Research paperPDF2026

A few-shot learning framework for HVAC fault diagnosis in data centers with minimal data required

Applied Energy / Elsevier; Fraunhofer Publica · Ke Yan, Changfu He et al.

An open-access paper proposing a learning method that classifies chiller and air handling unit (AHU) faults in newly commissioned data centres where neither labelled nor unlabelled operating data exist yet.

CC BY 4.0: share with attribution

On this page

Overview

The paper addresses the period when a new data centre's IT and HVAC systems are settling into an energy balance in their new configuration. During that period HVAC equipment may run at full capacity for a long time, which raises the risk of faults, yet existing data-driven diagnosis methods expect plenty of either labelled or unlabelled operating data. The authors state this is the first study to tackle the case where both kinds of data are scarce.

The proposed method, called SSAWPN, has two parts. A multi-scale attentive feature fusion network (MSAFN) uses channel-wise segmentation, residual connections and attention to capture fault signatures at several temporal and spatial scales. A semi-supervised adaptive weighted prototype optimisation strategy (SAWPS) gives adaptive weights to unlabelled observations so that class prototypes are refined as data accumulate, without manual annotation.

Experiments use two benchmark datasets: a centrifugal chiller with eight health states (normal plus seven faults: reduced condenser and evaporator water flow, refrigerant leakage and overcharge, excess oil, condenser fouling, non-condensables), four severity levels and 64 measured variables; and an AHU dataset with seven faults plus normal operation and 19 selected features. Data scarcity is simulated by randomly drawing 60 samples per health state and running 3-shot and 5-shot tasks.

SSAWPN reaches a mean F1 of 73.77% on the chiller severity-level-1 set and 67.22% on the AHU summer set, which is 3.21 and 1.35 points above the second-best method. The ablation study shows MSAFN contributes more than SAWPS. The limits are stated plainly: computational complexity is not yet optimised, the study uses clean labelled fault samples (noisy labels would degrade results), and the method has not yet been tested on a real building management system.

Key points

  1. Published in Applied Energy vol. 402 (2026), article 127056; available online 14 November 2025 under a CC BY licence.
  2. Scarce-data scenario: 60 randomly selected samples per health state; tasks set up as 3-shot and 5-shot.
  3. The chiller dataset has 8 health states (normal + 7 faults), 4 severity levels (SL1 subtlest and hardest to diagnose) and 64 measured variables.
  4. The AHU dataset covers summer, winter and spring data; each season has 7 faults plus normal operation, with 19 features used.
  5. Mean F1: 73.77% on chiller SL1 and 67.22% on AHU summer, +3.21 and +1.35 points over the runner-up.
  6. With one unlabelled sample per class, chiller accuracy rises to 74.57%, against 71.63% with no unlabelled samples.
  7. A scaling factor δ of 0.8 was found to be the best value.
  8. In ablation, the baseline prototype network scores 73.00% on 3-shot average and full SSAWPN 75.57%; on 5-shot, 72.78% versus 75.52%.
  9. A conventional CNN trails SSAWPN by up to 34.05 points on scarce data.

Using it in design

  • In the commissioning period of a new hall, do not expect a classifier-based fault diagnosis to work from day one without labelled fault history; include in the BMS points list the temperature, flow and power channels for chillers and AHUs of the kind used in the paper.
  • When writing a fault-detection specification for chillers and AHUs, use the seven typical fault classes (reduced condenser/evaporator water flow, refrigerant leakage, condenser fouling and so on) as the coverage list.
  • Consider higher sensor resolution and sampling rate at design stage for low-severity (SL1) faults, which the paper shows are the hardest class; diagnosis gets easier as severity grows.
  • When procuring diagnosis software, ask the vendor to demonstrate starting performance with little data and how it learns (prototype updating) as operating data accumulate.
  • Position the model output as decision support in operating procedures; the paper notes the method has not yet been validated on a real building management system and is sensitive to label noise.

Who should read it

Data-centre mechanical and BMS designers, operations and commissioning engineers, and teams evaluating fault-diagnosis software.

Document contents

  1. Introduction (background, literature, key challenges and contribution)
  2. Theoretical knowledge (semi-supervised few-shot learning, prototype networks, attention mechanism)
  3. Proposed method (fault diagnosis framework, MSAFN, SAWPS)
  4. Experiments (datasets, ablation, comparative experiments)
  5. Conclusion and future work

Read the document

apenergy-2026-few-shot-hvac-diagnosis.pdf

PDF · 4.3 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Ke Yan; Changfu He; Chuan Wang; Yuan Gao; Yang Du; Afshin Afshari
Publisher
Applied Energy / Elsevier; Fraunhofer Publica
Year
2026
Document number
402, 127056
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
api.crossref.org
Original licence note

Creative Commons Attribution 4.0 International; licence verified from the Crossref licence metadata. Attribution to the authors and publisher is kept.

Citation

Ke Yan; Changfu He; Chuan Wang; Yuan Gao; Yang Du; Afshin Afshari (2026). A few-shot learning framework for HVAC fault diagnosis in data centers with minimal data required. Applied Energy / Elsevier; Fraunhofer Publica. 402, 127056. https://doi.org/10.1016/j.apenergy.2025.127056

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.