DOE operators' panel, ARPA-E COOLERCHIPS (2023)
Original title DOE Operator’s Panel: ARPA-E COOLERCHIPS
U.S. Department of Energy, ARPA-E · Arman Shehabi, Michael Kercher et al.
The ARPA-E COOLERCHIPS operators' panel presents cooling design and operating lessons from LBNL NERSC (PUE 1.05), NREL ESIF (PUE 1.04 or below), NCAR NWSC (PUE 1.08) and ORNL.
On this page
Overview
These are slides from the operators' panel held in October 2023 under the US Department of Energy's ARPA-E COOLERCHIPS programme. Four national laboratory facilities briefly describe their cooling design and operating experience: Lawrence Berkeley National Laboratory's NERSC Shyh Wang Hall, NREL's Energy Systems Integration Facility (ESIF), NCAR's Wyoming Supercomputing Center (NWSC) and the Oak Ridge Leadership Computing Facility.
The NERSC building has four floors, 150,000 GSF and 21.5 MW service capacity. It uses compressor-free air and water cooling year-round and reports a trailing twelve-month PUE of 1.05. At NREL ESIF, direct component-level liquid cooling runs on 24 °C (75 °F) supply water with 35-40 °C return; waste heat heats offices and laboratories, there is no mechanical cooling and PUE is 1.04 or below.
NCAR NWSC is a Tier II facility built in 2011 in Cheyenne at 6,800 ft elevation. It uses heat-exchanger free cooling with chiller backup and a Class W2 chilled water loop at an 18 °C setpoint. Current load is 4.2-4.5 MW and PUE is 1.08. The ORNL slide shows chilled, medium-temperature and high-temperature water loops at 40 MW scale with kW/ton values.
The deck is in slide form and gives no method or calculation detail. Each operator closes with short project advice: serviceability, spare part supply, simple fluids and series-parallel arrangements, and avoiding a razor's-edge control envelope.
Key points
- NERSC: 150,000 GSF, 21.5 MW service capacity, year-round compressor-free cooling, PUE 1.05.
- NERSC cooling towers can supply 24 °C (75 °F) or colder water all hours of the year.
- NREL ESIF: 24 °C supply and 35-40 °C return water; no mechanical cooling, PUE 1.04 or below.
- NREL distributes 480 VAC directly to 60-80 kW racks and finds pumps more efficient than fans.
- NCAR NWSC: Tier II, 2011, 6,800 ft, Class W2 chilled water at 18 °C, 4.2-4.5 MW load, PUE 1.08.
- NWSC advice: ease of servicing, spare part availability and software interfaces suited to entry-level users.
- ORNL slide shows chilled water at 0.8 kW/ton, medium-temperature water at 0.4 kW/ton and high-temperature water at 0.2 kW/ton.
- ORNL advice: small decisions add up at facility level, minimise flow, keep fluids simple and watch series versus parallel layouts.
Using it in design
- For a liquid-cooled design with supply water near 24 °C, test whether mechanical cooling can be removed entirely using tower wet-bulb data.
- In mixed facilities, define chilled, medium- and high-temperature water loops with separate kW/ton targets.
- Where return water is 35-40 °C, add office and laboratory heating to the heat recovery study.
- Choose simple user interfaces, accessible maintenance points and parts that can be sourced reliably for operations teams.
- Do not design the control envelope at the limit; keep margin without carrying excess flow.
Who should read it
Mechanical engineers and operations managers designing high-density or HPC data-centre cooling.
Document contents
- NERSC Shyh Wang Hall
- Center of Expertise resources
- NREL HPC Data Center and ESIF
- NCAR Wyoming Supercomputing Center
- ORNL Leadership Computing Facility
Publication details
- Authors
- Arman Shehabi; Michael Kercher; David Grant
- Publisher
- U.S. Department of Energy, ARPA-E
- Year
- 2023
- Document language
- Unverified
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Arman Shehabi; Michael Kercher; David Grant (2023). DOE Operator’s Panel: ARPA-E COOLERCHIPS. U.S. Department of Energy, ARPA-E. https://arpa-e.energy.gov/sites/default/files/2025-06/Day2_06_DOE_Operators.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.