Research paperFree to read2026

Co-Design Optimization for Data Center Cooling System via Digital Twin

arXiv (author manuscript) · Shrenik Jadhav, Zheng Liu

Jadhav and Liu (arXiv 2605.15516, ASME JESBC 2026) show that a two-subloop design for Frontier's 25 CDUs saves 35.48% of annual cooling energy.

On this page

Overview

The paper notes that cooling plants of liquid-cooled exascale supercomputers are organised as multiple parallel subloops, but how to allocate coolant distribution units (CDUs) across subloops and how to distribute flow among them has not been addressed systematically at this scale. The proposed three-layer optimisation framework jointly determines the integer partition of CDUs across subloops, the continuous flow fraction allocation and the per-timestep co-design of total flow rate and supply temperature under per-subloop thermal safety constraints.

The Modelica simulation model is built on data from the Frontier exascale supercomputer at Oak Ridge National Laboratory. With a reduced-order surrogate model, all 611 feasible partitions of 25 CDUs are evaluated over a full-year operational dataset of 49,353 timesteps. Three strategies are compared, from flow control optimisation to full three-layer co-design. The best design is a two-subloop plant achieving 35.48% annual cooling energy savings, only 0.18% above the current three-subloop design at 35.30%. Most savings come from supervisory co-optimisation of total flow rate and supply temperature; flow fraction optimisation adds design robustness rather than extra raw savings.

Flow fraction optimisation compensates for any feasible CDU-to-subloop assignment, reducing design sensitivity by 93% and giving a low-cost software-only path to near-optimal performance on the existing Frontier hardware. The framework is transferable to other liquid-cooled high-performance computing plants. The paper is accepted by the ASME Journal of Engineering for Sustainable Buildings and Cities, 19 pages with 8 figures; arXiv version 4 (6 August 2026).

Key points

  1. Subject: partitioning CDUs into subloops and distributing flow in liquid-cooled exascale plants.
  2. The model is built on Frontier data at Oak Ridge; 611 feasible partitions of 25 CDUs are evaluated over a full year of 49,353 timesteps.
  3. The best design is a two-subloop plant: 35.48% annual cooling energy savings.
  4. The current three-subloop design saves 35.30%; the difference is 0.18%.
  5. Most savings come from joint supervisory optimisation of total flow rate and supply temperature.
  6. Flow fraction optimisation reduces design sensitivity by 93%.

Using it in design

  • In large liquid-cooled plants compare CDU count and subloop partition against annual operating data; note the small savings gap (0.18%) between two and three subloops.
  • Plan a supervisory control layer that optimises total flow and supply temperature together; most savings come from it.
  • Treat flow fraction tuning as a software-based robustness measure against imbalance between subloops.
  • Define thermal safety constraints per subloop and run the optimisation under them.

Who should read it

Engineers and researchers designing cooling plants and controls for large liquid-cooled HPC and AI facilities.

Publication details

Authors
Shrenik Jadhav; Zheng Liu
Publisher
arXiv (author manuscript)
Year
2026
Document number
arXiv:2605.15516v4
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY-NC-SA 4.0: share with attribution for noncommercial purposes under the same licence
Original licence note

Article-specific arXiv view-license link is CC BY-NC-SA 4.0; commercial redistribution is not authorized.

Citation

Shrenik Jadhav; Zheng Liu (2026). Co-Design Optimization for Data Center Cooling System via Digital Twin. arXiv (author manuscript). arXiv:2605.15516v4. https://doi.org/10.48550/arXiv.2605.15516

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.