Project Profile: Data Center in Frankfurt (Germany) - AquaForce 30XF air-cooled screw chillers with integrated free cooling
Carrier
Carrier's Frankfurt data-centre project profile describes 38 AquaForce 30XF air-cooled screw chillers of up to 1,795 kW each, with integrated 100% free cooling.
On this page
Overview
This 2024 Carrier project profile covers a new-build data centre in Frankfurt, Germany. Sound level, limited space and a high efficiency target all shaped the design. Carrier supplied 38 AquaForce 30XF air-cooled screw chillers; each unit delivers up to 1,795 kW cooling chilled water from 24.4 °C to 16.6 °C at 39 °C outdoor temperature.
The chillers run in three modes: compressor only, free cooling only, or a combination. Free cooling uses an internal glycol circuit, while the customer's circuit runs on plain water, which avoids the heat-transfer penalty of glycol. Frequency-controlled operation improves part-load efficiency and sound level.
V-shaped condensers fit about 1,800 kW into a 16.7 x 2.3 m footprint. The main control cabinet holds harmonic filters in a separate compartment, limiting harmonics to under 5%. Power factor is 0.98. An option restores power within 190 seconds after an outage, supporting service continuity.
The document is a customer application story. It has no measured annual energy, PUE or free-cooling hours. It notes that options developed at the customer's request have become standard in the new product.
Key points
- 38 AquaForce 30XF air-cooled screw chillers supplied.
- Capacity up to 1,795 kW per unit, at 39 °C ambient and 24.4 to 16.6 °C chilled water.
- Three modes: compressor only, free cooling only, combined.
- Free cooling uses an internal glycol circuit; the customer loop uses plain water.
- About 1,800 kW in a 16.7 x 2.3 m area with V-condensers.
- Harmonic filters limit harmonics below 5%; power factor 0.98.
- Power can be restored 190 seconds after an outage with an option.
- Frequency-controlled operation gives part-load efficiency and low sound level.
Using it in design
- When selecting free-cooling chillers, check the separation between the plain-water loop and the internal glycol circuit, and the exchanger loss, in the data sheet.
- On sound- and space-limited sites, use the density of about 1,800 kW per 16.7 x 2.3 m as a benchmark.
- Tie the 190-second power restoration time to chilled-water storage and UPS-backed control power for continuity.
- Use the harmonic limit (under 5%) and the 0.98 power factor as inputs to grid connection and generator studies.
- Compare the 39 °C rating condition with the project design ambient.
Who should read it
Data-centre mechanical designers choosing between air-cooled chillers and free-cooling solutions.
Document contents
- Project objective
- A brand-new data centre site
- Features of the delivered units
Publication details
- Authors
- Carrier
- Publisher
- Carrier
- Year
- 2024
- Document number
- EN032024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
©2024 Carrier. All Rights Reserved
Citation
Carrier (2024). Project Profile: Data Center in Frankfurt (Germany) - AquaForce 30XF air-cooled screw chillers with integrated free cooling. Carrier. EN032024. https://carrier.com/commercial/en/uk/media/case-studies-data-center-frankfurt-en_tcm217-230744.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.