Generator sizing

Calculate the continuous demand on the generator in kW and kVA, including UPS losses, battery recharge and auxiliaries.

Inputs

0.01 kW–10,000,000 kW
1%–100%
0 kW–1,000,000,000 kW
0 kW–1,000,000,000 kW
0.01–1
0.01%–100%
0.01%–100%

Result

Select Calculate to see the result.

Method

  1. P = IT load / UPS efficiency + battery recharge + auxiliaries. S = P / aggregate power factor.
  2. Required kW = P / site factor. Required kVA = S / site factor / nonlinear-load factor.

Assumptions and limits

UPS efficiency, recharge power, auxiliaries and power factor are examples. Enter the manufacturer’s derating factors for temperature, altitude and harmonic load; 100% does not reflect site conditions.

The kW/kVA relationships are those of SoSo CAD’s steady-state check. Leading power factor, load steps, inrush currents, voltage and frequency recovery, and fuel autonomy are checked separately.

The same calculation in the design model

In SoSo CAD the generator load is summed from the power paths, and load steps and fuel autonomy are checked against the manufacturer data you enter.