Compact Busways HE: Design, Installation and Technical Information

Bahra Electric · Bahra TBS

Bahra Electric's Bahra TBS Compact Busway HE catalogue describes a copper-conductor, epoxy-insulated, aluminium-cased busway system from 800 to 5000 A: IEC 61439-6 compliant, IP55, 1 s short-time withstand current of 50 to 150 kA and a joint tightening torque of 85 Nm.

On this page

Overview

The catalogue covers the compact busway family that Saudi-based Bahra Electric manufactures at its Bahra TBS factory. Bahra Electric acquired Transformers and Busways Solutions (TBS), set up in 2015 in partnership with Legrand France, in 2021 and uses the Legrand designs under licence. The system has copper conductors from 800 to 5000 A, epoxy insulation and an aluminium casing that also serves as the protective conductor. The standard protection degree is IP55 and insulation class is B; IP66 and class F are available on request. The range is type tested by LOVAG.

Most of the document is given to product selection: item codes for straight elements, feed units, elbows, T elements, tap-off boxes, hanger brackets and accessories. Straight elements have a standard length of 3 m, and distribution elements carry up to 5 tap-off outlets per side at 580 mm spacing. Tap-off boxes range from 63 to 1250 A and can be inserted and removed while the line is energised. The technical data tables give, for each rating, dimensions, short-circuit withstand, phase resistance, reactance, fault-loop impedance, voltage-drop coefficients and weight per metre.

The guidelines section covers measurement, project development and installation. For a special-length straight element, 285 mm is subtracted from the measured gap; for elbows, 72.5 mm is subtracted from each leg. The project checklist asks for the rating, the short-circuit current at the start of the line, the protection degree, the neutral section (100% standard, 200% optional), the ambient temperature (50 °C standard) and the PE cross-section. At the joint, the 285 mm distance between elements is verified and the monobloc bolt is tightened until its first head shears off; the nominal torque is 85 Nm.

The mechanical precautions section defines layout clearances: at least 300 mm from the wall for edgewise installation, at least 100 mm for access to the monobloc bolt, and at least 200 mm between a joint and a wall crossing. The technical information section explains Joule losses (three-phase Pj = 3 x Rt x Ib² x L / 1000), the overload condition (Ib ≤ In ≤ Iz), voltage-drop calculation for lines over 100 m, and short-circuit withstand. Ratings apply without derating across ambient temperatures of 35 to 55 °C, and mounting orientation does not change the rating. The values are specific to this system.

Key points

  1. Rated current 800...5000 A, copper conductors; single bar for 800...2500 A, double bar for 3200...5000 A; rated voltage 1000 V, 50/60 Hz.
  2. Overall dimensions run from 145 x 220 mm (800...1600 A) to 145 x 530 mm (5000 A).
  3. Rated short-time current (Icw, 1 s): 50 kA for 800 and 1000 A, 88 kA for 2000 and 2500 A, 150 kA for 3200...5000 A; peak current 105...330 kA.
  4. Phase resistance at thermal conditions: 0.051 mΩ/m at 800 A, 0.021 mΩ/m at 2500 A, 0.011 mΩ/m at 5000 A.
  5. Weight (standard): 23.70 kg/m at 800 A, 51.80 kg/m at 2500 A, 101.80 kg/m at 5000 A.
  6. Joint assembly: 285 mm between elements; nominal tightening torque of the shear-head bolt 85 Nm; the completed joint is IP55.
  7. Clearances: 300 mm from the wall for edgewise mounting, 100 mm for the monobloc bolt, 200 mm between a joint and a wall crossing.
  8. Minimum element size dimension X with a plug-in tap-off box: 500 mm for 63...160 A boxes, 720 mm for 250...630 A boxes.
  9. Operating ambient -5...55 °C; ratings are unchanged from 35 to 55 °C, and the 5000 A size is not offered at 60 °C.
  10. Voltage drop is checked on lines longer than 100 m; the current distribution factor b ranges from 1 to 1/8 depending on supply point and load distribution.

Using it in design

  • Calculate busway heat loss with Pj = 3 x Rt x Ib² x L / 1000, using the resistance at thermal conditions and working trunk by trunk; add the result to the hall cooling load.
  • Compare the prospective short-circuit current at the start of the line with the Icw and peak values of the selected rating, and check the separate withstand values for neutral and PE.
  • In route drawings provide 300 mm from walls, 100 mm for bolt access and 200 mm between a joint and a wall crossing; check the open-cover dimension of tap-off boxes separately.
  • Verify Ib ≤ In ≤ Iz in the protection settings; apply the diversity and utilisation coefficients and the supply factor d when calculating Ib.
  • For lines over 100 m, calculate voltage drop with the catalogue formula and the appropriate b factor; feed the line at an intermediate point where needed.
  • Use weight per metre for support steel and hanger calculations (101.80 kg/m at 5000 A); do not apply these values as a general rule to other manufacturers' systems.

Who should read it

Electrical engineers designing high-current busway distribution, project teams preparing route and support details, and installation contractors.

Document contents

  1. Bahra TBS Factory Overview
  2. Product Offer: Technical Details
  3. Product Offer: Elements and Accessories Overview
  4. Bahra TBS Busway Advantages
  5. Product Selection: Item codes (Busway Element & Accessories)
  6. Technical Data
  7. Guidelines: Measurement, Project Development, Design & Installation
  8. Technical Information (Joule effect losses, Overload Protection, Voltage drop, Short Circuit Withstand)

Related standards

  • IEC 61439-6

Publication details

Authors
Bahra TBS
Publisher
Bahra Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bahra TBS Compact Busways HE: Design, Installation and Technical Information. Bahra Electric. https://bahra-electric.com/Downloads/BahraTBS_Busway_HE_Catalogue.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.