An Update on Lithium-ion Battery Use in Critical Facilities (Safety Rules)
Vertiv
This 2018 Vertiv Q&A-style white paper compares Li-ion and VRLA qualitatively for data-centre UPSs and summarises the safety standards that applied at the time.
On this page
Overview
The document compares Li-ion and VRLA qualitatively. Li-ion systems can reduce battery footprint by 50-75% against VRLA, weigh less and have roughly double the effective life, while VRLA batteries lose about 50% of life for every 10°C rise in temperature. A 2013 Ponemon study found UPS and battery failure to be the leading cause of data-centre downtime. The text also explains why UPS-grade cells differ from consumer cells.
Safety and fire-code requirements are the centre of gravity. The 2018 NFPA 1 Section 52.3 requirements apply to Li-ion systems above 20 kWh (about a 5-minute 50 kW UPS load): batteries need UL 1973 listing, an approved BMS supplied with the batteries, a listed non-combustible locked cabinet, automatic sprinklers and smoke detection. Relevant standards are IEC 62619 (industrial Li cells including BMS), IEC 62897, UN 38.3 and IEC 62281 for transport, IEC 62477-1, IEC 62040-1 and IEC 61439-1/2.
Chemistry selection weighs LFP, NMC and LMO against LCO. The UPS BMS is two-level: cell-level monitoring of voltage, temperature and current reports to a rack-level controller that manages system safety, balancing and switching. The paper recommends only UPS-manufacturer-approved battery systems. Code citations are to 2018 editions, so current fire-code thresholds should be re-verified during a project. The practical message is that battery selection is not only a chemistry choice but a decision about approved pairing with the UPS, listings and room-level fire protection.
Key points
- Li-ion systems can reduce battery footprint by 50-75% versus VRLA, with lower weight and roughly double the effective life.
- VRLA batteries lose about 50% of life for every 10°C rise in temperature.
- A 2013 Ponemon study found UPS and battery failure to be the leading cause of data-centre downtime.
- 2018 NFPA 1 Section 52.3 applies to Li-ion systems above 20 kWh (about a 5-minute 50 kW UPS load): UL 1973 listing, approved BMS supplied with the batteries, listed non-combustible locked cabinet, automatic sprinklers and smoke detection.
- Relevant standards: IEC 62619 (industrial Li cells incl. BMS), IEC 62897, UN 38.3 and IEC 62281 (transport), IEC 62477-1, IEC 62040-1, IEC 61439-1/2.
- The UPS BMS is two-level: cell-level monitoring of voltage, temperature and current reporting to a rack-level controller managing safety, balancing and switching.
- Chemistry options are LFP, NMC, LMO versus LCO; only UPS-manufacturer-approved battery systems are recommended.
Using it in design
- Give the battery catalogue chemistry (LFP/NMC/LMO/VRLA), kWh per cabinet, UL 1973 / IEC 62619 listing, BMS level and approved UPS models.
- When total Li-ion energy in a room exceeds the fire-code threshold (for example 20 kWh), require sprinklers, smoke detection and a hazard mitigation analysis.
- Block pairing Li-ion cabinets with UPS models not on the vendor-approved list.
- Apply temperature derating to VRLA life estimates.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Designers choosing between Li-ion and VRLA in UPS battery rooms and checking fire-code compliance.
Related standards
- NFPA 1
- NFPA 855
- UL 1973
- UL 9540A
- IEC 62619
- IEC 62040-1
- UN 38.3
- IEEE 1679.1
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2018
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Vertiv (2018). An Update on Lithium-ion Battery Use in Critical Facilities (Safety Rules). Vertiv. https://www.vertiv.com/4a12fa/globalassets/documents/white-papers/vertiv-lithium-ion-batteries-safety-wp-en-emea_239293_0.pdf
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.