Artificial Intelligence-Based Temperature Twinning and Pre-Control for Data Center Airflow Organization
Energies (MDPI AG) · Na Huang, Xiang Li et al.
A data-driven thermal twin for a 200-cabinet hall built from contained micro-modules: an LSTM forecasts supply, return, cold-aisle and hot-aisle temperatures, and a Deep Q-Network adjusts air-conditioning output so predicted hotspots do not occur.
CC BY 4.0 — share with attribution
On this page
Overview
The study asks how AI-based temperature forecasting and air-conditioning control can prevent hotspots before they form and improve energy efficiency. The test room is 5.4 m high with a 1.0 m raised floor, five contained micro-modules of 40 cabinets (200 total, 2.2 m high, 5 kW each) and 70% open floor tiles. Fourteen 100 kW units (5 duty + 2 standby per side) of 25,000 m³/h each sit in side AC rooms. The room has 728 sensor points sampled every 15 min, with temperature accuracy ±0.5 °C over -10 to +50 °C.
The LSTM forecasts supply, return, cold-aisle and hot-aisle temperatures from the temperature and equipment power of the past 15 time steps. A DQN controller then adjusts air-conditioning output so that predicted hotspots do not occur. Setpoints were supply air 26 ± 1 °C, return air 39 ± 1 °C and cold aisle 27 ± 1 °C, with a target prediction error of no more than ±0.4 °C.
Results: LSTM mean absolute errors were 0.32 °C for supply air, 0.21 °C for return air, 0.36 °C for the cold aisle and 0.19 °C for the hot aisle, with cabinet power predicted within ±2 kW. The DQN controller cut PUE by an average of 2.6% and WUE by 2.5% over a year.
Limits: the object is limited because the building structure could not be modified, the cooling and air-supply type is simple, and only particular AI verification was done. As a learned, sensor-based model rather than a CFD surrogate, it shows what instrumentation operational twins need.
Key points
- Test room: 5.4 m height, 1.0 m raised floor, five contained micro-modules of 40 cabinets (200 total, 5 kW each, 2.2 m high), 70% open floor tiles; fourteen 100 kW units (5 duty + 2 standby per side) of 25,000 m³/h each in side AC rooms.
- The room has 728 sensor points sampled every 15 min, with temperature accuracy ±0.5 °C over -10 to +50 °C.
- Setpoints: supply air 26 ± 1 °C, return air 39 ± 1 °C and cold aisle 27 ± 1 °C, with a target prediction error of no more than ±0.4 °C.
- LSTM mean absolute errors: 0.32 °C supply air, 0.21 °C return air, 0.36 °C cold aisle and 0.19 °C hot aisle; cabinet power predicted within ±2 kW.
- The DQN controller cut PUE by an average of 2.6% and WUE by 2.5% over a year.
Using it in design
- For an operational thermal twin, define adequate sensor density covering supply, return, cold-aisle and hot-aisle temperatures and equipment power (728 points at 15-minute sampling in this study).
- Set the prediction error target (±0.4 °C) and setpoints (supply 26 °C, return 39 °C, cold aisle 27 °C) as twin validation criteria.
- Design air-conditioning control as pre-control that acts before hotspots form, and weigh the PUE/WUE gain (about 2.5%) against sensor and control investment.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers and researchers developing data-centre cooling control and operational twins.
Document contents
- 1. Introduction
- 2. Materials and Methods
- 3. Digital Twin (Simulation) Module (3.1 Application of Digital Twin Technology in Data Center Cooling Systems, 3.2 Time Series Based Temperature Prediction Model)
- 4. Optimal Control Module: Hotspot and Fault Pre-Control and Group Control (4.1 Hot Spots and Fault Pre-Control, 4.2 Optimised Control Module for Group Control)
- 5. Experiments (5.1 Data Center Simulation Platform, 5.2 Experimental Data, 5.3 Experimental Setup, 5.4 Experiments and Analysis of Data Center Task Prediction)
- 6. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
- ISO/IEC 30134-2 (PUE)
- ISO/IEC 30134-9 (WUE)
Read the document
ai-temperature-twinning-airflow-2023.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Na Huang; Xiang Li; Quanming Xu; Ronghao Chen; Huidong Chen; Aidong Chen
- Publisher
- Energies (MDPI AG)
- Year
- 2023
- Volume
- 16
- Issue
- 16
- Pages
- 6063
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Na Huang; Xiang Li; Quanming Xu; Ronghao Chen; Huidong Chen; Aidong Chen (2023). Artificial Intelligence-Based Temperature Twinning and Pre-Control for Data Center Airflow Organization. Energies (MDPI AG). 16(16), 6063. https://doi.org/10.3390/en16166063
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.