Analysis of Air-Side Economizers in Terms of Cooling-Energy Performance in a Data Center Considering Exhaust Air Recirculation
Energies (MDPI AG) · Seonghyun Park, Janghoo Seo
A dynamic energy simulation of a Korean data centre compares a central chilled-water system with direct airside economisers (mixing chamber) and indirect airside economisers (70% effective heat exchanger); 13 cases vary supply-air temperature and the share of exhaust air recirculated back into the outdoor-air intake.
CC BY 4.0: share with attribution
On this page
Overview
In data centres with high-temperature IT equipment, enormous cooling systems operate year-round; studies have aimed to improve the cooling efficiency of server-room units, but cooling-energy analysis considering exhaust air (EA) recirculation had not been researched sufficiently. This study analysed the cooling-energy saving effect considering EA recirculation and supply-air (SA) temperature conditions when direct and indirect air-side economisers were applied to a data centre in Korea; the existing system consumes 69,121 MWh/yr.
At 13.5 °C supply air with no recirculation, the direct airside economiser had 4536 h/yr of outdoor-air availability and 43.8% energy savings versus the existing system. Raising supply air to 18 °C and 22 °C raised direct-economiser outdoor-air hours to 5665 h and 6838 h, with energy savings of 54.9% and 67.2%. The indirect airside economiser (70% HX effectiveness) had 6988 h at 13.5 °C, 8206 h at 18 °C and 8707 h at 22 °C, with savings of 32.3%, 44.1% and 55.3%.
At 15% exhaust-air recirculation, annual cooling energy rose about 6.1% for the direct economiser and about 9% for the indirect economiser, and indirect-economiser savings fell from 32.3% to 26.3%. With a mixing-ratio approach on fixed outdoor-air intervals, supply-air temperature fell outside the ASHRAE recommended range, so the OA fraction must be controlled to the target supply condition. The authors recommend placing exhaust-air grilles so recirculation is below 5%, or handling it in the envelope plan at design stage.
Limits: a single Korean data centre and a dynamic simulation, so results depend on that climate and facility. Recirculation of hot exhaust cuts the hours when outdoor air can be used and erodes savings, while raising supply-air temperature greatly increases economiser hours.
Key points
- At 13.5 °C supply air with no recirculation, the direct airside economiser had 4536 h/yr of outdoor-air availability and 43.8% energy savings versus the existing system (69,121 MWh/yr).
- Raising supply air to 18 °C and 22 °C raised direct-economiser outdoor-air hours to 5665 h and 6838 h, with energy savings of 54.9% and 67.2%.
- The indirect airside economiser (70% HX effectiveness) had 6988 h at 13.5 °C, 8206 h at 18 °C and 8707 h at 22 °C, with savings of 32.3%, 44.1% and 55.3%.
- At 15% exhaust-air recirculation, annual cooling energy rose about 6.1% for the direct economiser and about 9% for the indirect economiser; indirect-economiser savings fell from 32.3% to 26.3%.
- The authors recommend placing exhaust-air grilles so recirculation is below 5%, or handling it in the envelope plan at design stage.
- With a mixing-ratio approach on fixed outdoor-air intervals, supply-air temperature fell outside the ASHRAE recommended range; the OA fraction must be controlled to the target supply condition.
Using it in design
- In airside economiser design, plan exhaust grilles and the building envelope so recirculation stays below 5%; 15% recirculation raised energy about 6.1% for direct and 9% for indirect.
- Consider raising supply-air temperature (13.5 to 22 °C) as the main lever for economiser hours and savings (43.8% to 67.2% for direct).
- Control the outdoor-air fraction to the target supply condition rather than splitting it into fixed intervals; otherwise supply temperature can leave the ASHRAE recommended range.
Who should read it
Cooling engineers designing airside economisers and assessing the energy effect of exhaust recirculation.
Document contents
- 1. Introduction
- 2. Cooling Load and Energy Consumption of a Conventional Data Center (2.1 Overview, 2.2 Boundary, 2.3 Devices: cooling tower, cooling coil, fan and pump components; 2.4 Cooling Load and Energy Consumption)
- 3. Monthly Analysis and Case Study (3.1 Case Study, 3.2 Direct Air-Side Economizer, 3.3 Indirect Air-Side Economizer, 3.4 Cooling Energy Consumed by Air-Side Economizers)
- 5. Results (annual analysis)
- 4. Conclusions
Related standards
- ASHRAE TC9.9 Thermal Guidelines
Read the document
airside-economizer-exhaust-recirculation-2018.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Seonghyun Park; Janghoo Seo
- Publisher
- Energies (MDPI AG)
- Year
- 2018
- Volume
- 11
- Issue
- 2
- Pages
- 444
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.
Citation
Seonghyun Park; Janghoo Seo (2018). Analysis of Air-Side Economizers in Terms of Cooling-Energy Performance in a Data Center Considering Exhaust Air Recirculation. Energies (MDPI AG). 11(2), 444. https://doi.org/10.3390/en11020444
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.