CISA/DOE Insights: Mitigating Attacks Against Uninterruptible Power Supply Devices
Cybersecurity and Infrastructure Security Agency (CISA) · Cybersecurity and Infrastructure Security Agency (CISA), U.S. Department of Energy
A two-page joint CISA and DOE alert of 29 March 2022 reporting that threat actors accessed internet-connected UPS devices, often through unchanged default credentials, and giving concrete actions.
On this page
Overview
The two-page joint CISA and DOE alert reports that threat actors gained access to internet-connected UPS devices, often via unchanged default usernames and passwords. UPS loads range from a few servers to whole buildings and data centres, and responsibility may sit with IT, facilities or third-party monitoring vendors.
The primary action is to enumerate all UPSs and similar systems and ensure they are not reachable from the internet. Where remote access is unavoidable, use VPN, multifactor authentication and strong passphrases per NIST guidance. Change factory-default credentials and use login timeout and lockout features. It is a short but pointed reminder that power-chain equipment is part of the attack surface.
Key points
- Threat actors accessed internet-connected UPS devices, often via unchanged default usernames and passwords.
- UPS loads range from a few servers to whole buildings and data centres; responsibility may sit with IT, facilities or a third-party monitoring vendor.
- Primary action: enumerate all UPSs and similar systems and ensure they are not reachable from the internet.
- Where remote access is unavoidable, use VPN, multifactor authentication and strong passphrases per NIST guidance.
- Change factory-default credentials and use login timeout and lockout features.
Using it in design
- Inventory all UPS management interfaces (network card, SNMP, web) and verify at commissioning that they are not reachable from the internet.
- Make changed default credentials on UPS network cards an acceptance condition.
- If remote monitoring is needed, design it with VPN and multifactor authentication and name the responsible party (IT, facilities or third party).
- Keep the UPS management network in a separate segment and standardise session timeout and account lockout settings.
Who should read it
Engineers and security managers who design, operate and monitor data centre electrical and UPS systems.
Related standards
- NIST SP 800-82 Rev. 3
- IEC 62443
Publication details
- Authors
- Cybersecurity and Infrastructure Security Agency (CISA); U.S. Department of Energy
- Publisher
- Cybersecurity and Infrastructure Security Agency (CISA)
- Year
- 2022
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- U.S. public domain: U.S. Government work; free to reuse
Original licence note
U.S. federal government work (CISA/DOE). Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Cybersecurity and Infrastructure Security Agency (CISA); U.S. Department of Energy (2022). CISA/DOE Insights: Mitigating Attacks Against Uninterruptible Power Supply Devices. Cybersecurity and Infrastructure Security Agency (CISA). https://www.cisa.gov/sites/default/files/2023-01/cisa-doe_insights-mitigating_vulnerabilities_affecting_uninterruptible_power_supply_devices_mar_29.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.