A Comparative CFD Study of Two Air Distribution Systems with Hot Aisle Containment in High-Density Data Centers
Energies (MDPI AG) · Jinkyun Cho, Jesang Woo et al.
A CFD comparison for a Korean reference hall with ducted hot-aisle containment (HAC) and 100 racks (40 at 16 kW, 60 at 8.8 kW) served by six perimeter CRAHs: raised-floor (down-flow) supply versus hard-floor supply in which the CRAHs blow straight into open cold aisles.
CC BY 4.0 — share with attribution
On this page
Overview
The study asks how the thermal performance of raised-floor and hard-floor air distribution differs with HAC in high-density data centres, and how that difference changes when a cooling unit fails. The IT room has 40 A-type racks at 16 kW and 60 B-type racks at 8.8 kW, 1830 mm cold aisles and 1220 mm hot aisles, ducted HAC, six CRAHs (234,000 m³/h total) supplying 15 °C and a 15 °C server delta-T. Both layouts were tested with all six units running and with the unit serving the high-density rows failed (N-1).
Under normal cooling, mean inlet temperatures were 16.5 °C (raised floor) and 16.9 °C (hard floor), but maximum inlet temperatures were 20.6 °C and 30.2 °C. Only 97% of racks met the ASHRAE recommended range on the hard floor, with failures in the racks nearest the CRAHs. Maximum rack recirculation ratio was 25.7% on the raised floor versus 50% on the hard floor, meaning some hard-floor racks received only half their required airflow. On the hard floor, supply velocities of 10 m/s or more persisted to the eighth rack position, versus the fourth with a raised floor, which explains the starvation of near-CRAH racks.
With one CRAH failed (N-1), the remaining five kept almost normal conditions on the raised floor. On the hard floor, more racks had recirculation above 40-50%, with inlet temperatures of about 26.1-30.4 °C. The authors report that raised-floor HAC improved air distribution efficiency by 28% over hard-floor HAC, equivalent to a 40% reduction in racks with recirculation above 20%.
Limits: the model is not validated against field measurements, and results depend on one reference hall geometry, CRAH layout and 15 °C supply. The conclusion is that HAC systems with a raised floor have higher cooling efficiency than those with a hard floor.
Key points
- IT room: 40 A-type racks at 16 kW and 60 B-type racks at 8.8 kW, 1830 mm cold aisles, 1220 mm hot aisles, ducted HAC, six CRAHs (234,000 m³/h total) supplying 15 °C, 15 °C server delta-T.
- Under normal cooling, mean inlet temperatures were 16.5 °C (raised floor) and 16.9 °C (hard floor); maximum inlet temperatures were 20.6 °C and 30.2 °C; only 97% of racks met the ASHRAE recommended range on the hard floor.
- Maximum rack recirculation ratio was 25.7% on the raised floor versus 50% on the hard floor; some hard-floor racks received only half their required airflow.
- On the hard floor, supply velocities of 10 m/s or more persisted to the eighth rack position, versus the fourth with a raised floor.
- With one CRAH failed (N-1), the remaining five kept almost normal conditions on the raised floor; on the hard floor more racks had recirculation above 40-50%, with inlet temperatures of about 26.1-30.4 °C.
- The authors report raised-floor HAC improved air distribution efficiency by 28% over hard-floor HAC, equivalent to a 40% reduction in racks with recirculation above 20%.
Using it in design
- In high-density HAC halls, prefer a raised floor to hard-floor supply; on a hard floor high-velocity jets can starve the racks nearest the CRAHs and draw hot air back into them.
- Run cooling unit failure (N-1) as a separate scenario in thermal verification and report recirculation ratio and maximum inlet temperature by rack.
- For hard-floor supply, add CRAH discharge velocity and rack distance (10 m/s jets persisting to the eighth rack) to the design check.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Cooling designers choosing between raised-floor and hard-floor air distribution for high-density data halls.
Document contents
- 1. Introduction
- 2. Methodology (2.1 Analytic Validity of CFD Simulation for Data Centers, 2.3 Basic Analysis Model: IT server room, server, hot aisle containment; 2.4 CFD Analysis Alternatives)
- 3. Numerical Analysis Results (3.1 Normal Cooling Conditions (ALT-1 and ALT-2): temperature distribution, airflow distribution, inlet temperature, recirculation ratio, operational net cooling power; 3.2 Cooling fault conditions: same measures)
- 5. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
hac-air-distribution-comparison-2020.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Jinkyun Cho; Jesang Woo; Beungyong Park; Taesub Lim
- Publisher
- Energies (MDPI AG)
- Year
- 2020
- Volume
- 13
- Issue
- 22
- Pages
- 6147
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Jinkyun Cho; Jesang Woo; Beungyong Park; Taesub Lim (2020). A Comparative CFD Study of Two Air Distribution Systems with Hot Aisle Containment in High-Density Data Centers. Energies (MDPI AG). 13(22), 6147. https://doi.org/10.3390/en13226147
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.