Chilled Water Distribution Types: Centralized Vs Distributed
Armstrong Fluid Technology
Armstrong Fluid Technology's white paper of 14 August 2024 (100.255) compares centralized primary-only, centralized primary/secondary and distributed secondary pumping in a worked example with four load points and annual operating shares.
On this page
Overview
The document is an Armstrong Fluid Technology white paper on choosing the pumping and distribution layout of chilled water systems (document 100.255, 14 August 2024). Three layouts are described with schematic diagrams: centralized primary-only pumping, centralized primary/secondary pumping and distributed secondary pumping.
The white paper evaluates the layouts through a worked comparison. The comparison states four load points and their annual operating shares, so the assumed load distribution and pumping heads are visible. That transparency allows the result to be checked for model consistency.
The effect of the distribution layout on pump energy is weighed in chiller plant design together with plant scale; the document provides a reference comparison for that choice.
Key points
- Three distribution layouts are defined with schematic diagrams: centralized primary-only, centralized primary/secondary, distributed secondary pumping.
- The comparison specifies four load points and their annual operating shares explicitly.
- Assumed load distribution and pumping heads are visible in the worked example, so the result suits consistency checking.
- Document number 100.255, dated 14 August 2024; publisher Armstrong Fluid Technology.
Using it in design
- For a chilled water plant, compare centralized primary-only, primary/secondary and distributed secondary pumping on the same load profile and pump heads.
- In pump energy calculation, document the annual load distribution (load points and operating shares) as an explicit assumption.
- Use the white paper's worked comparison as a reference to check the consistency of your own energy model.
- Weigh the choice together with plant scale, redundancy and maintenance needs.
Who should read it
Mechanical designers and consultants selecting the pumping and distribution layout of chilled water plants.
Publication details
- Authors
- Armstrong Fluid Technology
- Publisher
- Armstrong Fluid Technology
- Year
- 2024
- Document number
- 100.255; 14 August 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.
Citation
Armstrong Fluid Technology (2024). Chilled Water Distribution Types: Centralized Vs Distributed. Armstrong Fluid Technology. 100.255; 14 August 2024. https://armstrongfluidtechnology.com/~/media/documents/sales-and-marketing/white-papers/100-255_chilled_water_distribution_types_centralized_vs_distributed_whitepaper.pdf?la=en