Free cooling by location
Calculate how many hours a year outdoor temperatures allow free cooling at your location, from NOAA 2024 hourly data.
Result
Select Calculate to see the result.
Method
- Water-side threshold = supply temperature − tower approach − heat-exchanger approach (wet bulb). Air-side threshold = supply temperature − air heat-exchanger approach (dry bulb).
- Hours are summed over 1 °C bins whose upper edge is at or below the threshold; a bin that straddles the threshold is excluded. Share = suitable hours / 8,784.
Assumptions and limits
Data is the NOAA NCEI ISD 2024 station-year, not a typical meteorological year. For each UTC hour the nearest valid observation within 30 minutes is used, gaps of up to 3 hours are filled and the distribution is scaled to annual hours. A station-year is used only with at least 90% direct and 95% filled coverage.
Wet bulb is derived from dry bulb and dew point with pressure correction. The result counts hours that are suitable by temperature; actual free-cooling time depends on humidity limits, air quality, freeze protection, plant capacity and control strategy.
The same calculation in the design model
In SoSo CAD the same climate data feeds the cooling plant’s annual energy estimate and the PUE calculation.
The personal plan is free. Detailed studies and IFC, DXF and PDF deliverables come with the paid plans.