Adjustable Protection Relays (Klemsan, TR/EN, Rev. 09122024)
Original title Adjustable Protection Relays / Ayarlanabilir Koruma Röleleri: TR/EN
Klemsan
The selection table and technical data of Klemsan's 18 mm adjustable protection relay family combining phase loss, phase sequence, asymmetry, high/low voltage, neutral break and PTC protection.
On this page
Overview
The document presents microprocessor-based relays with TRMS measurement, designed to TS EN 60255, in an 18 mm DIN-rail body. The relay output is 5 A SPDT, faults are indicated by red LEDs, relay status by an orange LED, and time and limit values are set with knobs. The devices optionally include asymmetry, phase sequence, phase loss, high and low voltage, PTC and neutral break protection, and offer star and delta connection options.
The product selection table lists ten models in two groups by connection type: star (3P4W, codes starting P1Y) and delta (3P3W, codes starting P1D). Nominal voltage bands are fixed 230 V and 400 V, and for the adjustable versions 100-200 V and 170-280 V (phase-neutral) and 175-345 V and 295-480 V (phase-phase). On M1 models the lower and upper limits are set as a percentage with a single knob; on M2 models they are set with separate knobs. Fault types are explained with figures: phase loss, neutral break, phase sequence, asymmetry, high voltage, low voltage and PTC faults.
The technical table gives the operating voltage range (85-300 V LN, 75-250 V LN, 145-520 V LL and 130-430 V LL, plus or minus 20%), 50/60 Hz frequency, voltage protection range (plus or minus 5% to 30% for low and high, or off), energisation delay (under 1 second), phase loss threshold (Un x 60%), asymmetry threshold (plus or minus 5-30% or off) and hysteresis (3%). Delay times are 2 seconds on activation; release time is 500 ms for phase loss, phase sequence and neutral break, 0.1 to 10 seconds for asymmetry and low/high voltage, and 1 second for PTC.
It also gives one C/O output contact (250 VAC / 5 A / 1250 VA or 30 VDC / 5 A / 150 W), overvoltage category CAT III, 2.5 mm2 copper conductor cross-section, 0.5 Nm tightening torque, power consumption under 13 VA, operating temperature of -20 to +60 degrees C and IP20 protection. The PTC fault is distinguished into two types: a high-value PTC fault and a short circuit between the PTC inputs T1-T3. The document is a product-specific sheet; settings are model-specific and should not be taken as universal design thresholds.
Key points
- 18 mm body, DIN-rail compatible, designed to TS EN 60255, TRMS measurement, microprocessor-based; 5 A SPDT relay output.
- Ten models in the selection table: star (3P4W) and delta (3P3W); fixed 230 V and 400 V and adjustable 100-200, 170-280, 175-345 and 295-480 V bands.
- On M1 models the lower and upper voltage limits are set as a percentage with one knob; on M2 models with separate knobs.
- Voltage protection range plus or minus 5% to 30% for low and high, or off; asymmetry threshold plus or minus 5-30% or off; phase loss threshold Un x 60%; hysteresis 3%.
- Fault delays: activation 2 s; release 500 ms for phase loss, phase sequence and neutral break, 0.1-10 s for asymmetry and low/high voltage, 1 s for PTC.
- Operating voltage ranges 85-300 V LN, 75-250 V LN, 145-520 V LL and 130-430 V LL (plus or minus 20%); frequency 50/60 Hz.
- Output contact 1 C/O, 250 VAC / 5 A / 1250 VA or 30 VDC / 5 A / 150 W; overvoltage category CAT III.
- The PTC fault is split into two types: high-value fault and short circuit between the T1-T3 PTC inputs.
- Terminal section 2.5 mm2 copper, tightening torque 0.5 Nm, power consumption below 13 VA, operating temperature -20 to +60 degrees C, IP20.
Using it in design
- Select the connection type (3P4W with neutral or 3P3W without) and nominal voltage band to suit the supply; on star models neutral break protection comes into play automatically.
- Set voltage and asymmetry thresholds per model to suit load tolerance; the ranges in the document (plus or minus 5-30%) are this relay's setting range, not universal design thresholds.
- Choose delay times (release 0.1-10 s) to fit overcurrent protection and supply coordination; keep the 500 ms release time for phase loss in mind.
- When choosing a PTC-input model for motor and equipment temperature protection, add to the commissioning checklist that the two PTC fault types (high value and short circuit) are reported separately.
- Match contact capacity (5 A, 250 VAC) to the contactor or alarm circuit and verify the CAT III and 2.5 mm2 terminal limits in the panel design.
Who should read it
Electrical engineers designing panels and motor/load protection circuits, and commissioning teams.
Document contents
- Fault types and LED indications
- Product selection table
- Technical specifications
- Fault descriptions: phase loss, neutral break, phase sequence, asymmetry, high and low voltage, PTC faults
Publication details
- Authors
- Klemsan
- Publisher
- Klemsan
- Year
- 2024
- Document number
- Rev.No.09122024
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. Facts use the legible English text and table; missing extraction cells were not filled.
Citation
Klemsan (2024). Adjustable Protection Relays / Ayarlanabilir Koruma Röleleri: TR/EN. Klemsan. Rev.No.09122024. https://klemsan.com.tr/wp-content/uploads/downloads/270283/Adjustable%20Protection%20Relays%2009122024-TR-EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.