Constant Power Loads

Caterpillar

A Caterpillar technical paper explains that constant-power loads draw more current as voltage falls and compares constant-power and constant-impedance loads for generator voltage response and load acceptance.

On this page

Overview

This Caterpillar technical paper compares the consequences of constant-power loads and constant-impedance loads for generator voltage response and load acceptance. The central point is that a constant-power load draws more current as voltage decreases.

The paper's concluding qualification states that simulation results represent approximate behaviour rather than guaranteed equipment performance. Load model choice therefore needs careful treatment in generator sizing.

Key points

  1. Constant-power loads draw more current as voltage decreases.
  2. The paper compares constant-power and constant-impedance loads.
  3. The comparison focuses on consequences for generator voltage response and load acceptance.
  4. Simulation results represent approximate behaviour, not guaranteed equipment performance.

Using it in design

  • Do not model loads with constant-power behaviour, such as UPS and power supplies, as constant-impedance loads in generator voltage dip and load acceptance analysis.
  • In generator sizing, allow for the rising current draw as voltage falls.
  • Read simulation results as approximate behaviour, not firm guarantees, and confirm with the manufacturer.

Who should read it

Electrical engineers sizing generators and UPS systems together.

Related standards

  • ISO 8528-5

Publication details

Authors
Caterpillar
Publisher
Caterpillar
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Publisher landing page opened with TinyFish on 2026-11-16. No explicit open licence or commercial redistribution grant was displayed in the retrieved page; retained as metadata and original summary only. Free access or a download button is not permission to redistribute. Publisher page opened successfully; summary and facts are limited to visible page content. Document year omitted when not explicitly established. License evidence: https://www.cat.com/en_US/by-industry/electric-power/Articles/White-papers/constant-power-loads.html

Citation

Caterpillar Constant Power Loads. Caterpillar. https://www.cat.com/en_US/by-industry/electric-power/Articles/White-papers/constant-power-loads.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.