Research paperPDF2021

Analysis of Power Quality Parameters at Comparing UPS of Different Technologies

ITEGAM- Journal of Engineering and Technology for Industrial Applications (ITEGAM-JETIA) (GN1 Sistemas e Publicacoes Ltd.) · Rafael Provenzano Jou Alves, André Abel Augusto et al.

A field measurement study from Fluminense Federal University compares the input and output power quality of a 75 kVA offline UPS feeding a laboratory and a 40 kVA online double-conversion UPS feeding a data centre.

CC BY 4.0: share with attribution

On this page

Overview

The study asks how UPS technology affects the power quality delivered to the supplied network and load. Two three-phase 380 V, 60 Hz UPS units were measured: UPS A, a 75 kVA offline unit feeding a research laboratory with a capacitive load character, and UPS B, a 40 kVA online double-conversion unit feeding a data centre. Voltage and current THD, individual harmonics up to the 41st, power factor, voltage unbalance and frequency were logged with a power-quality analyser and compared with Brazilian PRODIST Module 8 limits.

On the online 40 kVA UPS, input current THD was 33.89%, 46.92% and 23.31% per phase while output current THD was 5.93%, 7.20% and 5.79%. Output voltage THD was 0% on phases A and C and 0.87% on phase B, voltage unbalance 0.09%, frequency about 60.00 Hz and output power factor 0.97. On the offline 75 kVA unit, output current THD stayed high at 24.62%, 25.13% and 21.77%, with 3rd harmonics reduced but 5th, 7th and 9th increased, which the authors attribute to internal components resonating with the load.

The offline UPS output voltage unbalance factor was 3.91%, the only parameter that failed PRODIST limits; its output power factor was 0.95 (PRODIST range 0.92-1.00). The paper explains that offline UPS transfer delays are usually a few milliseconds, whereas online double conversion has no transfer delay but lower efficiency.

The conclusion is that a UPS installed to improve power quality must be online; an offline UPS does not improve network quality. Limits: only two units and two different loads were compared, and because rating and load type differ, the comparison does not isolate the topology effect alone. The authors stress the importance of a UPS labelling programme.

Key points

  1. Online 40 kVA UPS (data centre): input current THD was 33.89%, 46.92% and 23.31% per phase; output current THD was 5.93%, 7.20% and 5.79%.
  2. Online UPS output voltage THD was 0% on phases A and C and 0.87% on phase B; output voltage unbalance 0.09% and frequency about 60.00 Hz.
  3. Offline 75 kVA UPS: output current THD stayed high at 24.62%, 25.13% and 21.77%, with 3rd harmonics reduced but 5th, 7th and 9th increased, attributed to internal components resonating with the load.
  4. The offline UPS output voltage unbalance factor was 3.91%, the only parameter that failed PRODIST limits.
  5. Output power factor: offline UPS 0.95, online UPS 0.97 (PRODIST range 0.92-1.00).
  6. Offline UPS transfer delays are usually a few milliseconds; online double conversion has no transfer delay but lower efficiency.

Using it in design

  • Choose online double-conversion UPS for loads where power quality improvement is expected; an offline UPS passes harmonics and unbalance through to the load side.
  • Account for UPS input current THD (here 23%-47%) in grid- and generator-side filter and sizing decisions.
  • For offline UPS installations, verify output voltage unbalance and the resonance-driven rise of 5th, 7th and 9th harmonics by measurement before commissioning.

Who should read it

Electrical engineers selecting UPS topology and assessing harmonic impact on the supply side.

Document contents

  1. I. Introduction
  2. II. Literature Review
  3. III. Tests
  4. IV. Results Analysis
  5. V. Conclusion
  6. VI. Author's Contribution
  7. VII. References

Related standards

  • ANEEL PRODIST Module 8

Read the document

ups-technologies-power-quality-2021.pdf

PDF · 1.1 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Rafael Provenzano Jou Alves; André Abel Augusto; Marcio Zamboti Fortes
Publisher
ITEGAM- Journal of Engineering and Technology for Industrial Applications (ITEGAM-JETIA) (GN1 Sistemas e Publicacoes Ltd.)
Year
2021
Volume
7
Issue
28
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
doi.org
Original licence note

Page 1 states 'This work is licensed under the Creative Commons Attribution International License (CC BY 4.0)'.

Citation

Rafael Provenzano Jou Alves; André Abel Augusto; Marcio Zamboti Fortes (2021). Analysis of Power Quality Parameters at Comparing UPS of Different Technologies. ITEGAM- Journal of Engineering and Technology for Industrial Applications (ITEGAM-JETIA) (GN1 Sistemas e Publicacoes Ltd.). 7(28). https://doi.org/10.5935/jetia.v7i28.747

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.