Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

arXiv · Haoyu Wang, Chi Zhang et al.

A preprint (arXiv, v2, 9 September 2026) proposing fault-current limiting and controlled recovery inside an LLC converter, with reported prototype experiments. It addresses the current management a solid-state transformer (SST) needs in DC-distribution data centres to keep running through a load-branch short circuit while a fuse or breaker isolates the faulted branch.

On this page

Overview

The paper notes that SSTs are proposed as the interface between distribution grids and data centres for flexible power flow and fast dynamic response, but that when a short circuit occurs in a load branch, an SST with a voltage-source-type DC-DC stage (such as an LLC resonant converter) is forced to shut down by the fault currents. A downstream (rack-level) short circuit collapses load impedance and fault current rises within tens of microseconds; an unmitigated fault can drive the resonant current far beyond rating. Because load branches are protected by fuses or breakers that clear by I2t characteristics, selective isolation requires current that is neither unlimited nor blocked but regulated at a designated level for a specified period.

Existing approaches fall into three categories: hardware in series with the feeder (DC breakers, fault current limiters; adds cost), converter-level overcurrent protection (clamps the resonant current but does not hold a specified current or address restoration), and control-level fault ride-through that keeps the SST a controllable source during the fault. The paper's proposal is in the third category: a coordinated current-limiting and recovery strategy embedded in the control of the SST's DC-DC stage, with no added hardware cost, targeting a downstream DC load short circuit rather than a fault on the DC bus. The strategy runs within the local DSP and needs no communication with downstream protection devices.

The method has four stages: normal DC-DC operation; fault detection (a fault is flagged when DC current exceeds a threshold and a rate-of-rise threshold together; detection can be done in software from current sensing, with measurement and fibre transmission taking about 10 us; once flagged, the switches are disabled until DC current falls to a system-friendly level); current limiting (the switching frequency is stepped up rapidly to a limit, for example twice the resonant frequency, and closed-loop current control through duty cycle holds the DC current at a designated value; this stage lasts milliseconds while a fuse or breaker isolates the branch); and recovery (after isolation, frequency and duty cycle are returned to nominal with rate-limited ramps, avoiding inrush).

Experiments use an LLC prototype with SiC MOSFETs at 400 V input, 400 V DC reference, 2 kW output and a 154 kHz resonant frequency; a 2 ohm resistor simulates the fault. When the fault is applied, Idc and ir reach peaks of 117 A and 44 A within 10 us; when Idc exceeds the 20 A threshold the controller disables the switches for the next switching cycle.

After the output capacitor discharges, frequency is raised to 300 kHz and closed-loop current control holds Idc at 15 A, with Vdc staying at about 30 V for a stage of several milliseconds. After the fault is isolated, ramped recovery proceeds without inrush in the resonant tank. The paper presents only a laboratory, low-power validation on one LLC converter; it has not been tested at SST scale or in a data-centre DC distribution system.

Key points

  1. The controller detects a fault when DC current exceeds a fault threshold and a rate-of-rise threshold together; measurement and fibre transmission take about 10 us.
  2. Switching frequency is stepped up rapidly to a limit (twice the resonant frequency in the example) and closed-loop current control through duty cycle holds DC current at a designated level.
  3. The current-limiting stage lasts milliseconds, during which a fuse or breaker isolates the faulted branch.
  4. Recovery uses rate-limited ramps of frequency and duty cycle; no inrush results.
  5. The strategy needs no extra hardware cost and runs in the local DSP; no communication with downstream protection devices is needed.
  6. Prototype: 400 V input, 400 V DC reference, 2 kW, 154 kHz resonant frequency, SiC MOSFETs; a 2 ohm resistor simulates the fault.
  7. When the fault is applied, Idc and ir reach 117 A and 44 A within 10 us; the fault threshold is 20 A.
  8. In the limiting stage frequency rises to 300 kHz, Idc is held at 15 A and Vdc stays at about 30 V.
  9. The paper presents only a laboratory prototype of one LLC converter; it has not been validated at SST scale or in a DC distribution system.

Using it in design

  • In DC-distribution (for example 800 VDC) data-centre design, for SST and downstream DC protection coordination, ask the supplier whether the SST limits current without shutting down on a load-branch short circuit and supplies the current a fuse or breaker needs to isolate.
  • In the protection coordination study, assess the SST's limited current level (the designated value) and duration (milliseconds) together with fuse I2t curves.
  • Write ramped recovery and no inrush into the SST specification; add recovery time and bus voltage return to the acceptance test.
  • Define type-test and commissioning-test scenarios for SST fault ride-through behaviour (at what stage it shuts down, how much current it supplies).
  • Keep in mind that the paper's results are for a laboratory-scale LLC prototype; the same behaviour must be demonstrated by the supplier for megawatt-scale SSTs.

Who should read it

Electrical engineers designing 800 VDC and SST-based data-centre distribution, protection-coordination specialists, and SST and DC-DC converter manufacturers.

Document contents

  1. Introduction (SSTs, load-side fault management approaches and contributions)
  2. DC Fault Mechanism and Analysis (LLC converter)
  3. Current Limiting and Recovery Strategy (normal operation, fault detection, DC current limiting, recovery)
  4. Experimental Verification
  5. Conclusion

Publication details

Authors
Haoyu Wang; Chi Zhang; Mafu Zhang; Rudy Wang; Peter Barbosa
Publisher
arXiv
Year
2026
Document number
arXiv:2608.26595v2
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

arXiv non-exclusive distribution license is linked on the record; no general commercial redistribution permission established.

Citation

Haoyu Wang; Chi Zhang; Mafu Zhang; Rudy Wang; Peter Barbosa (2026). Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers. arXiv. arXiv:2608.26595v2. https://doi.org/10.48550/arXiv.2608.26595

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.