N+1 and 2N comparison

Compare the module count and installed capacity needed to serve the same load with N+1 and with 2N.

Inputs

0.01 kW–1,000,000,000 kW
0.01 kW–1,000,000,000 kW
0.01%–100%

Result

Select Calculate to see the result.

Method

  1. N = round up(load / (module rating × utilisation limit)).
  2. N+1 = N duty modules plus one standby. 2N = two independent N paths, each able to carry the full load.

Assumptions and limits

Modules are assumed identical with balanced load sharing. N+1 is checked with one module out, 2N with one whole path out. The 100% limit is SoSo CAD’s starting value, not a recommended operating target.

The result is an installed-capacity comparison. A/B independence, common failure points, transfer time and concurrent maintenance are assessed separately; availability or Tier assessment needs failure scenarios.