Technical guideFree to read2026

Selecting the Standard for Periodic Inspection of Building Electrical Installations: Comparative Application of TS HD 60364-6, TS EN 50678 and TS EN 50699

Original title Bina Elektrik Tesisatlarının Periyodik Kontrolünde Standart Seçimi: TS HD 60364-6, TS EN 50678 ve TS EN 50699’un Karşılaştırmalı Uygulaması

TMMOB Elektrik Mühendisleri Odası

An article in EMO's Elektrik Muhendisligi issue 479 separates fixed-installation verification (TS HD 60364-6) from appliance testing (TS EN 50678, TS EN 50699), giving 1.0 MOhm (500 V DC) insulation and 300 ms RCD limits.

On this page

Overview

The article (A. F. Aydin, Elektrik Muhendisligi, issue 479, 2026) addresses the basic confusion in building electrical inspections: which standard applies to which equipment. Fixed components such as the main board, distribution boards, cable lines, socket circuits and earthing fall under TS HD 60364-6; post-repair appliance checks follow TS EN 50678, and periodic safety tests of appliances in use (PAT) follow TS EN 50699. The author stresses that the two lines must run in parallel.

For TS HD 60364-6 the test order is visual inspection, continuity and insulation resistance with the installation de-energised, then energising for loop impedance and RCD trip tests. Insulation resistance is expected to be at least 0.5 MOhm (250 V DC) for SELV/PELV circuits and at least 1.0 MOhm (500 V DC) for normal circuits up to 500 V. General-type RCDs must trip within 300 ms at rated residual current and 40 ms at five times; S-type limits are 130-500 ms and 50-150 ms. Instruments need TURKAK-accredited calibration and must meet the TS EN 61557 series.

TS EN 50699 covers plug-in or fixed-connected equipment above 25 V AC / 60 V DC and up to 1000 V AC / 1500 V DC, current up to 63 A; UPS, PV inverters, power converters, PLCs, EV charging stations and drives are out of scope. PAT intervals vary with class and environment: 3-6 months for hand-held Class I equipment in damp or dusty sites, 1-2 years for Class II equipment in offices. In Turkey the annual periodic inspection derives from the Work Equipment regulation, and findings are documented in ZPKR01 and ZPKR02 report formats.

The article also covers authorisation (electrical engineer, SMM certificate and chamber registration), a five-step inspection workflow, the point that continuous monitoring sensors do not replace periodic physical testing, and a comparison of Turkish and European/US models. In the school example a reading of 0.38 MOhm falls below the 1.0 MOhm limit, so the circuit must be marked as non-compliant.

Key points

  1. Fixed installation follows TS HD 60364-6, post-repair appliance checks TS EN 50678, periodic appliance testing (PAT) TS EN 50699.
  2. Test order: visual inspection, continuity, insulation resistance (de-energised), then loop impedance and RCD test (energised).
  3. Insulation resistance: at least 0.5 MOhm (250 V DC) for SELV/PELV, at least 1.0 MOhm (500 V DC) for circuits up to 500 V.
  4. General-type RCD: at most 300 ms at IDn and 40 ms at 5xIDn; S-type: 130-500 ms at IDn and 50-150 ms at 5xIDn; must not trip at 0.5xIDn.
  5. Instruments need calibration from a TURKAK-accredited laboratory and must conform to TS EN 61557.
  6. EN 50699 scope: above 25 V AC / 60 V DC, up to 1000 V AC / 1500 V DC, up to 63 A; UPS, PV inverters, PLCs and EV chargers are excluded.
  7. The general periodic inspection interval for low-voltage installations is 1 year; results are reported in ZPKR01 and ZPKR02 formats.
  8. According to the ISIG 2025 report, 95 of at least 2,105 workplace deaths were from electric shock.

Using it in design

  • Write the periodic verification plan for a data-centre electrical installation around the annual TS HD 60364-6 check, and keep the commissioning verification results as the baseline.
  • In acceptance-test specifications, add insulation resistance (500 V DC, at least 1.0 MOhm) and RCD trip times with their limits to the measurement table template.
  • Note that UPS, PV inverters and power converters are outside EN 50699 scope; define the manufacturer's maintenance and test procedure for them separately.
  • Require instrument calibration certificates and signing authority in the report requirements.
  • Plan continuous monitoring sensors as a layer that complements periodic physical tests, not one that replaces them.

Who should read it

Engineers carrying out electrical inspection and commissioning, safety officers, and designers writing specifications under Turkish regulation.

Document contents

  1. Introduction
  2. Conceptual distinction: installation or appliance?
  3. TS HD 60364-6: verification of fixed installations
  4. TS EN 50678 and TS EN 50699
  5. Authorisation and limits of responsibility
  6. Inspection workflow for buildings
  7. Legal framework and international comparison
  8. Conclusion

Publication details

Authors
TMMOB Elektrik Mühendisleri Odası
Publisher
TMMOB Elektrik Mühendisleri Odası
Year
2026
Document number
Elektrik Mühendisliği, Sayı 479, Ekim 2026
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher or university publicly accessible text; no open redistribution licence established. No named author was established on the opened publisher page; authors left empty. Normative numeric limits and legal authorisation claims are not copied.

Citation

TMMOB Elektrik Mühendisleri Odası (2026). Bina Elektrik Tesisatlarının Periyodik Kontrolünde Standart Seçimi: TS HD 60364-6, TS EN 50678 ve TS EN 50699’un Karşılaştırmalı Uygulaması. TMMOB Elektrik Mühendisleri Odası. Elektrik Mühendisliği, Sayı 479, Ekim 2026. https://emo.org.tr/emoyayin/makale/12827/bina-elektrik-tesisatlarinin-periyodik-kontrolunde-standart-secimi-ts-hd-60364-6

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.