UPSon Sinus 5–6 kVA Uninterruptible Power Supply User Manual

Original title UPSon Sinus 5–6 kVA Kesintisiz Güç Kaynağı Kullanım Kılavuzu

AC/DC Elektronik

The AC/DC Elektronik manual for the 5-6 kVA UPSon Sinus on-line UPS: 6000 VA / 4200 W, 0 ms transfer, up to 90% efficiency in normal mode and 97% in ECO mode, 1-4 units in parallel and a 240 Vdc battery.

On this page

Overview

The manual covers safety instructions, product information, installation and use, troubleshooting, software installation, customer slot options and technical data for AC/DC Elektronik's 5-6 kVA true on-line, sine-output UPSon Sinus series. The unit uses 20 kHz pulse width modulation, handles inrush currents through a high crest factor and offers four operating modes: normal, ECO, CF50 and CF60.

Protection features include transfer to bypass at 150% overload with automatic return to inverter when load normalises, output shutdown on short circuit, bypass on over-temperature and DC-start during a mains outage. The safety section lists rules such as commissioning by authorised persons, output voltage present even without mains, 0 to 40 degree ambient and at most 90% relative humidity, and ventilation clearance.

Technical data: input voltage tolerance 160-280 Vac, frequency 45-65 Hz, output capacity 6000 VA / 4200 W (rated power factor 0.7), THD under 3%, static regulation under 1%. The battery set is 20 maintenance-free 12 V / 5 Ah dry cells (240 Vdc) charging to 90% in about 4 hours; 5 minutes of autonomy is stated with external batteries. It is a product manual, not a design guide.

Key points

  1. Capacity 6000 VA / 4200 W; rated power factor 0.7; output voltage selectable 220/230/240 Vac.
  2. Input voltage tolerance 160-280 Vac (160-176 Vac only below 75% load), frequency 45-65 Hz, input power factor up to 0.99.
  3. Transfer time 0 ms; efficiency up to 90% in normal mode and up to 97% in ECO mode.
  4. Four operating modes: normal, ECO, CF50 and CF60; up to 4 units can run in parallel.
  5. Bypass at 150% overload, output shutdown on short circuit, bypass on over-temperature.
  6. Battery: 20 x 12 V / 5 Ah, 240 Vdc; 90% charge in about 4 hours; 5 minutes autonomy (external battery).
  7. Operating ambient 0-40 degrees, at most 90% relative humidity; 40 degrees up to 2000 m, 35 degrees at 3000 m; noise under 50 dB at 1 m.
  8. Batteries must be charged every 2-3 months in storage or non-use, otherwise the warranty is void.
  9. Dimensions 440x176x680 mm, weight 55 kg.

Using it in design

  • When selecting a 5-6 kVA UPS for small rooms or edge points, use the kVA versus kW difference (0.7 power factor, 4200 W) in the load calculation.
  • Write the 97% ECO efficiency versus 90% normal-mode efficiency into the operating policy together with the protection trade-off.
  • Evaluate battery temperature against 25 degrees; add shortened battery life in hotter ambient to the maintenance plan.
  • Add address and ID settings for parallel operation (1-4 units) to the commissioning checklist.
  • For monitoring, note the RS232, RS485, USB, dry-contact and SNMP slot options and that some cards cannot be used simultaneously in building-management integration.

Who should read it

Technical staff and small-facility designers who install, operate or specify 5-6 kVA UPSs.

Document contents

  1. Important safety instructions
  2. Product information
  3. Installation and use
  4. Troubleshooting guide
  5. Installation guide for the software supplied with the UPS
  6. Customer slot options
  7. Technical specifications

Publication details

Authors
AC/DC Elektronik
Publisher
AC/DC Elektronik
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.

Citation

AC/DC Elektronik UPSon Sinus 5–6 kVA Kesintisiz Güç Kaynağı Kullanım Kılavuzu. AC/DC Elektronik. https://www.acdc.com.tr/tr/pdf/upson-sinus-5-6-kk.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.