Voltage Monitoring Relays / Gerilim İzleme Röleleri: TR/EN

Klemsan

A bilingual technical sheet from Klemsan for its single-phase and three-phase voltage monitoring relays, with a selection table, wiring configurations, technical values and fault diagrams.

On this page

Overview

The sheet describes a family of microprocessor-based voltage monitoring relays with TRMS measurement, designed to TS EN 60255. The devices have an 18 mm DIN-rail body, red LEDs for fault notification, an orange LED for relay status, and adjustable knobs for time and limit values. The output is a 5 A SPDT relay.

The product selection table separates eight models by connection type: V1Y-WFN 230 and V1Y-WS 300 (3P4W), V1D-WS 520 (3P3W), V1Y-WUN 120-480 (3P3W and 3P4W), V1Y-WUN.9 120-480 (3P3W, low voltage only), V1U-M2W 230 and V1U-M2W 120 (1P2W) and V1U-U.9 230 (1P2W, low voltage only). For each model it marks which of phase loss, phase sequence, low voltage and neutral break protection are included.

The fault diagrams show how each protection triggers: phase loss, neutral break, phase sequence (when the angle between the input phases is under 60° or over 180°), high voltage and low voltage. The technical table gives operating frequency 50-60 Hz, energization delay under 1 second, one changeover contact (1 C/O) and a maximum switching rating of 250 VAC / 5 A / 1250 VA or 30 VDC / 5 A / 150 W.

Other values: overvoltage category CAT III, power consumption under 13 VA, protection degree IP 20 and a screw torque of 0.5 Nm. The sheet is for device-level protection selection; it contains no site-wide monitoring architecture or selectivity analysis.

Key points

  1. Eight models: V1Y-WFN 230, V1Y-WS 300, V1D-WS 520, V1Y-WUN 120-480, V1Y-WUN.9 120-480, V1U-M2W 230, V1U-M2W 120, V1U-U.9 230.
  2. Connection types 1P2W, 3P3W and 3P4W; V1Y-WUN 120-480 works on both 3P3W and 3P4W.
  3. Protection functions: phase loss, phase sequence, low/high voltage and neutral break; varies by model.
  4. Phase sequence fault occurs when the angle between input phases is under 60° or over 180°.
  5. One changeover contact (1 C/O); maximum 250 VAC / 5 A / 1250 VA or 30 VDC / 5 A / 150 W.
  6. Operating frequency 50-60 Hz, energization delay under 1 s, TRMS measurement.
  7. CAT III, IP 20, under 13 VA consumption, 18 mm DIN-rail body.
  8. Design follows TS EN 60255.

Using it in design

  • Choose the relay for each incoming source by connection type: a neutral-break function makes no sense on a 3-wire system.
  • Do not use the low-voltage-only models (WUN.9, U.9) where high-voltage protection is required.
  • When using the 5 A contact for a contactor coil or ATS control, check the 250 VAC / 5 A limit and the effect of inductive load.
  • In ATS and transfer logic, verify relay delay settings against generator start and UPS transfer times during commissioning tests.
  • Add phase sequence protection to panels feeding rotating loads such as pumps and chillers.

Who should read it

Electrical engineers designing panels and protection, and commissioning teams.

Document contents

  1. Fault Types and LED Indications
  2. Product Selection Table
  3. Technical Specifications

Publication details

Authors
Klemsan
Publisher
Klemsan
Year
2025
Document number
Rev.No.03022025
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. Facts use the legible English table; partially missing Turkish text-layer fields were not reconstructed.

Citation

Klemsan (2025). Voltage Monitoring Relays / Gerilim İzleme Röleleri: TR/EN. Klemsan. Rev.No.03022025. https://klemsan.com.tr/wp-content/uploads/downloads/270296/Voltage%20Monitoring%20Relays%2003022025-TR-EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.