Bahra TBS Cast Resin Transformers: Installation and Maintenance Guidelines

Bahra Electric (Bahra TBS)

The 42-page cast resin dry-type transformer catalogue from Bahra Electric (Bahra TBS) combines product selection tables with a detailed installation and maintenance section: standard installation is up to 1000 m altitude and 40 °C maximum cooling air temperature, transformers stand at least 0.5 m from walls, and insulation resistance before energising must be at least 20 MΩ between HV and LV.

On this page

Overview

The catalogue presents Bahra TBS cast resin dry-type distribution transformers from 100 kVA to 5000 kVA. The first chapters cover production technology, service conditions, protection against temperature rise and overvoltages, ventilation and vector groups, followed by product selection tables with losses, impedance, noise and dimensions. The dry-type construction contains no cooling fluid, so the units can be installed inside buildings and need little maintenance. For data centres the main value lies in the installation and maintenance guidelines that start on page 23.

The installation section calls for indoor installation in a clean, dry place protected from direct sunlight. Standard conditions are an altitude not above 1000 m and cooling air at a 20 °C yearly average, a 30 °C warmest-month average and a 40 °C maximum, in line with IEC 60076-11. The guide shows installation with a protection enclosure and without one (IP00) in separate figures. Minimum distances between live parts and connections are given by voltage class: at least 125 mm up to 12 kV, 170 mm up to 17.5 kV, 225 mm up to 24 kV and 320 mm up to 36 kV. HV and LV cables are always supported separately so that the terminals carry no mechanical stress.

For ventilation, a table gives the net bottom opening area needed against total losses in the room (kW) and the height difference between inlet and outlet openings, for example 1.9 m² for 10 kW of losses and 1 m height. Forced ventilation is needed when natural ventilation falls short, the room is small, the yearly average temperature exceeds 20 °C or overloads are frequent. Recommended temperature monitoring settings follow the insulation class: alarm 130 °C and trip 140 °C for class F, alarm 140 °C and trip 155 °C for class H. Standard transformers have five tappings on the HV winding, ±5% in 2.5% steps.

The commissioning section lists earthing, connection tightening torques, tapping position, cleaning and insulation resistance measurement. The measurement is made for 60 seconds with a megohmmeter working up to 5000 V: at least 20 MΩ between HV and LV, at least 10 MΩ between HV and earth, and at least 10 MΩ between LV and earth (at 2500 V). The maintenance table calls for testing the temperature sensors and protection relay every six months, cleaning the windings yearly or more often in dusty environments, and tightening bolts with a torque wrench yearly and after exceptional events. Catalogue values are manufacturer specific, and the documents of the actual transformer govern.

Key points

  1. Product range: cast resin dry-type transformers from 100 to 5000 kVA.
  2. Standard installation conditions: altitude not above 1000 m; cooling air 20 °C yearly average, 30 °C warmest-month average, 40 °C maximum (IEC 60076-11).
  3. Minimum insulation distances: 125 mm up to 12 kV, 170 mm up to 17.5 kV, 225 mm up to 24 kV, 320 mm up to 36 kV.
  4. Transformers are positioned at least 0.5 m from walls and from each other.
  5. The ventilation opening table is for a 15 °C temperature difference; example: 1.9 m² net area for 10 kW of losses and 1 m height difference.
  6. Recommended temperature settings: class B alarm 110 °C and trip 120 °C, class F 130 °C and 140 °C, class H 140 °C and 155 °C.
  7. Five standard tappings on the HV winding: ±5% in 2.5% steps; tappings are changed with the transformer de-energised.
  8. Insulation resistance (60 s): at least 20 MΩ HV to LV at 5000 V; at least 10 MΩ HV to earth at 5000 V; at least 10 MΩ LV to earth at 2500 V.
  9. Maintenance: temperature sensor and relay test every 6 months; winding cleaning yearly (dry compressed air at 3 bar maximum); bolt tightening yearly and after exceptional events.
  10. Temperature during storage and installation must not fall below -25 °C; a transformer stored for long in high humidity is dried before being placed in service.

Using it in design

  • Show on the layout drawing the 0.5 m minimum clearance to walls and neighbouring transformers and the insulation distance for the voltage class.
  • Size the air inlet and outlet openings from the table by total losses and height difference between openings, with an allowance for louvres or grids that reduce net area.
  • On sites where the yearly average temperature exceeds 20 °C, or with frequent overloads, provide forced ventilation or a thermostat-controlled extract fan at the outlet.
  • Design independent supports for HV and LV cables and busbars; use flexible busbar links on the LV side and specify a transition plate where copper meets aluminium.
  • Enter the alarm and trip settings of the temperature monitoring relay by insulation class and bring the signals into the building management system.
  • Add the insulation resistance acceptance values to the commissioning procedure and the 6-monthly and yearly checks to the maintenance plan, with record forms.

Who should read it

Electrical and mechanical engineers designing transformer rooms, commissioning teams and operations maintenance staff.

Document contents

  1. TBS Factory Overview
  2. Product Offer
  3. Why Bahra TBS Cast Resin Transformers?
  4. Bahra TBS Technology - High quality production
  5. Service conditions
  6. Protection against temperature rise
  7. Ventilation
  8. Protection against overvoltages
  9. Vectorial groups
  10. Product Selection
  11. Installation and Maintenance: Safety guidelines
  12. Rating plate
  13. Transport, receipt and storage
  14. Installation
  15. Commissioning
  16. Maintenance
  17. Technical glossary

Publication details

Authors
Bahra Electric (Bahra TBS)
Publisher
Bahra Electric (Bahra TBS)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bahra Electric (Bahra TBS) Bahra TBS Cast Resin Transformers: Installation and Maintenance Guidelines. Bahra Electric (Bahra TBS). https://bahra-electric.com/Downloads/BahraTBS_Transformers_Catalogue.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.