deviates. The three-state output is close to a square wave and can be made sinusoidal with an LC filter. It is a small prototype and does not transfer directly to data-centre-class equipment.

Key points

  1. The system is a 700 VA on-line design producing 220 V AC / 50 Hz from a 24 V DC (2x12 V dry cell) source.
  2. It supplies full load for 15 to 30 minutes after mains loss; two 12 V, 18 Ah batteries can deliver 18 A for one hour.
  3. Battery charge voltage is 27.2 V DC for the 24 V block.
  4. Low-battery warning: buzzer every 3 seconds between 20 V and 25 V; no output below 20 V.
  5. Voltage change stays under 1% for load changes of 1% to 100%; the acceptable band is stated as 2%.
  6. Output change under 10% for sudden load changes and interruptions; frequency held at 49.5-50.5 Hz.
  7. Mains voltage is stated to deviate between -20% and +15%; the UPS reduces the variation to under 1%.
  8. The inverter is a parallel centre-tapped type; the three-state output can be brought close to a sine wave with an LC filter.
  9. An RS232 link to a computer is possible; toroidal transformers and more batteries are suggested for more power.

Using it in design

  • When calculating battery autonomy, define charge voltage, discharge cut-off and warning threshold as separate parameters; the paper gives 20 V and 20-25 V as an example.
  • Include the rules of never leaving batteries uncharged and not drawing current from discharged batteries in the operating procedure.
  • Compare UPS output-quality criteria (load regulation 1%, sudden load 10%, frequency 49.5-50.5 Hz) with the dynamic-performance lines of the specification.
  • Verify separately the suitability of small UPSs with near-square-wave output for loads that need a sine wave.

Who should read it

Students and electronics designers studying small UPS design, battery charge logic and PWM inverter control.

Document contents

  1. Introduction
  2. Theoretical background
  3. The implemented UPS circuit and its operation
  4. Conclusions and discussion

Publication details

Authors
Müzeyyen Sarıtaş; M. Timur Aydemir; Ayhan Dalbaz
Publisher
Gazi Üniversitesi Mühendislik Mimarlık Fakültesi Dergisi
Year
2002
Document number
17(1), 33–42
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. 2002 yılı PDF cilt/sayı künyesidir; arama motorundaki 2013 tarihi yayın yılı yerine kullanılmadı.

Citation

Müzeyyen Sarıtaş; M. Timur Aydemir; Ayhan Dalbaz (2002). 700 VA Kesintisiz Güç Kaynağı Devresinin Tasarımı ve Gerçekleştirilmesi. Gazi Üniversitesi Mühendislik Mimarlık Fakültesi Dergisi. 17(1), 33–42. https://dergipark.org.tr/tr/download/article-file/76416

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.