Directional protection and directional zone selectivity
ABB
ABB application paper on the directional (D) protection and directional zone selectivity functions of the PR123/PR333 trip units for LV systems with more than one source.
On this page
Overview
Directional protection D works like a definite-time S function but with two delays, t7FW (forward) and t7BW (backward), applied once threshold I7 is exceeded; it needs no auxiliary supply or dedicated wiring. Direction is decided from reactive power: the phase reactive power must exceed 2% of nominal phase power, otherwise the relay uses the shorter of t7FW and t7BW.
Directional zone selectivity requires zone selectivity S and G to be off and a 24 V DC auxiliary supply; each relay has DFin/DBin inputs and DFout/DBout block outputs. Breakers bounding the faulted section trip at t7s, and if one fails to open the next upstream breaker opens after about a further 100 ms. Without auxiliary power, directional zone selectivity degrades to plain directional protection with t7FW/t7BW times, which the designer must allow for.
The paper shows how lock signals between relays isolate a faulted section in ring or meshed networks. Worked examples cover two generators on a common busbar, a double-transformer substation with bus tie, and a board fed by LV generators in parallel with transformers, followed by a practical commissioning guide.
Key points
- D works like a definite-time S with two delays (t7FW forward, t7BW backward) above threshold I7; no auxiliary supply or dedicated wiring needed.
- Direction comes from reactive power; phase reactive power must exceed 2% of nominal phase power, otherwise the shorter of t7FW and t7BW is used.
- Directional zone selectivity needs S and G zone selectivity off and a 24 V DC auxiliary supply; DFin/DBin inputs and DFout/DBout outputs.
- Breakers bounding the faulted section trip at t7s; if one fails, the next upstream opens about 100 ms later.
- Without auxiliary power it degrades to plain directional protection with t7FW/t7BW times.
- Examples: two generators on one busbar, MV/LV substation with bus tie, LV generators in parallel with transformers.
Using it in design
- For main switchboards with two transformers plus bus tie, or generator paralleling boards, flag that conventional time selectivity cannot discriminate fault direction and propose directional or directional-zone selectivity on incomers and bus tie.
- Capture per breaker whether it supports D/ZSI-D and whether auxiliary supply is present.
- Warn that loss of 24 V DC auxiliary reverts to slower directional times and include that in the selectivity study.
Who should read it
Electrical engineers designing selectivity for multi-source LV boards with parallel transformers or generators.
Related standards
- IEC 60947-2
- IEC 60947-1
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2008
- Document number
- 1SDC007401G0201
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
ABB (2008). Directional protection and directional zone selectivity. ABB. 1SDC007401G0201. https://library.e.abb.com/public/c1a005fc597b0df7c1257ac5003d1c59/1SDC007401G0201.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.