Modeling Liquid-Cooled Data Centers in EnergyPlus
arXiv (author manuscript) · Yun-Dam Ko, Dipashreya A. Sur et al.
Ko et al. (arXiv 2610.33148, October 2026) add a direct-to-chip liquid cooling object to EnergyPlus; warm-water cooling cuts annual PUE from 1.43 to 1.25 and facility energy by 37.9%.
On this page
Overview
The paper says AI workloads are moving data centres to high-density racks with direct-to-chip (DTC) liquid cooling, while existing simulation tools remain limited in evaluating whole-building and multi-year efficiency. To bridge this gap the authors develop a native EnergyPlus object, ElectricEquipment:ITE:LiquidCooled. The object models chilled-water and warm-water architectures as plant-loop components and couples facility-water loops, rack-side secondary loops, coolant distribution units and chip-junction temperatures within a single solver.
Validation is against an independent Modelica implementation across 21 operating conditions, including two full-year runs compared at one-minute resolution. Loop-temperature RMSE is at or below 0.021 K, well within the 0.1 K acceptance threshold. The case study shows that warm-water liquid cooling reduces annual PUE from 1.43 to 1.25, eliminates on-site water use and cuts total facility energy by 37.9% relative to an air-cooled baseline. By embedding liquid-cooling logic in EnergyPlus the work provides whole-building, long-term energy modelling for high-density AI infrastructure within an open-source framework. The paper has 14 pages, 7 figures and 6 tables; code is public.
Key points
- New EnergyPlus object: ElectricEquipment:ITE:LiquidCooled (DTC liquid cooling as a plant-loop component).
- Couples chilled-water and warm-water architectures, facility-water loop, rack-side secondary loop, CDU and chip-junction temperatures in one solver.
- Validation: 21 operating conditions against an independent Modelica implementation; two full-year runs at one-minute resolution.
- Loop-temperature RMSE is at or below 0.021 K; acceptance threshold 0.1 K.
- Case study: warm-water liquid cooling reduces annual PUE from 1.43 to 1.25.
- On-site water use is eliminated; total facility energy falls 37.9% against the air-cooled baseline.
Using it in design
- Model the annual energy of liquid-cooled facilities with the new EnergyPlus object to compare warm-water and chilled-water architectures.
- Compute the design PUE target next to the air-cooled reference; the case study shows a fall from 1.43 to 1.25.
- Define facility-water temperature, CDU approach temperature and chip-junction temperature limits as model inputs.
- Cross-check model results against an independent implementation or measurement; loop-temperature deviation should stay below the 0.1 K threshold.
Who should read it
Designers and researchers doing whole-building energy modelling of liquid-cooled data centres.
Publication details
- Authors
- Yun-Dam Ko; Dipashreya A. Sur; Cade Napier; Carlos D. Díaz-Marín; Rishee K. Jain
- Publisher
- arXiv (author manuscript)
- Year
- 2026
- Document number
- arXiv:2610.33148v1
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Article-specific arXiv view-license link grants arXiv a non-exclusive distribution right; this is not general commercial redistribution permission.
Citation
Yun-Dam Ko; Dipashreya A. Sur; Cade Napier; Carlos D. Díaz-Marín; Rishee K. Jain (2026). Modeling Liquid-Cooled Data Centers in EnergyPlus. arXiv (author manuscript). arXiv:2610.33148v1. https://doi.org/10.48550/arXiv.2610.33148
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.