GRAPE-UPS: Direction-Constrained Peer Anomaly Detection for Weak Batteries in Data-Center UPS Strings
IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)) · Shibo Luo, Bin Shen et al.
A monitoring method for series-connected UPS battery strings that compares each battery with its peers during the same load event and scores only deviations in physically adverse directions (for example higher voltage drop), ranking weak units for maintenance.
CC BY 4.0 — share with attribution
On this page
Overview
In a series-connected UPS battery string the same discharge current flows through every unit, so the first unit to reach an unsafe voltage limits the usable capacity of the whole string. The difficulty is that load and environmental variation can hide the weak unit's degradation signature. GRAPE-UPS uses each shared load event to define a robust peer reference and keeps only departures in physically adverse directions; the directed peer score determines maintenance ranking, while one-class reconstruction and labelled validation support a separate, weakly supervised alert pathway.
Evaluation is almost entirely on simulated strings plus a separate electrochemical simulation benchmark. Across 15 independent simulated realisations per difficulty level, mean AUPRC was 0.904, 0.839 and 0.823 for easy, medium and hard conditions and exceeded all 18 comparison methods, with paired differences significant after correction across 54 comparisons. On the independent electrochemical benchmark, directed peer scoring achieved AUPRC 0.848 under nominal conditions and 0.850-0.877 under operating shifts.
The method requires comparable units and a healthy majority in the string. The available field record had no independent health labels, so prospective validation against capacity tests is still needed; results were evaluated under simulation conditions and transfer to real installations is not proven.
The paper is therefore best read as an operations paper with limited design content. Its design relevance is in showing how valuable per-block battery monitoring and peer comparison on each load event are for detecting weak units.
Key points
- In a series UPS string the same discharge current flows through every unit, so the first unit to reach an unsafe voltage limits the usable capacity of the whole string.
- Across 15 simulated realisations per difficulty level, mean AUPRC was 0.904, 0.839 and 0.823 for easy, medium and hard conditions, better than all 18 comparison methods.
- All 54 paired comparisons were significant after Holm correction; direction and reference controls showed the contribution of combining event-conditioned peers with adverse-direction evidence.
- On an independent electrochemical simulation benchmark, directed peer scoring achieved AUPRC 0.848 under nominal conditions and 0.850-0.877 under operating shifts.
- The method requires comparable units and a healthy majority in the string.
- The field record lacked independent health labels, so prospective validation against capacity tests is still needed.
Using it in design
- Require block-level (per-unit) voltage and resistance monitoring in UPS battery monitoring rather than string totals, citing that one weak unit in a series string limits the whole string's capacity.
- Produce the weak-unit ranking by relative comparison with peers on the same load event, and turn only adverse-direction deviations (such as higher voltage drop) into alerts.
- Validate monitoring results with periodic capacity tests; do not treat thresholds based only on simulation as definitive in the field.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Facility engineers and operations teams setting UPS battery monitoring and maintenance strategy in data centres.
Document contents
- I. Introduction
- II. Related Work (A. Threshold-, trend-, and model-based battery diagnosis, B. Statistical and learned pack-relative diagnosis, C. General multivariate time-series anomaly detection, D. Research gap and positioning of GRAPE-UPS)
- III. GRAPE-UPS Method (A. Problem formulation and design rationale, B. Direction-constrained group-relative evidence, C. Decoupled reconstruction and decision, D. Temporal evidence accumulation, E. End-to-end decision procedure)
- IV. Experimental Design (A. Simulation datasets, B. Baselines and evaluation discipline, C. Evaluation metrics and sensitivity analyses, D. Physical and operational robustness)
- V. Results
- VI. Discussion (A. What the results establish, B. Relation to existing battery and time-series methods, C. Operational interpretation, D. Limitations and next validation step)
- VII. Conclusion
Read the document
grape-ups-weak-battery-detection-2026.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Shibo Luo; Bin Shen; Xiaoning Chen; Yiquan Fang; Huifeng Wang
- Publisher
- IEEE Access (Institute of Electrical and Electronics Engineers (IEEE))
- Year
- 2026
- Pages
- 1-1
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- ieeexplore.ieee.org
Original licence note
Accepted author version; page footer states 'This work is licensed under a Creative Commons Attribution 4.0 License'.
Citation
Shibo Luo; Bin Shen; Xiaoning Chen; Yiquan Fang; Huifeng Wang (2026). GRAPE-UPS: Direction-Constrained Peer Anomaly Detection for Weak Batteries in Data-Center UPS Strings. IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)). 1-1. https://doi.org/10.1109/ACCESS.2026.3753456
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.