Research paperFree to read2026

Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation

arXiv · Salish Maharjan, Junyuan Zheng et al.

A preprint that uses impedance scans at the point of common coupling to ask whether UPS-fed data-centre loads can take part in sub-synchronous control interaction (SSCI), as wind plants and HVDC converters do.

On this page

Overview

Most data-centre demand reaches the grid through power converters inside the UPS. In a double-conversion UPS every watt passes through a rectifier, a DC bus and an inverter before the IT equipment. Whether this constant-power chain shows negative resistance toward the grid, and whether that can lead to sub-synchronous control interaction, has been little studied. The paper addresses the question with impedance-based frequency scans at the point of common coupling (PCC).

The method has two stages. First, a detailed proprietary model (INS-ISU) is used to scan the motor, variable-frequency-drive (VFD), lighting and UPS-fed IT branches of a representative facility separately. The same scans are then repeated on three public models from PNNL, TAMU and NLR. Across models, the size and frequency range of the negative resistance differ with converter controls, but the pattern is the same.

The result is that only the UPS in double-conversion mode shows negative resistance. The other branches and the UPS in bypass mode stay passive. Lowering the load from rated to light load deepens the negative resistance, so a lightly loaded facility in double-conversion mode is the worst case. Raising the DC-link capacitance confines the negative resistance to a narrow band around the fundamental.

The work is a preprint and stresses that a scan result alone does not mean instability: whether negative load resistance creates a problematic interaction is judged only by assessing load and network together. Time-domain (EMT) confirmation, series-compensated and weak grids, and field validation are left to future work.

Key points

  1. In the INS-ISU model the motor, VFD and lighting branches stay passive from 5 to 1000 Hz.
  2. The UPS-fed IT branch in double-conversion mode shows negative resistance across the whole sub-synchronous band, continuing up to about 170 Hz; in bypass mode the branch is passive.
  3. None of the three public models (PNNL, TAMU, NLR) shows negative resistance in bypass mode; three of the four models do in double-conversion mode.
  4. In bypass mode, positive resistance grows inversely with load: about 1.5 to 3 mΩ at 100 MW and about 15 to 30 mΩ at 10 MW (below the fundamental).
  5. In the TAMU model the negative band between about 100 and 190 Hz deepens from about -5 mΩ at 100 MW to about -25 mΩ at 10 MW.
  6. In the NLR model the low-frequency negative band reaches about 17 Hz at 100 MW, 22 Hz at 50 MW and 33 Hz at 10 MW, where it reaches about -150 mΩ.
  7. Raising the DC-link capacitance from 20 mF to 50 mF confines the INS-ISU negative resistance to a narrow band around the fundamental, which points to the DC-voltage control response as the key factor.
  8. Recommended practice: screen the UPS branch in double-conversion mode at partial load and, where negative resistance appears, run a combined scan with the network at the PCC.

Using it in design

  • As an input to interconnection studies, request the UPS branch frequency scan at partial load as well as rated load; the worst case is light load in double-conversion mode.
  • Where negative resistance appears, commission a combined scan with the network impedance at the PCC, and flag series-compensated or weak grids specifically.
  • Obtain the DC-voltage control bandwidth and DC-link capacitance from the UPS manufacturer and treat capacitance as a design parameter for the negative-resistance band.
  • Record double-conversion and bypass (eco) operating modes as separate impedance profiles; mode changes present different dynamics to the grid.
  • Add a field comparison of the predicted sub-synchronous behaviour to the commissioning programme.

Who should read it

System engineers performing data-centre interconnection studies, electrical designers specifying UPS converter controls, and operators.

Document contents

  1. Introduction
  2. Method and frequency-scan setup
  3. Cross-Validation with Open-Source Data Center Models
  4. Sensitivity and Mitigation Studies on the INS-ISU Model
  5. Results Summary and Discussion
  6. Conclusion
  7. Appendix: Further Exploration on Open-source Models

Publication details

Authors
Salish Maharjan; Junyuan Zheng; Lung-An Lee; Min Lwin; Zhaoyu Wang
Publisher
arXiv
Year
2026
Document number
arXiv:2611.17550v1
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

arXiv page license link is a non-exclusive grant to arXiv only. PDF p. 1 says submitted to IEEE for possible publication; no accepted-journal status or general redistribution permission asserted.

Citation

Salish Maharjan; Junyuan Zheng; Lung-An Lee; Min Lwin; Zhaoyu Wang (2026). Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation. arXiv. arXiv:2611.17550v1. https://doi.org/10.48550/arXiv.2611.17550

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.