White paperFree to read2025

Power Topology and Analysis of 800 VDC Architectures to Support Next Generation AI Factory Infrastructure

Alpha and Omega Semiconductor

An Alpha and Omega Semiconductor white paper (Version 1.0, 10/06/2025) comparing three LLC DCX converter topologies that step from 800 VDC rack distribution down to a 48-54 V bus, in terms of power semiconductor voltage and current stress.

On this page

Overview

The document says AI workloads are driving data centre power demand up fast and that traditional 54 V in-rack distribution cannot support megawatt-scale racks. 800 VDC distribution is promoted for three reasons: scalability to racks from 100 kW to over 1 MW, up to 5% better end-to-end efficiency than current 54 V systems, and less copper because less conduction current flows at 800 V input. The power rack converts three-phase AC to 800 V DC, an isolated DC/DC steps down to 54/12 V, and the IT rack delivers 12 V to the GPU.

The white paper examines only the power stage that converts 800 VDC to a 54 V or 12 V intermediate bus and proposes three topologies: three-phase half-bridge LLC DCX, three-level series half-bridge (TLSHB) LLC DCX and diode-neutral-point-clamped three-level (TLDNPC) three-phase LLC DCX. The three-phase LLC spreads power over three resonant tanks; the 120 degree phase difference between the three rectifier outputs makes the output ripple frequency six times the switching frequency and reduces output filter capacitance. A Y connection cuts the transformer winding voltage to two thirds of the input voltage and is found more suitable for 800 V input.

In topology I the primary MOSFET voltage equals 800 V, and 1200 V devices are recommended for a 10% margin plus turn-off spikes. Because 1200 V silicon MOSFETs have too much switching loss and 1200 V GaN is not widely available, SiC is chosen as the best candidate. In topologies II and III the primary device voltage falls to half the input (400 V), so 650 V GaN devices are used. The comparison table, for a 12 kW 800 V to 48 V DCX, gives primary device current stress of pi/24 x Iin (7.8 A), pi/8 x Iin (23.4 A) and pi/24 x Iin (7.8 A); primary device counts of 6, 4 and 12; secondary device current stress of pi/12 x Io (63 A) and 12 secondary devices.

The document is a component-level vendor comparison. Hardware testing, frequency, thermal and electromagnetic interference (EMI) studies, magnetics design and the final topology choice are left to later work. It therefore gives no definitive ranking on efficiency, density or cost; for a data centre designer its value is in showing the semiconductor voltage and current levels in the power stage of an 800 VDC architecture.

Key points

  1. 800 VDC architecture targets rack power from 100 kW to over 1 MW; 54 V in-rack distribution is stated as insufficient for megawatt-scale racks.
  2. The vendor anticipates up to 5% higher end-to-end efficiency than current 54 V systems and less copper because of lower conduction current at 800 V input.
  3. Three topologies: three-phase half-bridge LLC DCX, three-level series half-bridge (TLSHB) LLC DCX and TLDNPC three-phase LLC DCX.
  4. In the three-phase LLC the output ripple frequency is six times the switching frequency; a Y connection reduces winding voltage to two thirds of the input voltage.
  5. Topology I primary device voltage is 800 V; a 1200 V SiC MOSFET (40 mOhm target, 20 mOhm GTPAK example) is recommended; 1200 V silicon switches too lossily and 1200 V GaN is not widely available.
  6. Topologies II and III have 400 V primary stress; 650 V GaN devices are recommended (examples: 35 mOhm GTPAK and 140 mOhm DFN5x6).
  7. 12 kW 800 V to 48 V DCX comparison: primary current stress 7.8 A / 23.4 A / 7.8 A, primary device count 6 / 4 / 12; secondary current stress 63 A, 12 secondary devices.
  8. The secondary side is a full bridge in all three topologies and the same SR devices (80 V silicon or 100 V GaN, e.g. 1.6+1.8 mOhm dual die or 1.4 mOhm) are recommended.
  9. The conclusion of Version 1.0 (10/06/2025) names frequency, thermal and EMI studies as further work.

Using it in design

  • When assessing 800 VDC rack distribution, draw the conversion chain between power rack and IT rack (AC/DC 800 V, isolated DC/DC 54/12 V, GPU DC/DC) and verify the efficiency-gain claim stage by stage.
  • Compare rack power from 100 kW to 1 MW against busbar and cable cross-sections using the lower conduction current at high voltage, and include the copper saving in the design with your own calculation.
  • Confirm vendor-based hardware choices (SiC/GaN) against supplier datasheets and test results; the document contains no hardware testing.
  • Take insulation, short-circuit protection and safety requirements for 800 V DC from the relevant standards and equipment makers, not from this document, which addresses only the semiconductor level.
  • In topology selection, weigh primary device count and current stress (6, 4 or 12 devices) against power-board area and the need for paralleling.

Who should read it

Power electronics and electrical system engineers studying high-voltage DC distribution in AI data centres.

Document contents

  1. Introduction
  2. I. Three phase half bridge LLC DCX resonant converter
  3. II. Three-level series half bridge (TLSHB) DCX LLC
  4. III. TLDNPC three phase LLC DCX resonant converter
  5. IV. Comparison of different topologies
  6. Summary
  7. Future work

Publication details

Authors
Alpha and Omega Semiconductor
Publisher
Alpha and Omega Semiconductor
Year
2025
Document number
Version 1.0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Publisher source opened. No document-specific commercial redistribution permission established; link and original metadata only.

Citation

Alpha and Omega Semiconductor (2025). Power Topology and Analysis of 800 VDC Architectures to Support Next Generation AI Factory Infrastructure. Alpha and Omega Semiconductor. Version 1.0. https://www.aosmd.com/sites/default/files/res/application_notes/800-VDC-solution-white-paper.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.