Project Profile: Data Center in Frankfurt (Germany) - AquaForce 30XF air-cooled screw chillers with integrated free cooling

Carrier

Carrier's Frankfurt data-centre project profile describes 38 AquaForce 30XF air-cooled screw chillers of up to 1,795 kW each, with integrated 100% free cooling.

On this page

Overview

This 2024 Carrier project profile covers a new-build data centre in Frankfurt, Germany. Sound level, limited space and a high efficiency target all shaped the design. Carrier supplied 38 AquaForce 30XF air-cooled screw chillers; each unit delivers up to 1,795 kW cooling chilled water from 24.4 °C to 16.6 °C at 39 °C outdoor temperature.

The chillers run in three modes: compressor only, free cooling only, or a combination. Free cooling uses an internal glycol circuit, while the customer's circuit runs on plain water, which avoids the heat-transfer penalty of glycol. Frequency-controlled operation improves part-load efficiency and sound level.

V-shaped condensers fit about 1,800 kW into a 16.7 x 2.3 m footprint. The main control cabinet holds harmonic filters in a separate compartment, limiting harmonics to under 5%. Power factor is 0.98. An option restores power within 190 seconds after an outage, supporting service continuity.

The document is a customer application story. It has no measured annual energy, PUE or free-cooling hours. It notes that options developed at the customer's request have become standard in the new product.

Key points

  1. 38 AquaForce 30XF air-cooled screw chillers supplied.
  2. Capacity up to 1,795 kW per unit, at 39 °C ambient and 24.4 to 16.6 °C chilled water.
  3. Three modes: compressor only, free cooling only, combined.
  4. Free cooling uses an internal glycol circuit; the customer loop uses plain water.
  5. About 1,800 kW in a 16.7 x 2.3 m area with V-condensers.
  6. Harmonic filters limit harmonics below 5%; power factor 0.98.
  7. Power can be restored 190 seconds after an outage with an option.
  8. Frequency-controlled operation gives part-load efficiency and low sound level.

Using it in design

  • When selecting free-cooling chillers, check the separation between the plain-water loop and the internal glycol circuit, and the exchanger loss, in the data sheet.
  • On sound- and space-limited sites, use the density of about 1,800 kW per 16.7 x 2.3 m as a benchmark.
  • Tie the 190-second power restoration time to chilled-water storage and UPS-backed control power for continuity.
  • Use the harmonic limit (under 5%) and the 0.98 power factor as inputs to grid connection and generator studies.
  • Compare the 39 °C rating condition with the project design ambient.

Who should read it

Data-centre mechanical designers choosing between air-cooled chillers and free-cooling solutions.

Document contents

  1. Project objective
  2. A brand-new data centre site
  3. Features of the delivered units

Publication details

Authors
Carrier
Publisher
Carrier
Year
2024
Document number
EN032024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

©2024 Carrier. All Rights Reserved

Citation

Carrier (2024). Project Profile: Data Center in Frankfurt (Germany) - AquaForce 30XF air-cooled screw chillers with integrated free cooling. Carrier. EN032024. https://carrier.com/commercial/en/uk/media/case-studies-data-center-frankfurt-en_tcm217-230744.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.