A Bidirectional Gated Recurrent Unit Model for PUE Prediction in Data Centers
arXiv preprint (National University of Singapore) · Dhivya Dharshini Kannan, Anupam Trivedi et al.
A preprint developing a BiGRU neural network to predict data centre PUE and comparing it with a standard GRU; because the data are simulated, the very high accuracy is not field validation.
On this page
Overview
The study develops a BiGRU neural network to predict data centre PUE and compares it with a standard GRU. Training data come from a one-year EnergyPlus simulation of the example data centre model with Singapore weather at 10-minute steps: 52,560 samples with 117 features. The data are therefore simulator output, not metered field data.
Feature selection uses recursive feature elimination with cross-validation (RFECV) with XGBoost, choosing subsets of 21-43 variables covering outdoor conditions, IT power, UPS and CRAC/cooling-coil variables, with hyperparameters tuned for each set. RFECV selected sets of {21, 28, 29, 32, 33, 43} features with the minimum MSE. The 21 features include outdoor dry-bulb, dew-point and wet-bulb temperature, ITE CPU, fan and UPS electric power, air volume flow, CRAC total power, net sensible capacity and SCOP, and cooling-coil power and outlet temperature.
The BiGRU with 21 features gave the lowest error: MAE 0.00038 (MSE 5.6342e-7, R2 0.99673), while the GRU performed best with 28 features (MAE 0.0004181). The paper recalls that Google's neural-network PUE model achieved an MAE of 0.004 +/- 0.005 for a PUE of 1.1, and that Singapore guidance requires new data centres to have a PUE of 1.3 or below at 100 percent IT load.
The key limit is that the data are simulated: the very high accuracy reflects the regularity of the simulator, not field validation. The model is a surrogate of the simulator and should be validated against metered data before being used for guarantees. The document is a preprint, not a peer-reviewed publication. ISO/IEC 30134-2 is named as the related standard.
Key points
- Dataset: one-year EnergyPlus simulation with 2009 Singapore weather at 10-minute intervals, giving 52,560 samples with 117 features.
- RFECV selected feature sets of {21, 28, 29, 32, 33, 43} features with the minimum MSE.
- The 21 features include outdoor dry-bulb, dew-point and wet-bulb temperature, IT CPU, fan and UPS power, air flow, CRAC power, net sensible capacity and SCOP, and coil power and outlet temperature.
- BiGRU with 21 features achieved the lowest MAE of 0.00038 (MSE 5.6342e-7, R2 0.99673); GRU did best with 28 features (MAE 0.0004181).
- Cited Singapore guidance requires new data centres to have a PUE of 1.3 or below at 100 percent IT load.
- Prior work cited: Google's neural-network PUE model achieved an MAE of 0.004 +/- 0.005 for a PUE of 1.1.
Using it in design
- For an operations or digital-twin study, use the feature list as a practical minimum sensor set for PUE prediction: outdoor dry/wet-bulb, IT power, UPS power, CRAC power/capacity/SCOP, coil temperatures and airflow.
- Treat ML PUE models trained on simulation as surrogates of the simulator and validate against metered data before using them for guarantees.
- Keep regional PUE limits (e.g. Singapore 1.3 at full IT load) in the metrics/compliance catalogue.
Who should read it
Operations engineers and data scientists building digital twins and energy forecasting.
Related standards
- ISO/IEC 30134-2
Publication details
- Authors
- Dhivya Dharshini Kannan; Anupam Trivedi; Dipti Srinivasan
- Publisher
- arXiv preprint (National University of Singapore)
- Year
- 2025
- Document number
- arXiv:2512.20161
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- arXiv distribution permission: reuse conditions remain with the rights holder
Original licence note
arXiv default non-exclusive distribution licence; citation only
Citation
Dhivya Dharshini Kannan; Anupam Trivedi; Dipti Srinivasan (2025). A Bidirectional Gated Recurrent Unit Model for PUE Prediction in Data Centers. arXiv preprint (National University of Singapore). arXiv:2512.20161. https://doi.org/10.48550/arXiv.2512.20161
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.