Retrofit Optimization of Raised-Floor Plenum Thermal Performance for Energy-Efficient and Sustainable Operation of Non-Standard Campus Data Centers

Sustainability (MDPI AG) · Jinuo Zhang, Zhiyi Wang et al.

A field-calibrated 6SigmaDC model of a small, asymmetric campus server room in Hangzhou: 18.0 m × 8.4 m × 3.6 m, 0.4 m plenum, 36 racks of 0.35-2.94 kW, no containment; plenum retrofits are tested.

CC BY 4.0 — share with attribution

On this page

Overview

The study asks how disordered airflow distribution and prominent local hotspots in non-standard campus data centres can be fixed with plenum retrofits. The room is 18.0 m × 8.4 m × 3.6 m with a 0.4 m raised floor, 36 racks at 0.35-2.94 kW, no containment, and three precision units totalling 8 m³/s at 18 °C supply. Validation: temperature MAE no more than 0.9 °C in all zones and velocity MAE no more than 0.20 m/s, with point velocity deviations reaching about 18-30% near tile joints and pipe obstructions. Tiles were modelled as 50% porous media.

Pre-screening found the best perforation ratio and position for a transverse plenum baffle. Perforation screening (0.3 m from the outlet): 30% open gave uniformity index 0.62 with an 18.7% resistance increase; 50% open gave 0.58 with 8.5%; 70% was worse. A 50% baffle was selected. Position screening at 50% perforation: 0.3 m from the unit outlet was best (uniformity 0.58, local velocity 4.2 m/s); at 0.9 m the uniformity index was only 0.52.

A factorial set of eight scenarios then combined baffle types (none, perforated, solid partitions, composite) with uniform or graded variable-opening tiles. The optimal scenario S4 (perforated baffle plus graded tile openings) cut the tile net-flow range from 0.100 to 0.077 m³/s, lowered CV from 12.8% to 10.8% and raised the uniformity index by 10.7%; solid partition baffles alone (S2) widened the range to 0.132 m³/s. For S4, SHI fell from 0.42 to 0.35, maximum rack inlet temperature fell from 27.2 °C to 26.7 °C, and all racks met the 27 °C ASHRAE recommended limit.

Energy estimate: about 1.5 °C higher supply setpoint at 2-3% COP gain per °C (3-4.5% refrigeration saving), minus an 8.5% fan-power penalty (about 0.4% of total), gives a PUE change from about 1.90 to 1.87. Limits: a single small, asymmetric room; results depend on this geometry and the energy estimate rests on simple assumptions.

Key points

  1. The room is 18.0 m × 8.4 m × 3.6 m with a 0.4 m raised floor, 36 racks at 0.35-2.94 kW, no containment, and three precision units totalling 8 m³/s at 18 °C supply.
  2. Validation: temperature MAE no more than 0.9 °C in all zones and velocity MAE no more than 0.20 m/s; point velocity deviations reached about 18-30% near tile joints and pipe obstructions; tiles modelled as 50% porous media.
  3. Baffle perforation screening (0.3 m from the outlet): 30% open gave uniformity index 0.62 with an 18.7% resistance increase; 50% open gave 0.58 with 8.5%; 70% was worse; 50% was selected.
  4. Baffle position screening at 50% perforation: 0.3 m from the unit outlet was best (uniformity 0.58, local velocity 4.2 m/s); at 0.9 m the uniformity index was only 0.52.
  5. Optimal scenario S4 (perforated baffle plus graded tile openings) cut the tile net-flow range from 0.100 to 0.077 m³/s, lowered CV from 12.8% to 10.8% and raised the uniformity index by 10.7%; solid partition baffles alone (S2) widened the range to 0.132 m³/s.
  6. For S4, SHI fell from 0.42 to 0.35, maximum rack inlet temperature fell from 27.2 °C to 26.7 °C, and all racks met the 27 °C ASHRAE recommended limit.
  7. Energy estimate: about 1.5 °C higher supply setpoint at 2-3% COP gain per °C (3-4.5% refrigeration saving), minus an 8.5% fan-power penalty (about 0.4% of total), gives PUE from about 1.90 to 1.87.

Using it in design

  • For plenum imbalance, consider a 50%-perforated transverse baffle about 0.3 m from the unit outlet; 50% open gave a smaller resistance increase than 30% (8.5% against 18.7%).
  • Combine the perforated baffle with graded variable-opening tiles (restricting near-end tiles, opening far-end tiles); a solid baffle alone made distribution worse.
  • Calculate the fan-power penalty (8.5%) together with the energy saving and report the net PUE effect (1.90 to 1.87).
  • Show with a full-room thermal verification that all rack inlets stay below 27 °C.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling engineers retrofitting raised-floor plenums in small, irregular campus server rooms.

Document contents

  1. 1. Introduction
  2. 2. Materials and Methods (2.1 Test Facility, 2.2 Field Measurements, 2.3 CFD Simulation: boundary conditions, solution control, mesh generation and independence verification)
  3. 3. Model Validation (3.1 Cabinet Inlet/Outlet Temperature Validation, 3.2 Perforated Floor Tile Outlet Validation, 3.3 Cold/Hot Aisle Temperature Validation, 3.4 Conclusions on Model Reliability)
  4. 4. Scenarios and Results (4.1 Scenario Design, 4.2 Scenario Analysis, 4.3 Evaluation Metrics, 4.4 Full-Room Thermal Verification)
  5. 5. Discussion (5.1 Analysis of Energy Consumption and PUE Impact, 5.2 Discussion of Engineering Applicability and Limitations)
  6. 6. Conclusions

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments

Read the document

raised-floor-plenum-retrofit-2026.pdf

PDF · 5.9 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Jinuo Zhang; Zhiyi Wang; Guoming Jiang
Publisher
Sustainability (MDPI AG)
Year
2026
Volume
18
Issue
16
Pages
8144
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

Citation

Jinuo Zhang; Zhiyi Wang; Guoming Jiang (2026). Retrofit Optimization of Raised-Floor Plenum Thermal Performance for Energy-Efficient and Sustainable Operation of Non-Standard Campus Data Centers. Sustainability (MDPI AG). 18(16), 8144. https://doi.org/10.3390/su18168144

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.