Technical guideFree to read2023

How piping configuration affects pump energy

Original title Saving Energy by Piping Configuration

Armstrong Fluid Technology

Armstrong Fluid Technology's 2023 paper compares duty/standby pump pipework with a shared-pipe arrangement, holding pumps and duty point constant and converting added fittings to equivalent pipe length.

On this page

Overview

Armstrong's paper of 22 August 2023 (100.251) compares duty/standby pump pipework with a shared-pipe arrangement in terms of energy. To isolate the pipework effect, the comparison uses the same pumps and the same design flow and head.

In the worked example, two tees and two long-radius elbows are converted to equivalent pipe length and the added friction and power effect are evaluated. The result shows that the hydraulic resistance of fittings has to be counted.

Key points

  1. Paper number 100.251, dated 22 August 2023.
  2. Duty/standby pump pipework is compared with a shared-pipe arrangement.
  3. The same pumps and the same design flow and head are used.
  4. Two tees and two long-radius elbows are converted to equivalent pipe length (Table 1).

Using it in design

  • Include standby-leg fittings and operating combinations in hydraulic calculations.
  • Add tee and elbow losses to pump head using the equivalent pipe length method.
  • Verify the expected saving against actual system resistance and control strategy.

Who should read it

Mechanical engineers designing chilled-water pump station pipework.

Publication details

Authors
Armstrong Fluid Technology
Publisher
Armstrong Fluid Technology
Year
2023
Document number
100.251; 22 August 2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

Armstrong Fluid Technology (2023). Saving Energy by Piping Configuration. Armstrong Fluid Technology. 100.251; 22 August 2023. https://armstrongfluidtechnology.com/~/media/documents/sales-and-marketing/white-papers/100-251_energysavingpiping_whitepaper.pdf?la=en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.