Inform UPS - Uninterruptible Power Supply Catalogue
Inform Elektronik
Inform Elektronik's (Legrand group) UPS product catalogue, with full specification tables for its single- and three-phase online ranges and the Modulera modular UPS up to 800 kVA.
On this page
Overview
This is a product catalogue rather than a white paper, but its tables give the fields a UPS catalog needs: IEC/EN 62040 classification, input/output power factor, THDi/THDv, online and eco-mode efficiency, overload capability, battery string options, transfer times, parallel limits and environmental limits.
Modulera 30-800 kVA uses 30 kW or 50 kW hot-swappable modules in 150-800 kVA frames, up to 4 frames in parallel, output PF 1.0 and efficiency of at least 95-96.5%. Overload is 110% for 60 min, 125% for 10 min and 150% for 1 min, with 0 ms transfer from utility to battery and utility to bypass. Modulera 20-200 kVA uses 20 kVA/18 kW modules, input THDi down to 3%, PF 0.99 or better, efficiency up to 94% (97% eco) and is classified VFI-SS-111 under EN/IEC 62040-3.
The three-phase online range (10-250 kVA) has output PF 1, THDi below 3%, THDv below 2%, efficiency up to 96.5% online and 98.5% eco, and parallel operation of up to 8 units. Pyramid DSP T (10-120 kVA, with output isolation transformer) has output PF 0.8, efficiency of at least 90%, overload of 125% for 10 min and 150% for 1 min, and a maximum altitude without derating below 1,000 m. Operating temperature is 0-40 C, with 20-25 C recommended for battery life.
Key points
- Modulera 30-800 kVA: 30/50 kW modules, 150-800 kVA frames, up to 4 frames in parallel, output PF 1.0, efficiency >=95-96.5%.
- Modulera 30-800 kVA overload: 110% 60 min, 125% 10 min, 150% 1 min; utility-to-battery and utility-to-bypass transfer 0 ms.
- Modulera 20-200 kVA: 20 kVA/18 kW modules, THDi down to 3%, PF >=0.99, efficiency up to 94% (97% eco), VFI-SS-111.
- Three-phase online (10-250 kVA): PF 1, THDi <3%, THDv <2%, 96.5% online / 98.5% eco, up to 8 units in parallel.
- Pyramid DSP T (10-120 kVA, isolation transformer): PF 0.8, efficiency >=90%, overload 125% 10 min / 150% 1 min, altitude <1,000 m.
- Operating temperature 0-40 C; 20-25 C recommended for battery life.
Using it in design
- Keep module size, frame maximum, maximum parallel frames, output PF, online and eco efficiency, IEC 62040-3 class, overload curve points, THDi, altitude limit and battery string voltage options as UPS catalog fields.
- Check N+X module redundancy within a frame and across up to 4 frames.
- Flag use of eco-mode efficiency without stating the change of class.
- Derate above the stated altitude.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Electrical designers selecting UPS and product owners defining UPS catalog fields.
Related standards
- IEC 62040-1
- IEC 62040-2
- IEC 62040-3
Publication details
- Authors
- Inform Elektronik
- Publisher
- Inform Elektronik
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Inform Elektronik (2025). Inform UPS - Uninterruptible Power Supply Catalogue. Inform Elektronik. https://www.informups.com/inform-catalog-2022.pdf
Events on this subject
- Electricity Eurasia 2027
- ELECO 2026 Elektrik-Elektronik ve Biyomedikal Mühendisliği Konferansı
- 7x24 Exchange Spring Conference
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.