White paperPDF2026

Considerations for Shipping and Storage of 1-Phase Cold Plate Liquid Cooled Racks and Servers (OCP white paper, v2.0)

Open Compute Project Foundation · Cheng Chen (Meta), Sean Sivapalan (NVIDIA)

Compares shipping cold-plate servers and racks wet, partially wet, semi-dry or dry in terms of expansion and corrosion risk and operational burden. It is used to plan shipment, storage and on-site commissioning logistics.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The paper addresses the question of what state liquid-cooled AI racks and servers should arrive in at the final site: filled with coolant, partially filled, semi-dry or dry. The four methods are defined by fill ratio: wet about 100%, partial wet 90-95%, semi-dry under 50% and dry under 10%. A single table compares each method on expansion-damage risk, corrosion risk and the preparation, shipping and storage steps it requires.

The technical-risk section gives shipment temperature ranges from IEC 60721-3-2: road and rail -20 to 45 degC, sea -10 to 50 degC, air -10 to 40 degC, and 5-25 degC for controlled transport. The focus is inhibited propylene glycol at 25 vol.% (PG25) and treated water. PG25 expands about 2-5% on freezing; a slush zone sits at roughly -10 to -15 degC between freeze and burst points, and localised freezing with blockage is judged a larger risk than ordinary liquid-state expansion.

On corrosion, three mechanisms are covered: thermo-oxidative breakdown of PG25 forming acidic by-products, oxygen exposure of internal metal surfaces in dry shipments, and depletion of corrosion inhibitors because copper cold plates present a high surface-to-fluid ratio. The remedies described are temperature control, a jumper hose that acts as an expansion reservoir, nitrogen protection and effective draining.

The last section is about scale. The choice is not just wet versus dry; hardware robustness, transport resources, operations-team capacity, delivery speed and logistics workflow are weighed together. Examples include shipping dry from the factory and installing filling rigs at sites with enough resources (hybrid), wet shipping everywhere with reefers, or deciding on temperature control route by route. The paper is licensed CC BY-SA 4.0.

Key points

  1. Fill ratios: wet about 100%, partial wet 90-95%, semi-dry under 50%, dry under 10%.
  2. Wet shipping carries medium expansion risk and low corrosion risk; semi-dry shipping carries high corrosion risk and low expansion risk.
  3. Standard transport temperatures: air -10 to 40 degC, road and rail -20 to 45 degC, sea -10 to 50 degC; controlled transport 5-25 degC.
  4. PG25 slush zone is around -10 to -15 degC; volume rises about 2-5% on freezing.
  5. Recommended non-operating range for wet and partial-wet material is 5-60 degC, with 20-25 degC for long-term storage; with suitable packaging, internal temperature lags the environment so excursions outside the range of up to 4-8 hours can be tolerated.
  6. Worked example: a 20 L rack with a 4 L empty jumper hose; a 10% expansion compresses the air from 4 L to 2 L and raises pressure from 1 atm to 29.4 psi (against an example system limit of 75 psi).
  7. Nitrogen charge is 25-50 psi; component or tray-level protection gives 3-12 months of shelf life, and rack-level assemblies are shorter.
  8. Wet storage can reach acceptable inhibitor limits in 9-12 months depending on copper surface-to-volume ratio; dry storage nitrogen pressure can fall below limits in 3-12 months.
  9. Draining with clean dry air below 75 psi for a few minutes typically brings residual fluid below 5%; the air pressure must be released before transport.

Using it in design

  • At project start, define the shipping and storage state (wet, dry, hybrid) for each hardware type (rack, tray, subcomponent), using the paper's example of flexible trays absorbing expansion while rigid-piped trays cannot as a decision criterion.
  • Plan on-site filling and nitrogen-release space and equipment: if every destination receives dry shipments, each site needs filling rigs and nitrogen charging equipment.
  • For wet shipping, obtain temperature data for the route and season; verify actual transit temperatures with an instrumented dummy rack and specify temperature-controlled transport where needed.
  • Link storage to the commissioning schedule: 20-25 degC for storage over one month, nitrogen pressure monitoring and renewal for dry storage, and converting partial-wet or semi-dry units to wet or dry state before long storage.
  • Add fluid quality and inhibitor level checks before first fill to the acceptance procedure, and determine shelf life experimentally for each product.

Who should read it

Operators commissioning liquid-cooled AI halls, MEP consultants, supply-chain and logistics planners, and server and rack manufacturers.

Document contents

  1. Introduction
  2. Compliance with Open Compute Project Tenets (openness, efficiency, impact, scale, sustainability)
  3. Overview of Shipment and Storage Methods (wet, partial wet, dry, semi-dry, storage)
  4. Technical Risks (expansion damage, fluid expansion, thermoxidative breakdown, corrosion, inhibitor depletion)
  5. Operational Solutions (temperature control, jumper hose, nitrogen protection, effective draining)
  6. At Scale Considerations
  7. Conclusion
  8. Glossary and references

Related standards

  • OCP Base Specification for Single Phase Water-Based Cold Plate Coolants
  • OCP PG25 guidelines

Read the document

ocp-cold-plate-shipping-storage-2026.pdf

PDF · 0.8 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Cheng Chen (Meta); Sean Sivapalan (NVIDIA)
Publisher
Open Compute Project Foundation
Year
2026
Document number
Version 2.0
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Cheng Chen (Meta); Sean Sivapalan (NVIDIA) (2026). Considerations for Shipping and Storage of 1-Phase Cold Plate Liquid Cooled Racks and Servers (OCP white paper, v2.0). Open Compute Project Foundation. Version 2.0. https://www.opencompute.org/documents/considerations-for-shipping-and-storage-of-1-phase-coldplate-liquid-cooled-racks-and-servers-final-march-2026-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.