N+1 and 2N comparison
Compare the module count and installed capacity needed to serve the same load with N+1 and with 2N.
Result
Select Calculate to see the result.
Method
- N = round up(load / (module rating × utilisation limit)).
- N+1 = N duty modules plus one standby. 2N = two independent N paths, each able to carry the full load.
Assumptions and limits
Modules are assumed identical with balanced load sharing. N+1 is checked with one module out, 2N with one whole path out. The 100% limit is SoSo CAD’s starting value, not a recommended operating target.
The result is an installed-capacity comparison. A/B independence, common failure points, transfer time and concurrent maintenance are assessed separately; availability or Tier assessment needs failure scenarios.
The same calculation in the design model
In SoSo CAD N+1, 2N and block-redundant options are designed for the same load and compared through failure scenarios on the design’s power paths.
The personal plan is free. Detailed studies and IFC, DXF and PDF deliverables come with the paid plans.