Is PUE actually going UP?

Uptime Institute Journal (Uptime Institute) · A. Lawrence

A. Lawrence's Uptime Institute Journal article discusses the 2019 survey finding that average PUE rose from 1.58 to 1.67, and the possible reasons.

On this page

Overview

The article starts from the finding of the 2019 Uptime Institute survey that average PUE rose from 1.58 in 2018 to 1.67 in 2019. The sample covered 624 sites. The author asks whether the rise reflects a real loss of efficiency or a measurement and sampling effect, and lists possible explanations. The article should be read as a short, open-ended assessment that questions how averages of a widely accepted industry metric should be interpreted.

The suggested causes include hotter weather, lower utilisation and higher power density. The piece stresses that these factors were not measured individually, so the exact cause of the rise is unknown; the text is therefore commentary rather than proof. In other words, the rise has not been separated by cause with data, so the results should be treated as a list of factors to watch rather than as a firm cause-and-effect relationship in design decisions.

The most important distinction in the article is between average PUE per site and overall PUE per kW of IT load. As work shifts to cloud and large colocation facilities, the site average can rise while the load-weighted overall PUE falls. The author also notes that PUE is not the only efficiency metric and cautions against reading it in isolation.

As context, hyperscale and large colocation operators claim annual or design PUE between 1.1 and 1.4. The largest efficiency gains are described as having come between 2007 and 2013 from hot/cold separation, higher temperatures and cooling controls, after which progress slowed. The declared low values should therefore be read as the results of large facilities with particular operating conditions, not as a target every sector average could reach.

Key points

  1. Average PUE rose from 1.58 in 2018 to 1.67 in 2019 (sample of 624).
  2. Hyperscale and big colo operators claim annual or design PUE between 1.1 and 1.4.
  3. The largest efficiency gains came in 2007-2013 from hot/cold separation, higher temperatures and cooling controls.
  4. Possible causes include hotter weather, lower utilisation and higher density.
  5. Average PUE per site is not the same as overall PUE per kW of IT load.
  6. Load-weighted overall PUE is falling as work moves to cloud and large colos.
  7. PUE is not the only efficiency metric and should not be read alone.

Using it in design

  • In a PUE benchmark display, show the survey average next to the hyperscale range.
  • State that the average across facility PUE values is not load-weighted.
  • When setting a design PUE target, treat utilisation and seasonal temperature effects as separate scenarios.
  • Present PUE together with complementary metrics in efficiency reports.
  • Treat hot/cold separation, higher operating temperature and cooling controls as proven sources of PUE improvement.

Who should read it

Data center designers and energy managers who set efficiency targets or interpret PUE data.

Publication details

Authors
A. Lawrence
Publisher
Uptime Institute Journal (Uptime Institute)
Year
2019
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Uptime Institute Journal article, copyright Uptime Institute, no open licence. Citation only.

Citation

A. Lawrence (2019). Is PUE actually going UP?. Uptime Institute Journal (Uptime Institute). https://journal.uptimeinstitute.com/is-pue-actually-going-up/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.