Research paperFree to read2026

Modeling Liquid-Cooled Data Centers in EnergyPlus

arXiv (author manuscript) · Yun-Dam Ko, Dipashreya A. Sur et al.

Ko et al. (arXiv 2610.33148, October 2026) add a direct-to-chip liquid cooling object to EnergyPlus; warm-water cooling cuts annual PUE from 1.43 to 1.25 and facility energy by 37.9%.

On this page

Overview

The paper says AI workloads are moving data centres to high-density racks with direct-to-chip (DTC) liquid cooling, while existing simulation tools remain limited in evaluating whole-building and multi-year efficiency. To bridge this gap the authors develop a native EnergyPlus object, ElectricEquipment:ITE:LiquidCooled. The object models chilled-water and warm-water architectures as plant-loop components and couples facility-water loops, rack-side secondary loops, coolant distribution units and chip-junction temperatures within a single solver.

Validation is against an independent Modelica implementation across 21 operating conditions, including two full-year runs compared at one-minute resolution. Loop-temperature RMSE is at or below 0.021 K, well within the 0.1 K acceptance threshold. The case study shows that warm-water liquid cooling reduces annual PUE from 1.43 to 1.25, eliminates on-site water use and cuts total facility energy by 37.9% relative to an air-cooled baseline. By embedding liquid-cooling logic in EnergyPlus the work provides whole-building, long-term energy modelling for high-density AI infrastructure within an open-source framework. The paper has 14 pages, 7 figures and 6 tables; code is public.

Key points

  1. New EnergyPlus object: ElectricEquipment:ITE:LiquidCooled (DTC liquid cooling as a plant-loop component).
  2. Couples chilled-water and warm-water architectures, facility-water loop, rack-side secondary loop, CDU and chip-junction temperatures in one solver.
  3. Validation: 21 operating conditions against an independent Modelica implementation; two full-year runs at one-minute resolution.
  4. Loop-temperature RMSE is at or below 0.021 K; acceptance threshold 0.1 K.
  5. Case study: warm-water liquid cooling reduces annual PUE from 1.43 to 1.25.
  6. On-site water use is eliminated; total facility energy falls 37.9% against the air-cooled baseline.

Using it in design

  • Model the annual energy of liquid-cooled facilities with the new EnergyPlus object to compare warm-water and chilled-water architectures.
  • Compute the design PUE target next to the air-cooled reference; the case study shows a fall from 1.43 to 1.25.
  • Define facility-water temperature, CDU approach temperature and chip-junction temperature limits as model inputs.
  • Cross-check model results against an independent implementation or measurement; loop-temperature deviation should stay below the 0.1 K threshold.

Who should read it

Designers and researchers doing whole-building energy modelling of liquid-cooled data centres.

Publication details

Authors
Yun-Dam Ko; Dipashreya A. Sur; Cade Napier; Carlos D. Díaz-Marín; Rishee K. Jain
Publisher
arXiv (author manuscript)
Year
2026
Document number
arXiv:2610.33148v1
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Article-specific arXiv view-license link grants arXiv a non-exclusive distribution right; this is not general commercial redistribution permission.

Citation

Yun-Dam Ko; Dipashreya A. Sur; Cade Napier; Carlos D. Díaz-Marín; Rishee K. Jain (2026). Modeling Liquid-Cooled Data Centers in EnergyPlus. arXiv (author manuscript). arXiv:2610.33148v1. https://doi.org/10.48550/arXiv.2610.33148

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.