Research paperFree to read2008

Design and Implementation of a PIC Controlled Uninterruptible Power Supply

Original title PIC Kontrollü Kesintisiz Güç Kaynağı Tasarımı ve Gerçeklemesi

e-Journal of New World Sciences Academy, Natural and Applied Sciences · Mehmet Üstündağ, Mehmet Gedikpınar

A 2008 paper from Fırat University describing an off-line UPS built around a PIC16F84 microcontroller, with a measured transfer from mains to inverter of about 4 ms.

On this page

Overview

The paper describes the design and laboratory build of an off-line (standby) uninterruptible power supply that feeds sensitive loads for a limited time when mains fails. Its single goal is to shorten the transfer (switching) time, because a long transfer degrades the behaviour of sensitive loads such as computers.

The introduction splits UPSs into on-line, off-line and line-interactive groups. The off-line structure is simple, small and cheap but performs poorly with non-linear loads because of the long transfer time, and it cannot regulate voltage. The on-line structure always feeds the load through the inverter, giving constant voltage and a clean sine wave, but costs considerably more. Line-interactive adds regulation and frequency stability.

The system has six blocks: rectifier, battery bank, DC-DC converter, inverter, transfer switches and microcontroller. The rectifier supplies the 15 V and 12 V control rails. A battery labelled 12 V is charged between 13.6 V and 14.5 V. Transfer uses a zero-crossing solid-state relay (SSR), and the microcontroller watches the mains continuously to drive it.

Oscilloscope traces show the inverter taking over within about 4 ms after mains loss, so the load is supplied without a visible interruption. The converter runs at 56 kHz. The paper covers a small prototype; it has no data-centre-scale design or efficiency analysis, but it illustrates the transfer-time limit inherent to the off-line topology.

Key points

  1. The aim is to shorten the transfer time of an off-line UPS with a microcontroller; the measured transfer time is about 4 ms.
  2. The transfer time is expected to stay within a quarter of a mains period, taken as the criterion for protecting sensitive loads.
  3. The system has six blocks: rectifier, battery bank, DC-DC converter, inverter, transfer switches, microcontroller.
  4. Rectifier output for the control circuits is 15 V with mains present and 12 V after mains loss.
  5. A 12 V battery is charged between 13.6 V and 14.5 V; charge current and voltage are limited with a TL431.
  6. The converter runs at 56 kHz; the inverter switching frequency is given as 100 Hz.
  7. The off-line structure cannot regulate voltage but can act as an active power filter; the on-line structure is costly.
  8. An on-line UPS has three modes: normal, emergency (battery) and standby (bypass).

Using it in design

  • When off-line or line-interactive UPSs are considered, compare the manufacturer's transfer time with the ride-through tolerance of the load power supplies; about 4 ms is the value measured on this prototype.
  • For halls dominated by non-linear (switch-mode) loads, document the choice of double-conversion on-line over off-line using the drawbacks the paper lists.
  • Size the UPS from the total load power and the maximum current it can draw; the paper treats this as the first selection condition.
  • Add a commissioning check comparing battery charge voltage settings (13.6 V to 14.5 V for a 12 V block) with the charger set points.

Who should read it

Students, junior engineers and educators who want the basic operating principle of UPS topologies and the transfer-time problem of the off-line structure.

Document contents

  1. Introduction
  2. Research significance
  3. Model of the UPS
  4. Experimental results
  5. Results and suggestions

Publication details

Authors
Mehmet Üstündağ; Mehmet Gedikpınar
Publisher
e-Journal of New World Sciences Academy, Natural and Applied Sciences
Year
2008
Document number
3(1), A0060, 151–157
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. DergiPark sayfasındaki 10.12739/10.12739 DOI alanı şüpheli olduğundan DOI null bırakıldı; PDF’de DOI görülmedi.

Citation

Mehmet Üstündağ; Mehmet Gedikpınar (2008). PIC Kontrollü Kesintisiz Güç Kaynağı Tasarımı ve Gerçeklemesi. e-Journal of New World Sciences Academy, Natural and Applied Sciences. 3(1), A0060, 151–157. https://dergipark.org.tr/tr/download/article-file/187416

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.