CITEC G-Volution PRO catalogue, printed pp.18-22
Original title CITEC G-Volution PRO catalogue, printed pp.18–22
CITEC
Printed pages 18-22 of the CITEC G-Volution PRO catalogue give capacity tables for the room-type precision cooling family: EZ/EV DX models (24 °C/45% return air, 45 °C condensing) and EZ/EF chilled-water models (7/12 °C water).
On this page
Overview
The published model tables for CITEC's current room-type precision cooling family G-Volution PRO fall into two groups: the direct-expansion EZ/EV series and the chilled-water EZ/EF series. In the DX tables gross capacity is given at 24 °C and 45% relative humidity return air with 45 °C condensing temperature. The chilled-water tables are for 7/12 °C water; for EF models downflow and upflow values are given separately.
The document is image-based; the tables hold total and sensible capacity in separate columns and the two must not be mixed. The tables show catalogue rating points, not design conditions; if the room condition differs, capacity must be confirmed with the manufacturer.
Key points
- EZ/EV DX tables give gross capacity at 24 °C/45% return air and 45 °C condensing temperature.
- EZ/EF chilled-water tables are for 7/12 °C water.
- EF models have separate downflow and upflow values.
- Total and sensible capacity must be read from separate columns.
- The document is image-based; DX and chilled-water model tables are on printed pp.18-22.
Using it in design
- For DX models compare capacity with the 24 °C/45% return air and 45 °C condensing condition; request a correction if the site outdoor temperature is high.
- For chilled-water models have capacity recalculated if the planned regime differs from 7/12 °C water.
- Base the load calculation on sensible capacity; do not use total capacity in place of sensible.
- For EF models downflow and upflow, choose the correct value.
Who should read it
Mechanical designers selecting room-type precision cooling and data-hall planners.
Publication details
- Authors
- CITEC
- Publisher
- CITEC
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CITEC CITEC G-Volution PRO catalogue, printed pp.18–22. CITEC. https://citecinternational.com/pdf/products/gv/CITEC_G-Volution-Pro-Catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.