Wide-Area Power System Oscillations from Large-Scale AI Workloads
arXiv preprint (University of Texas at Austin; formatted for IEEE Transactions on Power Systems) · Min-Seung Ko, Hao Zhu
A stochastic power-profile model for AI-centric datacenters represents training and fine-tuning jobs as periodic compute/communicate cycles with random cycle length and phase power; aggregated profiles are injected into WECC 179-bus and NPCC 140-bus dynamic models to study forced and wide-area oscillations.
CC BY 4.0: share with attribution
On this page
Overview
The work develops a new dynamic power-profiling approach for AI-centric datacenter loads and analyses their impact on grid operations, particularly their potential to induce wide-area oscillations. It characterises the periodic stochastic power fluctuations inherent to large-scale AI workloads during training and fine-tuning, driven by GPU architecture. These sustained, large power fluctuations, unlike conventional load ramping, act as persistent forcing inputs capable of interacting with and amplifying local and inter-area oscillation modes.
Training model parameters: baseline fluctuation frequency U(0.5, 1.5) Hz, cycle-duration sigma 0.1, compute-phase share 55%-80% of each cycle, and an average 30% demand reduction in synchronisation phases (mu_Delta = 0.3). The fine-tuning model uses a dominant frequency U(0.3, 0.7) Hz and compute fraction 0.7-0.9. Baseline WECC case: 60.8 GW base load, system inertia 2.7, 7 datacenters of 1 GW each (11.5% penetration), fluctuation band 0.5-1.5 Hz, with 80% of each site's capacity modelled as steady load and 20% as fluctuating AI load.
Eigen-analysis of the WECC system found unstable modes at 0.852, 1.06 and 1.44 Hz; higher-penetration scenarios of 23% and 34.5% were also simulated. Across 20 stochastic runs the response consistently shows a dominant oscillation around 1 Hz, and narrower workload frequency ranges give stronger, more repeatable oscillations. Direct suppression of datacenter load fluctuation is substantially more effective than indirect system-level measures such as added damping.
The finding is that AI datacenters behave as persistent, frequency-selective forcing sources rather than ramping loads, and oscillation severity depends on fluctuation frequency band, single-site size, siting, system inertia and penetration. Limits: the stochastic model parameters are assumptions, not from a measured single-facility profile; the simulation is on two test systems. It is a preprint.
Key points
- Non-computational datacenter components (cooling, networking, storage) are cited as typically 40-50% of total consumption, and AI workloads as roughly 10-20% of datacenter electricity today.
- Training model parameters: baseline fluctuation frequency U(0.5, 1.5) Hz, cycle-duration sigma 0.1, compute-phase share 55%-80% of each cycle, and an average 30% demand reduction in synchronisation phases (mu_Delta = 0.3).
- The fine-tuning model uses a dominant frequency U(0.3, 0.7) Hz and compute fraction 0.7-0.9.
- Baseline WECC case: 60.8 GW base load, system inertia 2.7, 7 datacenters of 1 GW each (11.5% penetration), fluctuation band 0.5-1.5 Hz; 80% of each site as steady load and 20% as fluctuating AI load.
- Eigen-analysis of the WECC system found unstable modes at 0.852, 1.06 and 1.44 Hz; higher-penetration scenarios of 23% and 34.5% were also simulated.
- Across 20 stochastic runs the response consistently shows a dominant oscillation around 1 Hz; narrower workload frequency ranges give stronger, more repeatable oscillations.
- Direct suppression of datacenter load fluctuation is substantially more effective than indirect system-level measures such as added damping.
Using it in design
- Model AI data-centre load as a persistent periodic forcing (0.3-1.5 Hz band, about 20% of peak fluctuating) rather than a ramp, and add oscillation analysis to the grid-interconnection study.
- Suppress fluctuation on site (UPS, battery, workload smoothing); direct suppression is far more effective than system-level damping.
- Treat single-site size, siting and penetration (11.5% to 34.5%) as limiting factors at the point of connection.
Who should read it
Grid planners and data-centre designers assessing the grid-stability impact and interconnection conditions of large AI data centres.
Document contents
- Introduction
- AI Workload Power Profile Modeling (A. Training Workload Modeling, B. Fine-tuning Workload Modeling, C. Aggregated AI Workloads for Datacenter Power Profiling)
- Simulation Results (A. Simulation Settings, WECC 179-bus and NPCC 140-bus systems, eigen-analysis, penetration and siting sensitivity)
- Oscillation Implications of AI Datacenter Deployment
- Conclusion
Read the document
ai-workload-wide-area-oscillations-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Min-Seung Ko; Hao Zhu
- Publisher
- arXiv preprint (University of Texas at Austin; formatted for IEEE Transactions on Power Systems)
- Year
- 2025
- Document number
- arXiv:2508.16457
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- arxiv.org
Original licence note
arXiv record licence is http://creativecommons.org/licenses/by/4.0/ (checked via arXiv OAI-PMH, v2)
Citation
Min-Seung Ko; Hao Zhu (2025). Wide-Area Power System Oscillations from Large-Scale AI Workloads. arXiv preprint (University of Texas at Austin; formatted for IEEE Transactions on Power Systems). arXiv:2508.16457. https://doi.org/10.48550/arXiv.2508.16457
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.