Artificial Intelligence-Based Temperature Twinning and Pre-Control for Data Center Airflow Organization
Energies (MDPI AG) · Na Huang, Xiang Li et al.
A data-driven thermal twin for a 200-cabinet hall built from contained micro-modules: an LSTM forecasts supply, return, cold-aisle and hot-aisle temperatures, and a Deep Q-Network adjusts air-conditioning output so predicted hotspots do not occur.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how AI-based temperature forecasting and air-conditioning control can prevent hotspots before they form and improve energy efficiency. The test room is 5.4 m high with a 1.0 m raised floor, five contained micro-modules of 40 cabinets (200 total, 2.2 m high, 5 kW each) and 70% open floor tiles. Fourteen 100 kW units (5 duty + 2 standby per side) of 25,000 m³/h each sit in side AC rooms. The room has 728 sensor points sampled every 15 min, with temperature accuracy ±0.5 °C over -10 to +50 °C.
The LSTM forecasts supply, return, cold-aisle and hot-aisle temperatures from the temperature and equipment power of the past 15 time steps. A DQN controller then adjusts air-conditioning output so that predicted hotspots do not occur. Setpoints were supply air 26 ± 1 °C, return air 39 ± 1 °C and cold aisle 27 ± 1 °C, with a target prediction error of no more than ±0.4 °C.
Results: LSTM mean absolute errors were 0.32 °C for supply air, 0.21 °C for return air, 0.36 °C for the cold aisle and 0.19 °C for the hot aisle, with cabinet power predicted within ±2 kW. The DQN controller cut PUE by an average of 2.6% and WUE by 2.5% over a year.
Limits: the object is limited because the building structure could not be modified, the cooling and air-supply type is simple, and only particular AI verification was done. As a learned, sensor-based model rather than a CFD surrogate, it shows what instrumentation operational twins need.
Key points
- Test room: 5.4 m height, 1.0 m raised floor, five contained micro-modules of 40 cabinets (200 total, 5 kW each, 2.2 m high), 70% open floor tiles; fourteen 100 kW units (5 duty + 2 standby per side) of 25,000 m³/h each in side AC rooms.
- The room has 728 sensor points sampled every 15 min, with temperature accuracy ±0.5 °C over -10 to +50 °C.
- Setpoints: supply air 26 ± 1 °C, return air 39 ± 1 °C and cold aisle 27 ± 1 °C, with a target prediction error of no more than ±0.4 °C.
- LSTM mean absolute errors: 0.32 °C supply air, 0.21 °C return air, 0.36 °C cold aisle and 0.19 °C hot aisle; cabinet power predicted within ±2 kW.
- The DQN controller cut PUE by an average of 2.6% and WUE by 2.5% over a year.
Using it in design
- For an operational thermal twin, define adequate sensor density covering supply, return, cold-aisle and hot-aisle temperatures and equipment power (728 points at 15-minute sampling in this study).
- Set the prediction error target (±0.4 °C) and setpoints (supply 26 °C, return 39 °C, cold aisle 27 °C) as twin validation criteria.
- Design air-conditioning control as pre-control that acts before hotspots form, and weigh the PUE/WUE gain (about 2.5%) against sensor and control investment.
Who should read it
Engineers and researchers developing data-centre cooling control and operational twins.
Document contents
- 1. Introduction
- 2. Materials and Methods
- 3. Digital Twin (Simulation) Module (3.1 Application of Digital Twin Technology in Data Center Cooling Systems, 3.2 Time Series Based Temperature Prediction Model)
- 4. Optimal Control Module: Hotspot and Fault Pre-Control and Group Control (4.1 Hot Spots and Fault Pre-Control, 4.2 Optimised Control Module for Group Control)
- 5. Experiments (5.1 Data Center Simulation Platform, 5.2 Experimental Data, 5.3 Experimental Setup, 5.4 Experiments and Analysis of Data Center Task Prediction)
- 6. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
- ISO/IEC 30134-2 (PUE)
- ISO/IEC 30134-9 (WUE)
Read the document
ai-temperature-twinning-airflow-2023.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Na Huang; Xiang Li; Quanming Xu; Ronghao Chen; Huidong Chen; Aidong Chen
- Publisher
- Energies (MDPI AG)
- Year
- 2023
- Volume
- 16
- Issue
- 16
- Pages
- 6063
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Na Huang; Xiang Li; Quanming Xu; Ronghao Chen; Huidong Chen; Aidong Chen (2023). Artificial Intelligence-Based Temperature Twinning and Pre-Control for Data Center Airflow Organization. Energies (MDPI AG). 16(16), 6063. https://doi.org/10.3390/en16166063
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.