Technical guideFree to read2023

The Advantages of Using Lithium-Ion Batteries in Single-Phase UPS Applications for Edge Data Centers

Vertiv

This 2023 Vertiv paper makes the case for lithium-ion batteries in single-phase UPSs serving branch offices, server rooms, network closets and edge sites.

On this page

Overview

The paper first lists the weaknesses of VRLA: string failure risk, a 3-5 year life, temperature sensitivity and weight. A 2013 Ponemon study attributed 55% of unplanned outages and one third of UPS failures to VRLA battery failure. VRLA needs about 25°C room temperature for a 3-5 year life, each 15°C rise halves useful life, and end of life is defined at 80% capacity.

On the Li-ion side, UPS chemistries are LFP, LMO and NMC (or LMO/NMC blends). Li-ion has an 8-10 year design life and is still at about 93% capacity when VRLA reaches 80%; it is about 60% lighter, up to 70% smaller and operates at 30°C without life loss. Li-ion rack systems recharge to 90% in under 2 hours versus over 4 hours for VRLA, with up to 24 hours for a full VRLA recharge.

The cost comparison is the paper's decision point: Li-ion's initial cost is 1.75-2.25 times VRLA, yet the 10-year TCO for a 1500 VA UPS is $1,000 against $1,700, a 41% saving, with payback within five years. The saving comes from avoiding battery replacements at remote sites. The document focuses on small single-phase UPSs and does not cover large three-phase systems.

Key points

  1. 2013 Ponemon study: 55% of unplanned outages and one third of UPS failures attributed to VRLA battery failure.
  2. VRLA needs ~25°C room temperature for a 3-5 year life; each 15°C increase halves useful life; end of life is at 80% capacity.
  3. UPS Li-ion chemistries are LFP, LMO and NMC (or LMO/NMC blends).
  4. Li-ion: 8-10 year design life (still ~93% capacity when VRLA reaches 80%), ~60% lighter, up to 70% smaller, operates at 30°C without life loss.
  5. Li-ion rack systems recharge to 90% in under 2 h versus over 4 h for VRLA (up to 24 h for full recharge).
  6. Initial Li-ion cost is 1.75-2.25x VRLA.
  7. 10-year TCO for a 1500 VA UPS is $1,000 vs $1,700 (41% saving), with payback within five years.

Using it in design

  • For edge and closet designs, default the single-phase UPS battery to Li-ion where room temperature is uncontrolled, and show replacement cycles in lifecycle cost (VRLA 3-5 y, Li-ion 8-10 y).
  • Give the catalogue battery design life, recharge time to 90% and maximum ambient without derating.
  • Warn when VRLA is placed in spaces above 25°C.
  • Include travel and labour cost per replacement for remote sites in TCO.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

IT and facilities managers choosing single-phase UPS batteries for many branch and edge sites.

Related standards

  • IEC 62040-1
  • IEC 62619
  • UL 1973

Publication details

Authors
Vertiv
Publisher
Vertiv
Year
2023
Document number
SL-70595
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Vertiv (2023). The Advantages of Using Lithium-Ion Batteries in Single-Phase UPS Applications for Edge Data Centers. Vertiv. SL-70595. https://www.vertiv.com/493b19/globalassets/shared/vertiv_liebert_psi5_lio_advantages-of-using-lithium-ions-batteries-sl-70595.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.