StandardFree to read2021

Emergence and Expansion of Liquid Cooling in Mainstream Data Centers

ASHRAE TC 9.9

This 2021 ASHRAE TC 9.9 white paper urges mainstream facilities to plan for liquid cooling as CPU/GPU power rises and allowable case temperatures fall. It introduces the high-density air class H1 and the renamed W facility-water classes.

On this page

Overview

The paper brings two classification changes. For high-density air-cooled ITE it defines class H1: allowable 15-25 degC and recommended 18-22 degC. Facility-water classes are renamed by their upper supply limit: W17 (was W1), W27 (W2), W32 (W3), W40 (new), W45 (W4) and W+ (W5), all with a 2 degC lower limit. The limits of air cooling are put in numbers.

Server fans can consume up to about 20% of server power, which in a 50 kW rack is at least 5 kW. A 40-50 kW rack can need about 5,000 cfm while the best-in-class perforated tile passes about 1,900 cfm, so beyond a certain density a single raised-floor tile is physically insufficient. The energy section states liquid cooling can bring PUE below 1.1, and a case study using warm water (40-45 degC) with absorption chilling reached a cooling pPUE under 0.07.

The key planning warning is that facilities running W32 today may have to move to W27 as chip power rises, hence the recommendation to design new data centers to accommodate liquid cooling later. It is a classification and planning white paper; it does not give detailed hydraulic design or CDU sizing. For context it also cites A1 allowable maximum 32 degC and A4 maximum 45 degC, and should be read with the 5th edition of ASHRAE Thermal Guidelines and the Liquid Cooling Guidelines.

Key points

  1. Class H1: allowable 15-25 degC, recommended 18-22 degC.
  2. Liquid classes: W17 (was W1), W27 (W2), W32 (W3), W40 (new), W45 (W4), W+ (W5); all with 2 degC lower limit.
  3. Server fans can use up to about 20% of server power; at least 5 kW in a 50 kW rack.
  4. A 40-50 kW rack can need about 5,000 cfm; best-in-class perforated tile about 1,900 cfm.
  5. Liquid cooling can bring PUE below 1.1; 40-45 degC water with absorption chilling gave cooling pPUE under 0.07 in a case study.
  6. Facilities on W32 today may need to move to W27 as chip power rises.
  7. Context: A1 allowable max 32 degC, A4 max 45 degC.

Using it in design

  • Assess thermal class H1 and facility-water classes W17/W27/W32/W40/W45/W+ separately when selecting liquid cooling.
  • Above about 1,900 cfm per rack (about 12-15 kW at 20 degF dT) one tile is not enough; require containment, in-row cooling or liquid.
  • Add a 'liquid-ready' option that reserves pipe routes, CDU space and room for W32 or colder water.
  • Check facility-water capacity against a move down to W27, not just the first chip generation.

Who should read it

Thermal and mechanical designers preparing an air-cooled facility for liquid cooling or planning a new one.

Related standards

  • ASHRAE Thermal Guidelines for Data Processing Environments 5th ed.
  • ASHRAE Liquid Cooling Guidelines for Datacom Equipment Centers
  • ASHRAE 90.4

Publication details

Authors
ASHRAE TC 9.9
Publisher
ASHRAE TC 9.9
Year
2021
Document number
TC 9.9 White Paper
Document language
English
Source type
Standard
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

ASHRAE TC 9.9 (2021). Emergence and Expansion of Liquid Cooling in Mainstream Data Centers. ASHRAE TC 9.9. TC 9.9 White Paper. https://www.ashrae.org/File%20Library/Technical%20Resources/Bookstore/Emergence-and-Expansion-of-Liquid-Cooling-in-Mainstream-Data-Centers_WP.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.