Technical guideFree to read2025

AquaForce 30XF Air-Cooled Variable-Speed Screw Chiller Designed for Data Centers

Carrier

The Carrier AquaForce 30XF brochure presents a data-centre chiller with up to 50% energy savings from full hydronic free cooling, 60-120 s recovery to full load and a 5% THDi harmonic filter option.

On this page

Overview

Carrier's AquaForce 30XF is an air-cooled variable-speed screw chiller prepared for data centres. The brochure highlights the new-generation 06Z variable-speed twin-screw compressor, a permanent-magnet motor, a microchannel air-side heat exchanger and the SmartVU control system. A built-in active harmonic filter and hydraulic kit reduce the need for external components at installation.

Free cooling uses the natural temperature difference between outdoor air and water, and 100% hydronic free cooling is stated to deliver up to 50% energy savings. Data-centre capabilities include ultra-fast capacity recovery after a power outage: 60 seconds to 100% load on single-circuit units and 120 seconds on dual-circuit and duplex units. Options are also offered for working with an ATS (automatic transfer switch) and generators.

In the R134a and R513A versions (30XF), nominal cooling capacity runs from 738 kW to 2,519 kW. IDC1 and IDC2 conditions give separate capacity and power values, and capacity at IDC2 (45 °C ambient) is lower than at IDC1. Both R134a and R513A are AHRI-certified.

R134a and R513A operating range: water inlet 6.8-30 °C and outlet 3.3-20 °C in operation; ambient -20 to 50 °C (part load). Glycol or a frost protection option is mandatory when the fluid goes below 4 °C. The control box is IP54, and options include Modbus, BACnet, J-Bus and Lon gateways, dual power supply and energy metering. The active harmonic filter option limits THDi to 5%.

Key points

  1. 30XF (R134a/R513A) nominal capacity 738-2,519 kW.
  2. IDC1 and IDC2 conditions give separate values and are not interchangeable.
  3. Capacity tables are AHRI-certified for R134a and R513A.
  4. Version codes: A R134a, C R513A, Z R1234ze(E).
  5. Ultra-fast capacity recovery: 100% load in 60 seconds on single-circuit units and 120 seconds on dual-circuit and duplex units.
  6. Up to 50% energy savings are claimed for 100% hydronic free cooling.
  7. The active harmonic filter option limits THDi to 5%.
  8. Refrigerants: R1234ze(E), R513A and R134a.
  9. Glycol or frost protection is required when the temperature goes below 4 °C, and the same applies when ambient air falls below 0 °C.

Using it in design

  • Evaluate capacity separately at IDC1 and IDC2; for hot-climate design use the 45 °C ambient value.
  • Verify capacity recovery time (60 or 120 seconds) together with UPS and generator transfer times after a power loss.
  • Assess the free-cooling option against water temperatures and the annual ambient profile; 50% is the manufacturer's upper-bound claim, so calculate for the site profile.
  • Treat harmonic filter and ATS options together with the electrical single-line diagram and generator sizing.
  • Specify glycol percentage or frost protection for low ambient and for water below 4 °C.
  • Select the BACnet or Modbus option for BMS integration.

Who should read it

Data-centre mechanical designers selecting air-cooled chillers and decision makers on cooling infrastructure.

Document contents

  1. About Carrier
  2. Data-centre optimisation
  3. AquaForce 30XF
  4. Model description and options
  5. Operating range
  6. Designed to meet data-centre requirements
  7. Technical specifications

Related standards

  • EN 61800-3

Publication details

Authors
Carrier
Publisher
Carrier
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor product brochure; no open licence stated

Citation

Carrier (2025). AquaForce 30XF Air-Cooled Variable-Speed Screw Chiller Designed for Data Centers. Carrier. https://www.carrier.com/commercial/en/vn/media/Carrier%2030XF%20Data%20Center%20Chillers%20301225_tcm193-244180.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.